Beckett AF104WH Скачать руководство пользователя страница 9

 

Beckett 

Instruction Manual – 

Model AF Oil Burner

Startup & adjust burner 

 

 Service & maintain burner 

Perform regular maintenance 

Startup burner/set combustion 

 

   Do not attempt to start the burner when excess fuel or vapor 

has accumulated in the appliance.  Starting the burner under these conditions 
could result in a puffback of hot combustion gases, high smoke levels, or 
otherwise hazardous operation. 

WARNING 

   

      This equipment must be serviced only by a qualified service 

agency.  The appropriate test instruments must be used.  Failure to do so 
could result in burner or appliance failure, causing potential severe personal 
injury, death or substantial property damage. 

WARNING 

1.  Open the shutoff valves in the oil supply line to the burner. 

 

Replace the oil supply line filter.  The line filter cartridge must be replaced 

to avoid contamination of the fuel unit and nozzle. 

2.  Close air band and partially open air shutter.  This is an initial air setting 

for the pump bleeding procedure only.

   

Additional adjustments must be 

made with instruments. 

 

Inspect the oil supply system.  All fittings should be leak-tight.  The supply 

lines should be free of water, sludge and other restrictions. 

3.  Set the thermostat substantially above room temperature. 

 

Remove and clean the pump strainer if applicable. 

4.  Close the line voltage switch to start the burner.  If the burner does not 

start immediately you may have to reset the safety switch of the burner 
primary control. 

 

Replace the nozzle with an equivalent nozzle. 

 

Clean and inspect the electrodes for damage, replacing any that are 

cracked or chipped. 

 

Check electrode tip settings.  Replace electrodes if tips are rounded. 

5. 

Bleed air from the fuel unit

 as soon as burner motor starts rotating. 

 

Inspect the igniter spring contacts. 

To bleed the fuel unit, attach a clear plastic hose over the vent fitting.  
Loosen the fitting and catch the oil in an empty container.  Tighten the 
fitting when all air has been purged from the oil supply system. 

 

Clean the cad cell grid surface, if necessary. 

 

Inspect all gaskets.  Replace any that are damaged or would fail to seal 

adequately. 

• 

If the burner locks out on safety during bleeding, reset the safety 

switch and complete the bleeding procedure.  Note — Electronic 
safety switches can be reset immediately; others may require a three- 
to five-minute wait. 

 

Clean the blower wheel, air inlet, retention head and static plate of any lint 

or foreign material. 

 

If motor is not permanently lubricated, oil motor with a few drops of SAE 

20 nondetergent oil at each oil hole.  DO NOT over oil motor.  Excessive 
oiling can cause motor failure. 

• 

If burner stops after flame is established, additional bleeding is 

probably required.  Repeat the bleeding procedure until the pump is 
primed and a flame is established when the vent fitting is closed. 

 

Check motor current.  The Amp draw should not exceed the nameplate 

rating by more than 10%. 

• 

For R7184 primary controls, see 

Technician’s Quick Reference Guide

Beckett part number 61351, for special pump priming sequence. 

 

Check all wiring for secure connections or insulation breaks. 

 

Check the pump pressure and cutoff function. 

• 

Prepare for combustion tests by drilling a ¼" sampling hole in the flue 

pipe between the appliance and the barometric draft regulator. 

 

Check primary control safety lockout timing. 

 

Check ignition system for proper operation. 

6. 

Initial air adjustment

 — Using a smoke tester, adjust the air shutter (and 

air band, if necessary) to obtain a clean flame.  Now the additional 
combustion tests with instruments can be made 

 

Inspect the vent system and chimney for soot accumulation or other 

restriction. 

 

Clean the appliance thoroughly according to the manufacturer's 

recommendations. 

Set combustion with instruments 

 

Check the burner performance.  Refer to the section “

Set combustion 

with instruments

”. 

                 The  combustion  must  be  adjusted  using  test  instruments.  

Failure to do so could result in burner or appliance failure, causing potential 
severe personal injury, death or substantial property damage. 

WARNING 

It is good practice to make a record of the service performed and the 
combustion test results. 

1.  Let burner run for approximately 5 to 10 minutes. 
2.  Set the over-fire or stack draft to level specified by appliance manufacturer 

(usually –0.01 to –0.02 inches w.c. over-fire for natural draft applications). 

