Installation Instructions 

 

 
 

Connecting 24V

DC

 Power Supply 

 

The external wiring consists of the connection of the power supply, the 
battery pack (optional) and the connection of customized components for 
shutting down the PC. 

 

Cable Cross Sections 

Note cable cross sections, 
avoid voltage drop!  

For the connection of the power supply, wiring  with a cable-cross-section 
of 1.5 mm

 must be used.  

With bigger distances between voltage source and PC, you take the 
voltage drop as a function of the cable-cross-section as well as voltage 
fluctuations of your distribution voltage into account, so that is secured that 
the voltage doesn't fall under 22 V at the power supply.  

 

Insert fuse 

 

Attention 

The power supply must be protected with maximum 16 A. 

 

 

Configuration for shutting down the PC 

 

The connections for shutting down the Industrial PCs are established via 
the 

PC_ON

 input and the 

Power Status

 output.  

 

PC_ON and Power Status functions 

 

• 

If the 

PC_ON

 input is connected to 24 V via a switch, the PC shuts 

down according to the rules. The PC_ON signal is inverted, i.e. the PC 
shuts down if the 24 V connection is live. 

• 

If the 

PC_ON

 input is 

NOT

 connected by the user, the PC can be 

booted in the familiar way by connecting the supply voltage and shut 
down via the battery by switching off the supply voltage. 

 

Service life of the rechargeable battery 

 

Attention 

This procedure significantly reduces the service life of the rechargeable 
battery and should therefore not be used. 

 

 

• 

Once the PC has shut down, the 

Power Status

 output is switched from 

24 V to 0 V. Via this output a signal lamp can be connected or a 
contactor for de-energizing the whole system. The maximum load for 
the 

Power Status

 output is 0.5 A and a suitable fuse should be 

provided. 

 
 
 

C6240-1007 

17 

Содержание C6240-1007-0060

Страница 1: ...Installation and Operating instructions for Control Cabinet Industrial PC C6240 1007 from 0060 Version 2 0 Date 2018 02 16 ...

Страница 2: ......

Страница 3: ...uctions 11 Transport and Unpacking 11 Transport 11 Unpacking 11 Installation of the PC in the control cabinet 12 Earthing measures 12 Power Supply Connection with 100 240 VAC power supply unit 13 Mains Socket 13 Power supply cords 13 Power Supply Connection with 24 VDC power supply unit 14 Beckhoff power supply technology 14 Electrical Data 15 Connecting the power supply 15 Power Switch 15 Fitting...

Страница 4: ...and Service 24 Beckhoff branches and partner companies 24 Beckhoff company headquarters 24 Beckhoff Support 24 Beckhoff Service 24 Assembly dimensions 25 Configuration with 100 240 VAC Power Supply 25 Configuration with 24 VDC Power Supply optional 26 Appendix 27 Technical data 27 Approvals 27 FCC Federal Communications Commission 27 Radio Frequency Interference Statement 27 FCC Canadian Notice 27...

Страница 5: ...XFC are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners Patent Pending The EtherCAT Technology is covered including but not limited to the following patent applications and patents EP1590927 EP1789857 DE102004044764 DE102007017835 ...

Страница 6: ...ls Risk of injury WARNING If you do not adhere the safety advise adjoining this symbol there is danger to life and health of individuals Hazard to individuals CAUTION If you do not adhere the safety advise adjoining this symbol there is obvious hazard to individuals Hazard to devices and environment Attention If you do not adhere the notice adjoining this symbol there is obvious hazard to material...

Страница 7: ...ant Pulling out the fieldbus connection plug uncouples the PC optional Items of equipment that have been switched off must be secured against being switched on again The Industrial PC s power supply unit must be supplied with 100 VAC 240 VAC or 24 VDC optional Do not open the power supply unit while voltage is applied DANGER The supply voltage must be switched off before the power supply unit hous...

Страница 8: ...e National regulations depending on the machine type Depending on the type of machine and plant in which the Industrial PC is being used there will be national regulations for the control of such machines and plant that the operator must observe These regulations cover amongst other things the intervals between inspections of the controller The operator must initiate such inspections in good time ...

Страница 9: ... Opening the Housing Front view of C6240 1007 configuration with 100 240 VAC power supply 2 1 1 Front view of C6240 1007 configuration with 24 VDC power supply optional Opening the housing After solving the two screws 1 the upper housing cover 2 can now be tilted upwards thus providing access to the drives 3 inch hard disk processor memory and plug in cards 2 1 1 C6240 1007 7 ...

Страница 10: ...e shows the optional configuration of the PC with a removable hard disk drawer 1 for one Serial ATA hard disk drive and a slimline CD DVD ROM drive 2 instead of the standard CD DVD ROM drive The connections of the Industrial PC are located at the front of the housing removable hard disk drawer for one Serial ATA hard disk optional card holders slimline CD DVD ROM drive optional 100 240 VAC full ra...

Страница 11: ...er supply unit optional with UPS Front view of the PC The picture shows the optional configuration of the PC with a multi DVD drive 1 instead of the standard CD DVD ROM drive The connections of the Industrial PC are located at the front of the housing multi DVD drive optional instead of CD DVD ROM drive card holders 24 VDC power supply fanless with UPS optional 3 hard disk 7 slot ATX motherboard f...

Страница 12: ...007 0060 are equipped with 2 USB2 0 X110 X111 and 2 USB3 0 X108 X109 interfaces Devices with Intel 6th and 7th generation processors C6240 1007 0070 are equipped with 4 USB3 0 interfaces Network connection LAN1 The RJ 45 connector X112 allows the PC to be connected to a 10 100 1000BASE T Local Area Network LAN LAN2 The RJ 45 connector X113 allows the PC to be connected to a 10 100 1000BASE T Local...

