Error handling and diagnostics
CXxxxx-B110
50
Version: 1.3
6
Error handling and diagnostics
6.1
Diagnostic LEDs
These LEDs are used for fieldbus diagnostics.
Display
LED
Display State
Description
Link/Act
Link/Act
Link/Act
green
off
-
No connection on the EtherCAT strand
on
linked
EtherCAT device connected
flashing active
Communication with EtherCAT device
Display
LED
Color
Meaning
RUN
green
OP mode
flashing (green) 200 ms
on/off
PRE-OP mode
flashing (green) 200 ms
on/ 1000 ms off
SAFE-OP mode
off
INIT mode
ERR
off
OK
red
not configured