To replace the blower wheel: 

1.  Turn off all power to the burner before servicing. 

3.  Follow these four steps to properly adjust the burner: 

2.  Disconnect the burner motor wires. 

Step 1: 

Adjust air until a trace smoke level is achieved. 

3.  Remove the bolts securing the blower motor to 

the housing. 

Step 2: 

At the trace of smoke level, measure the CO

2

 (or O

2

). This is 

the vital reference point for further adjustments. 

4.  Remove the blower motor and wheel. 

• 

Example: 13.5% CO

2

 (2.6% O

2

5.  Remove the existing wheel. 

Step 3: 

Increase the air to reduce CO

2

 by 1 to 2 percentage points. (O

2

 

will be increased by approximately 1.4 to 2.7 percentage points.) 

6.  As shown at right, slide the new blower wheel 

onto the shaft. 

• 

Place a .125" (1/8" ± 1/32") feeler gauge on 

the motor as shown. 

• 

Example: Reduce CO

2

 from 13.5% to 11.5%. (O

2

 – 2.6% to 5.3%) 

Step 4: 

Recheck smoke level. It should be zero. 

• 

Slide blower wheel toward motor until it 

contacts feeler gauge. 

• 

This procedure provides a margin of reserve air to accommodate 
variable conditions. 

• 

Rotate the wheel until the setscrew is 

centered on the flat of the motor shaft. 
Tighten the setscrew to secure the wheel. 

• 

If the draft level has to be changed, recheck the smoke and CO

2

 

levels. Adjust the burner air if necessary. 

SK9190A 

4.  Once combustion is set, tighten all fasteners on air band and air shutter. 

7.  Install the motor on the burner housing. Tighten screws.  Reconnect wires. 

5.  Start and stop the burner several times to ensure satisfactory operation.  

Test the primary control and all other appliance safety controls to verify 
that they function according to the manufacturer’s specifications. 

8.  Restore power, start the burner and perform combustion tests.  Refer to 

the section

 

Set combustion with instruments

”. 

 
 
 

Содержание AF104WH

Страница 1: ...AF Oil Burner MODEL Instruction Manual AF Type F air tube combinations Voltage 120 Vac 60 Hz Model AF Burner Beckett...

Страница 2: ...ntenance 12 Warranty 12 Table 1 Air Tube Combination ATC codes Firing rate GPH Static plate size ATC codes for usable air tube lengths A in inches see Figure 2 page 6 min max Head inches 4 5 6 7 9 10...

Страница 3: ...with all burners compared to the standard fuels Reduced deposits extend the service interval for cleaning and improve the efficiency of the appliance over time Low sulfur fuels reduce particulate and...

Страница 4: ...e burner cannot properly burn the fuel This would result in incomplete combustion causing sooting and possible emission of carbon monoxide Severe personal injury death or substantial property damage c...

Страница 5: ...rt number 6711 Verify that the electrode tip settings comply with Figure 1 If the nozzle is not installed obtain a nozzle of the manufacturer capacity and spray angle specified in appliance manufactur...

Страница 6: ...for dimension A greater than 4 2 Use the following procedure to adjust the Z dimension if it is not correct Turn off power to the burner Disconnect the oil connector tube from the nozzle line See Fig...

Страница 7: ...ad cell primary controls Burner wiring may vary depending on primary control actually used The oil valve shown in Figures 4 and 5 may be an optional feature Connect fuel lines All wiring must be in ac...

Страница 8: ...connect power before servicing Figure 5 Typical wiring R7184 primary control R7184P shown DANGER Electrical shock hazard Disconnect power before servicing DANGER SK9359 SK9437 Feature R7184A R7184B R7...

Страница 9: ...hnician s Quick Reference Guide Beckett part number 61351 for special pump priming sequence Check all wiring for secure connections or insulation breaks Check the pump pressure and cutoff function Pre...

Страница 10: ...ve kit includes PD Timer cordset 2182602U 2182604U 10 Pump elbow 2256 11 Connector tube assembly 8 5394 12 Motor PSC 21805U Item Description Part Number 13 Blower wheel use only RWB replacement 2459U...

Страница 11: ...ith the unit or controls Call your qualified service agency Incorrect operation of the burner could result in severe personal injury death or substantial property damage The following could result in...

Страница 12: ...near the heating appliance there are no signs of oil or water leakage around the burner or appliance Weekly Check your oil tank level Always keep your oil tank full especially during the summer in ord...

Отзывы: