S80 with
• MLS Basic Card
• MLS Professional Card

Assembly and Operating Instructions 

Door Control Unit

en

Important information for:

 

Fitters

• Electricians
• Users
Please forward accordingly!
These instructions must be kept for future reference.

Содержание S80

Страница 1: ...r antriebe com S80 with MLS Basic Card MLS Professional Card Assembly and Operating Instructions Door Control Unit en Important information for Fitters Electricians Users Please forward accordingly These instructions must be kept for future reference ...

Страница 2: ...are not in accordance with these and our other instructions can result in serious injuries e g crushing of limbs Therefore structural modifications may only be carried out with our prior approval and strictly in accordance with our instructions particularly the information contained in these Assembly and Operating In structions Any further processing of the products which does not comply with thei...

Страница 3: ...st only be performed by an authorised technician In the event of a system malfunction the system must be shut down immediately and the malfunction rectified as quickly as possible The system must only be commissioned by an authorised technician Observe the generally applicable legal regulations safety accident prevention as well as these safety instruc tions particularly the regulation of the empl...

Страница 4: ...ed for this type of control Intended use IMP Impulse Button LS Photoelectric Barrier MLS Mechanical Limit Switch mechanical limit switching ELS Electronic Limit Switch electronic limit switching SKS USA Bottom Rail Sensor VES Pre Limit Switch AUTO WZL Automatic Closing Reclosing Wiederzulauf BES Becker Electronic System DW Testing Pressure Switch Testing pneumatic safety edge Abbreviations used ML...

Страница 5: ...ed X X Button input UP STOP DOWN STOP X Automatic closing X Partial opening X Pneumatic safety edge X Electrical safety edge X Safety edge switchover 1 2 kOhm 8 2 kOhm X Optoelectronic safety edge FRABA OSE X Photoelectric barrier X Yard light X Traffic lights door status indicator X X Warning lamp X Power supply lamp X X LED UP X X LED DOWN X X LED Operating status X LED ERROR Code X LED Safety e...

Страница 6: ...g cover screws carefully Only then will the IP 65 degree of housing protection re main intact Installing the control unit The S80 door control system for drives with mechanical limit switching can be con verted upgraded by changing plug in control cards The following control cards are available MLS Basic Card MLS Professional Card Before changing a control card disconnect the entire door control u...

Страница 7: ... button opens the door and keeps it open When the top end limit has been reached or if a safety function responds the door stops automatically If the UP button is pressed whilst the door is clos ing the door stops instantly and after a delay of 0 5 s time Z0 it moves to the top end limit If the MLS Basic Card is used the unit can either be in dead man mode the UP button has to be kept pressed if i...

Страница 8: ...ows Disconnect the S80 control unit from the mains Change over two phases at the power supply terminals e g the cables at terminals L1 and L3 see positions of the termi nals and the wiring diagram Check the direction of movement again MLS Professional Card MLS Basic Card Checking the direction of movement Setting the door end limits Note To set the door end limits you can also use the programming ...

Страница 9: ...AND Slack Rope Switch MLS Basic MLS Professional A slack rope switch can be connected across terminals A10 and B10 SCHLAFFSEIL ÜL For installation the wire jumper across terminals A10 and B10 must be removed This input is debounced via an internal timing element of approx 0 1 s de pending on the bounce of the switch If the slack rope switch responds beyond that time the door stops instantly no mat...

Страница 10: ...rol unit self monitoring sensor as per pr EN 12453 The pneumatic safety edge or the electric safety edge is connected up to terminals A6 and B6 SKS USA To ensure that the spiral rubber insulated cable is monitored the 1 2 kW resistor clamped across terminals A6 and B6 is supplied with the unit It must be connected inside the pressure switch contact or at the end of the electric safety edge in acco...

Страница 11: ...nt relay 2 switches on for 1s passing contact pulse to actuate a time delay relay ON OFF ON Warning light yard light with time delay Relay 1 switches on when the door leaves either of the end limits and remains on At the beginning of each door movement relay 2 switches on and remains on 120s time Z6 after the end of each door movement it switches off after a delay If automatic closing has been set...

