Basic information 

 

BK8000 

15 

Communication errors 

The top four LEDs show the operating states of RS485 communication. 
The two bottom LEDs indicate local communication between the bus 
coupler and bus terminals (as explained above).  
 

 

There is nevertheless a relationship between the bottom green I/O RUN 
LED and RS485 communication when the bus coupler is switched to the 
'Synchronous mode'. Then, the I/O RUN LED only lights up in connection 
with access to the internal K bus, i.e. the green I/O RUN LED does not light 
up until data transfer is commenced via the RS 485 connection. This 
means that the bus coupler must be accessed. This relationship does not 
apply in the bus coupler's default setting (Freerun). In this status, the I/O 
RUN LED is independent of the communication status of the serial 
communication link. The 4 communication LEDs indicate the status of RS 
485 transfer. The operating states are indicated by the „WD“, „RX“, „TX“ 
and „ERROR“ LEDs. 
 

 

WD
RX
TX
ERROR

RS 485

 

 

LED 

 

Operating state 

WD 

Off 

A watchdog timer overflow has occurred. No data is 
exchanged with the coupler during the set watchdog 
time.  

RX 

Flashing, 
flickering 

 

Data is being received from the bus coupler via the 
interface.  

TX 

Flashing, 
flickering 

Data is being transceived from the bus coupler via the 
serial interface. 

ERROR 

Lit 

A data transfer error has occurred (e.g. parity error). 

 

 

The green I/O LED lights up in connection with access to the internal K 
bus. However, the bus coupler queries the configuration of the bus 
terminals after switching on and does not exchange any data with the 
terminals. That is to say, the red I/O LED goes off after an error-free 
startup without the green I/O LED having to light up. Then, the green I/O 
LED does not light up until data transfer is commenced (see above).  
 

 

Содержание BK8000

Страница 1: ...Bus coupler with RS485 interface BK8000 Technical Documentation Version 1 2 2006 10 30...

Страница 2: ...Connection 8 K bus contacts 8 Supply isolation 8 The operating modes of the bus coupler 9 Mechanical construction 10 Electrical data 10 The peripheral data in the process image 12 Starting operation...

Страница 3: ...cked for consistency with performance data standards or other characteristics None of the statements of this manual represents a guarantee Garantie in the meaning of 443 BGB of the German Civil Code o...

Страница 4: ...ed and nullify the liability of Beckhoff Automation GmbH Description of safety symbols The following safety symbols are used in this documentation They are intended to alert the reader to the associat...

Страница 5: ...ventional terminal as the cabling level in the switch cabinet the switch cabinet can be made smaller The Beckhoff bus terminal system combines the advantages of a bus system with the functionality of...

Страница 6: ...isolation Potential input terminal Power contacts RS485 bus coupler BK8000 Power supply for the bus coupler X1 X10 Bus couplers for various fieldbus systems You can use a variety of bus couplers to at...

Страница 7: ...ith spring terminals can be used to supply power to the peripherals The spring terminals are connected in pairs to the power contacts The power supply to the power contacts has no connection to the po...

Страница 8: ...xchange of data between the bus coupler and the bus terminals Part of the data exchange takes place via a ring structure within the K bus Disengaging the K bus for example by pulling on one the bus te...

Страница 9: ...to test the attached bus terminals the bus terminal test and read in the configuration from which it constructs an internal structure list which is not accessible from outside If an error occurs the b...

Страница 10: ...can remove them without effort if you first release the latching mechanism by pulling the orange tab You should carry out work on the bus terminals and the bus coupler only while they are switched off...

Страница 11: ...disconnect other power supply points for the duration of the test by drawing the power supply terminals out from the remaining row of terminals by at least 10mm If you do this there will be no need to...

Страница 12: ...e oriented The processing of analog signals is always byte oriented and analog input and output values are stored in memory in a two byte representation The values are held as SIGNED INTEGER or twos c...

Страница 13: ...s no contradictions is said to be consistent The following consistency is required here 1 The high byte and low byte of an analog value word consistency 2 The control status byte and the corresponding...

Страница 14: ...he pattern of flashes as follows Flashing code Fast flashingq Start of the error code First slow sequence Error code Second slow sequence Error argument Error code Error argument Description 1 pulse 0...

Страница 15: ...the serial communication link The 4 communication LEDs indicate the status of RS 485 transfer The operating states are indicated by the WD RX TX and ERROR LEDs WD RX TX ERROR RS 485 LED Operating sta...

Страница 16: ...hed from the PC s serial interface to the bus coupler This OCX can be used by all programming languages that operate on the basis of the Microsoft Component Object Model COM specifications You will fi...

Страница 17: ...ned from Beckhoff RS 485 transmission Fundamental characteristics of physical data transmission per RS 485 Network topology Linear bus active bus terminator at both ends stubs are possible Medium Scre...

Страница 18: ...0 operates as the master and the slave bus coupler must be assigned the address 1 Request In the request the master sends the process output data to be transferred to the slave In the response the sla...

Страница 19: ...INTEL format The checksum is generated by adding up the contents of the individual bytes complete response string without checksum byte Any occurring overflow is ignored Status byte of the bus coupler...

Страница 20: ...ock Bus terminal 0 1 None POS06 KL3002 Channel 1 2 3 None POS06 KL3002 Channel 2 4 0 POS01 KL1002 Channel 1 4 1 POS01 KL1002 Channel 2 4 2 POS02 KL1002 Channel 1 4 3 POS02 KL1002 Channel 2 4 4 POS03 K...

Страница 21: ...70 p Start identifier Byte 3 0x05 3 input data words Byte 4 0x12 Returned message ident Byte 5 0x00 Master address 0 Byte 6 0x Status byte Byte 7 0xXX Data byte 0 Byte 8 0xXX Data byte 1 Byte 12 0xXX...

Страница 22: ...l input POS17 2 channel digital input POS18 2 channel digital output POS19 2 channel digital output POS20 2 channel analog output POS21 End terminal In the default settings RS485 RS232 CANopen DevicNe...

Страница 23: ...Area for bit oriented data digital inputs Relative byte address Bit position Process image in the control unit Position in the block 4 0 I4 POS02 4 1 I4 POS02 4 2 I4 POS03 4 3 I4 POS03 4 4 I4 POS04 4...

Страница 24: ...t significant bits are irrelevant Using the KS2000 configuration software it is possible to insert the third byte into the process image for any chosen channels The least significant byte has control...

Страница 25: ...econdary process image This representation is not available in the bus coupler s default setting The KS2000 software is needed The meanings of the registers and of the status bytes are explained in th...

Страница 26: ...here Beckhoff Headquarters Beckhoff Automation GmbH Eiserstr 5 33415 Verl Germany phone 49 0 5246 963 0 fax 49 0 5246 963 198 e mail info beckhoff com web www beckhoff com Beckhoff Support Support off...

Отзывы: