Product description
EK1960
22
Version: 1.3.1
3.6.1
Technical data – relay option
Product designation
EK1960-260x
Contacts
1 NO / 1 NC
Make contact material (NO)
AgNi + 0.2 µm Au
Feedback contact material (NC)
AgNi + 5 µm Au
Coil voltage
24V
DC
Maximum continuous current, NO contact
(when used in safety applications)
DC13 (24 V
DC
) I = 2 A
AC15 (230 V
AC
) I = 3 A
Maximum switching current (NO contact)
8 A
Minimum switching current (NO contact)
10 mA (AgNi)
Switching capacity according to IEC/EN
60947-5-1
AC15
DC13
250 V
AC
/ 3 A
24 V
DC
/ 2 A
Switching frequency (maximum)
20 switching cycles / s
Response time
≤ 15 ms (typically 10 ms)
Release time
≤ 5 ms (typically 2 ms)
NOTE
Allowed loads of the relay option
The potential-free contacts of the relay option (X4) may only be connected to resistive and inductive loads.
Capacitive loads are not permissible.
Load limit curve
Fig. 3: Load limit curve, make contact