Страница 12: ...aution When using a radio control system the person controlling the door must have a clear view of the door and its surrounding area during door movement and must not be in a dangerous position In setting mode and in the event of a malfunction the radio receiver board must be removed from the PCB slot J1 Programming the Hand held Transmitter Code The hand held radio control transmitter has been co...

Страница 13: ...eiver and keep it pressed The red signal LED begins to flash slowly After approx 5 s the red signal lamp flashes quickly Keep the button pressed until the red signal lamp goes out When the signal lamp goes out all the codes of the 1 channel radio control receiver and all 4 channels on the 4 channel radio control receiver will have been deleted Only now let go of the button again ...

Страница 14: ... DIP 1 5 1 6 ON ON 1 2 3 4 5 6 7 8 ON DIP 1 2 ON DIP 1 DIP 2 Relay 1 warning light early warning only for automatic closing Relay 2 yard light ON OFF 1 2 3 4 5 6 7 8 ON DIP 1 2 ON DIP 1 DIP 2 Relay 1 traffic lights door at top end limit Relay 2 yard light OFF ON 1 2 3 4 5 6 7 8 ON DIP 1 2 ON DIP 1 DIP 2 Relay 1 warning light always with early warning Relay 2 yard light OFF OFF 1 2 3 4 5 6 7 8 ON D...

Страница 15: ...ontin flash Internal communication fault or main processor faulty Fault2 Stör2 on Hardware test routine being processed 1 flash Safety circuit of drive has been triggered 2 flashes Safety edge actuated just before downward movement of door or internal bottom rail sensor faulty 3 flashes Slack rope switch pull in cable safety switch 4 flashes Internal communication fault or monitoring processor fau...

Страница 16: ...erve the indication of faults and errors by the LED s on the pc board of the basic control unit S80 and MLS Professional Card Fault Possible cause and remedy No reaction to pressing the button POWER lamp is not lit Check supply voltage terminals L3 L2 L1 N MAINS Check miniature fuse F1 400 mA slow blow Check EMERGENCY OFF button terminals A2 B2 EMERGENCY OFF No reaction to pressing the button POWE...

Страница 17: ...1K2 OSE 8K2 X1 CONTROL PANEL J3 J4 J2 UB J1 RADIO F1 400 mA T F2 200 mA T 3 2 1 W MOTOR E L3 L2 L1 L1 N N 8 9 10 11 4 5 6 7 E V U PE A 2 3 4 5 6 7 8 9 10 11 12 13 B 2 3 4 5 6 7 8 9 10 11 12 13 CONTROL INPUTS RELAY 1 RELAY 2 OPEN CLOSED MAINS RELAY 2 RELAY 1 MAIN SWITCH optional CONTACTOR TRANSFORMER Cycle counter optional NOT AUS STOP AUF STOP SKS USA IMP AUTO WZL 1 2 Torhöhe STOP X Überlastschalt...

Страница 18: ...3 4 5 6 7 8 9 10 11 12 13 A B Relay 1 Relay 2 L3 L2 L1 L1 N N F2 200 mAT Mains PE PE PE W V U Drive green red UB green Int 3 way pushbutton switch Contactor 24 V DC 200 mA Plug in card 5 3 x 400 V 230 V AC 50 60 Hz SKS USA OSE FRABA EL E or DW R 1k2 8k2 S Transmitter E Receiver Connection white B8 brown A8 green A9 lectric safety edge Safety edge with DW contact pneumatic optical safety edge slack...

Страница 19: ...age 24 V DC Control circuit max 125 mA Dimensions of housing 182 mm x 254 mm x 90 mm W x H x D Weight approx 1 5 kg not incl connecting cable Degree of protection IP65 Relay switching capacity each 250 V AC 5 A AC 1 Ambient temperature range 0 C 50 C Battery backup on site 3 x 10 A Specifications Basic insulation for operating voltage ...

Страница 20: ...4023 630 822 0c 02 13 ...