Страница 13: ...emperature make sure that moisture condensation does not form on or inside the device Prior to operation the unit must be allowed to slowly adjust to room temperature Should condensation occur a delay time of approximately 12 hours must be allowed before the unit is switched on Unpacking Proceed as follows to unpack the unit 1 Remove packaging 2 Do not discard the original packaging Keep it for fu...

Страница 14: ... the housing must be at least 5 cm in order to ensure adequate ventilation of the PC Avoid extreme environmental conditions Attention Extreme environmental conditions should be avoided as far as possible Protect the PC from dust moisture and heat The ventilation slots of the PC must not be covered Earthing measures Earthing measures Earthing connections dissipate interference from external power s...

Страница 15: ...ousing mains socket Power supply cords Power cords Europe In the area Europe you use the provided cable with inlet connector for non heating apparatus to connect the Industrial PC to the power supply Power cords USA Canada In the area USA Canada the power supply cable must show the following specifications according to the supply voltage Listed Detachable maximum 4 5 m 14 76 ft long rated minimum ...

Страница 16: ...imply turning off the supply voltage In this case the PC shuts down via the battery However over time this reduces the service life of the battery The new Beckhoff power supply technology approach addresses this problem and now offers the user the option of switching the PC off without the need for using the battery thereby reducing the load on the battery In addition to the main switch this innov...

Страница 17: ...ta Input voltage 22 30 V DC Current consumption 10 A 22 V Output capacity 150 W max Current carrying capacity of the 24 V power supply unit Output voltages from the 24 V power supply unit Current loading maximum 5 V 14 A 5 V 0 3 A 12 V 12 A 12 V 0 5 A 3 3 V 12 A 5 V VSB 1 5 A Connecting the power supply A 5 pin male plug connector with CAGE CLAMP connection see photo is installed at the PC housing...

Страница 18: ...lief housing A B C D Fitting the connector Fitting the connector to the cable The plug is fitted to the cable as follows 1 Strip insulation from the cable ends insulation length 8 9 mm 2 Push the conductors into their mountings simply by pushing them in as indicated on the pin assignment label 3 Push the lower part part A of the strain relief housing onto the top of the female plug connector until...

Страница 19: ... PC The connections for shutting down the Industrial PCs are established via the PC_ON input and the Power Status output PC_ON and Power Status functions If the PC_ON input is connected to 24 V via a switch the PC shuts down according to the rules The PC_ON signal is inverted i e the PC shuts down if the 24 V connection is live If the PC_ON input is NOT connected by the user the PC can be booted i...

Страница 20: ... diagram the circuit of PC_ON and Power Status is symbolical Wiring diagram external switch and power supply Connection of the Battery Pack and UPS Output Note Connection of the Battery Pack and UPS Output only in combination with integrated UPS order option 18 C6240 1007 ...

Страница 21: ...to the devices that are to be connected Connect all data transfer cables if present to the appropriate plug in receptacles of the data telecommunication networks Reconnect all devices to the power supply Check voltage rating and connect When fitted with 115 VAC 60 Hz 230 VAC 50 Hz power supply 1 Check that the mains voltage is correct 2 Insert the provided power supply cable into the Industrial PC...

Страница 22: ...g a file to the hard disk the file will be destroyed Control software typically writes something to the hard disk every few seconds so that the probability of causing damage by switching off while the software is running is very high Switch off power supply Attention When you have shut down the Industrial PC you have to switch off power supply for at least 10 seconds before rebooting the system Af...

Страница 23: ...ry only with the identical type or an alternative type recommended by the manufacturer Notice correct polarity Handling of Lithium Batteries WARNING Lithium Batteries should not be recharged exposed to fire opened and they should be protected against sunlight and moisture The used battery must be disposed of in accordance with national electronics scrap regulations Emergency procedures In case of ...

Страница 24: ...he driver CD provided Installation on the PC Installation To install the UPS driver software execute file Beckhoff_UPS_vx xx xx exe from the subdirectory of UPS from the CD provided on the Industrial PC Driver archive for the Industrial PC C9900 S700 xxxx The program is self extracting and will guide the user through the installation routine Help files Beckhoff Information System The driver softwa...

Страница 25: ... press any key Check the setup settings Call Beckhoff Service Computer boots software starts but control does not operate correctly Cause of the fault is either in the software or in parts of the plant outside the Industrial PC Call the manufacturer of the machine or the software Memory device access error Faulty disk or CD Faulty device Check disk or CD in another drive Call Beckhoff Service The ...

Страница 26: ... 33415 Verl Germany Phone 49 0 5246 963 0 Fax 49 0 5246 963 198 e mail info beckhoff com Web http www beckhoff de Beckhoff Support Beckhoff offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with wide ranging services worldwide support design programming and commissioning of complex automation systems training program fo...

Страница 27: ...he following pages show diagrams of the Industrial PC with dimensions in mm Configuration with 100 240 VAC Power Supply Assembly orientation Attention The assembly of the unit must take place with the orientation diagrammed here C6240 1007 25 ...

Страница 28: ...Assembly dimensions Configuration with 24 VDC Power Supply optional Assembly orientation Attention The assembly of the unit must take place with the orientation diagrammed here 26 C6240 1007 ...

Страница 29: ...Transport and storage The same values for atmospheric humidity and shock resistance are to be observed during transport and storage as in operation The shock resistance during transport can be improved by means of suitably packing the Industrial PC The ambient temperature during storage and transport must be between 20 C and 65 C Approvals FCC Federal Communications Commission Radio Frequency Inte...

Отзывы: