Parameterization and Commissioning
BC5250
32
Version: 2.0.0
The current configuration is loaded onto the Bus Terminal Controller. The display will show
Store Config
, and
the BUS and I/O LED will flash. Once the configuration is successfully loaded onto Bus Terminal Controller,
TwinCAT Config
should appear in the display of a BXxx00. The corresponding program can now be
transferred to the Bus Terminal Controller (program-download via the fieldbus).
4.2.4
Uploading a TwinCAT configuration
The TwinCAT configuration is loaded into the Bus Terminal Controller via ADS protocol.
Serial ADS protocol
(all Bus Terminal Controllers of the BCxx50, BCxx20 and BXxx00 series)
Enter the serial ADS connection, as described in the chapter
ADS protocol via the fieldbus
(BC3150, BC5150, BC9x20, BC9050, BX3100, BX5100, BX9000 only)
A prerequisite is that TwinCAT operates as master and is engaged in data exchange, i.e. the physical and
fieldbus configuration must be complete, and data exchange must take place between the master
(e.g. fieldbus card) and the Bus Terminal Controller.
Choose Target System
Select the Bus Terminal Controller onto which the configuration is to be loaded. Use the function key [F8] to
open the dialog for downloading your file to the corresponding device.
Fig. 24: Choose Target System
Select the corresponding Bus Terminal Controller.