Programming
BC3150
72
Version: 2.1.0
5.12.2.5
System information type
TYPE SYSTEMINFOTYPE
STRUCT
runTimeNo : BYTE;
projectName : STRING(32);
numberOfTasks : BYTE;
onlineChangeCount : UINT;
bootDataFlags : BYTE;
systemStateFlags : WORD;
END_STRUCT
END_TYPE
Key
runTimeNo: indicates the number of the runtime system (1).
projectName: project name as STRING.
numberOfTasks: number of tasks contained in the runtime system (max. 1).
onlineChangeCount: number of online changes since the last complete download.
bootDataFlags: Reserved
systemStateFlags: Reserved.
Development environment
Target platform
PLC libraries to be linked
TwinCAT v2.9.0
BCxx50, BC9x20 Controller
TcBaseBCxx50.lbx
5.12.2.6
ADS
5.12.2.6.1
Local ADS Port Numbers
Port number
Description
dec
Reading and writing of registers and tables from the coupler and the complex Bus
Terminals
dec
Local PLC process image
5.12.2.6.2
ADS services
Local process image task 1 port 800 or 801
Data can be read from and written to the local process image. If it is necessary for outputs to be written, it is
important to ensure that they are not used by the local PLC, because the local controller will overwrite these
values. The data are not associated with a watchdog, and therefore must not be used for outputs that would
have to be switched off in the event of a fault.
Index group
Meaning
Index offset (value range)
0xF020
Inputs
0...2047
0xF030
Outputs
0...2047
0x4020
Flags
0...4095
ADS services
AdsServerAdsState
Data type (read only)
Meaning
String
Start - the local PLC is running
Start - the local PLC is stopped
Содержание BC3150
Страница 1: ...Documentation BC3150 Bus Terminal Controller for PROFIBUS DP 2 1 0 2017 07 11 Version Date...
Страница 2: ......
Страница 45: ...Parameterization and Commissioning BC3150 45 Version 2 1 0 Fig 41 Sample for entering associated bytes...
Страница 57: ...Programming BC3150 57 Version 2 1 0 Fig 55 Build...
Страница 87: ...PROFIBUS BC3150 87 Version 2 1 0 Fig 78 RS485 topology with 3 segments and 2 repeaters...