Product overview
BC8050 und BC8150
13
Version: 3.0.0
2.4.2
Technical data - RS485
Fig. 2: BC8050
System data
RS485 (BC8050)
Protocols
• Address 1-39 serial ADS)*, KS8000 protocol (automatic recognition of
the protocol and the baud rate (9600, 19200, 38400 baud, fixed data
frame, 8 data bits, even parity, one stop bit)
• Address 40-59 ModbusRTU (fixed baud rate 1200, 2400, 4800,
9600
,
19200, 38400, DEFAULT 9600 baud, 8 bit data, optionally even, odd,
no
default no parity)
Number of I/O modules
32 (99 with repeater)
Number of I/O points
depending on controller
Data transfer medium
shielded copper cable 2 x 0.25 mm², cable type A according to EN 50 170
Segment length
up to 1200 m
Data transfer rate
1200 - 38400 baud
Topology
RS485 line
Transmission time
depending on protocol and baud rate
)* only via the configuration interfaces, not via RS485.