Information for the electrician

The tubular drives with mechanical limit switching must 

not

 be connected in parallel. The drive manufacturer offers a range of suit-

able controls for the simultaneous control of several drives.
Use external conductor L1 to control the up and down direction. Other devices or consumers (lamps, relays, etc.) must not be dir-
ectly connected to the drive connecting cables. For this purpose, the drives and additional devices must be decoupled by relay
controls.
When installing the drive, all-pole disconnection from the mains with a contact gap of at least 3 mm per pole must be provided.

Attention

Only use mechanically or electrically locked switching elements with a marked zero posi-

tion! This also applies when drives with electronic and mechanical limit switching are used

in the same system. The changeover time for switching the running direction must be at

least 0.5 s. The switch and control must not execute simultaneous UP and DOWN com-

mands. Protect the electrical connections from damp.

Once you have finished wiring everything to the control, ALWAYS check the right direction

assignment of the drive to the control buttons UP and DOWN, EXTEND and RETRACT.

If the drive is to be operated with devices which contain sources of interference, the elec-

trician must ensure suitable interference suppression for the relevant devices.

Disposal

The crossed-out bin symbol on the product indicates that the device is subject to mandatory disposal separate from household
waste. This product must be handed over to a collection point for electrical and electronic equipment at the end of its service life.
The packaging material must be disposed of properly.

Maintenance

These drives are maintenance-free.

Technical data dia. 45

Tubular drive

R4-17

Model

M17

Type

M

Rated torque [Nm]

4

Output speed [rpm]

17

Limit switch range

Supply voltage

230 V AC / 50 Hz

Connected load [W]

85

Rated current consumption [A]

0.40

Operating mode

S2 4 min

Degree of protection

IP 44

Min. tube inside diameter [mm]

47

Emission sound pressure level [dB(A)]

≤ 70

9 - en

Содержание M17

Страница 1: ... mechanical limit switching Important information for Fitters Electricians Users Please forward accordingly These instructions must be kept safe for future reference Becker Antriebe GmbH Friedrich Ebert Straße 2 4 35764 Sinn Germany www becker antriebe com 2010 300 725 0a 23 05 2022 ...

Страница 2: ...uctions for installation and commissioning 4 Intended use 6 Assembly 6 Setting the limit positions 8 Blockage detection when moving UP 8 Information for the electrician 9 Disposal 9 Maintenance 9 Technical data dia 45 9 What to do if 10 Sample wiring diagrams 10 Declaration of conformity 12 2 en ...

Страница 3: ...avoided could result in injury ATTENTION ATTENTION indicates measures that must be taken to avoid damage to property Denotes user tips and other useful information Warranty Structural modifications and incorrect installation which are not in accordance with these and our other instructions can result in serious injuries e g crushing of limbs Therefore structural modifications may only be carried o...

Страница 4: ...y the drive manufacturer If any questions or uncertainties regarding the safety instructions contained in the standard arise please contact the manufacturer of the part or end product in question All applicable standards and regulations for electrical installation must be complied with All work including maintenance and cleaning on electrical installations as well as other system parts must always...

Страница 5: ... down all lines and control devices that are not essential for op eration Crushing or shearing points must be avoided or protected When installing the drive all pole disconnection from the mains with a contact gap of at least 3 mm per pole must be provided EN 60335 If the mains connecting cable is damaged it may only be replaced by the manufacturer If the drive has a plug in connecting cable it mu...

Страница 6: ... Assembly Assembling the drive Attention To connect the drive to the driven part solely mechanical accessory components made by the drive manufacturer from the current product catalogue may be used Prior to mounting the fitter must ensure that the masonry and the system being motorised are sufficiently robust drive torque plus weight of the shading solution Caution Electrical connections may only ...

Страница 7: ...oove recesses have different sizes and allow the drive to fit exactly Y X For round shafts Measure the lug of the thrust ring X Y Then notch the tube on the motor side so the lug of the thrust ring can also be pushed into the shaft There must be no play between the lug of the thrust ring and the shaft 10 mm To ensure secure torque transmission for round shafts we recommend screwing the drive adapt...

Страница 8: ...ntinuous operation and has only been designed for start up Lay the connecting cable Lay the connecting cable up to the tubular drive and fix The connecting cable and any antennae must not project into the winding chamber Cover any sharp edges Setting the limit positions A fixed stop at the upper limit position and fixed shaft connectors must be in place During commissioning and subsequent use ensu...

Страница 9: ...ust not execute simultaneous UP and DOWN com mands Protect the electrical connections from damp Once you have finished wiring everything to the control ALWAYS check the right direction assignment of the drive to the control buttons UP and DOWN EXTEND and RETRACT If the drive is to be operated with devices which contain sources of interference the elec trician must ensure suitable interference supp...

Страница 10: ...lar drive does not run in the right direction Check the electrical connection Tubular drive does not switch off properly at the lower limit pos ition Use fixed shaft connectors Tubular drive does not switch off properly at the upper limit po sition Fit a fixed stop Sample wiring diagrams The assignment of the black and brown wires according to the direction of travel is de pendent on how the drive...

Страница 11: ...ual control using Centronic UnitControl UC42 Mains 230 V 50 Hz Central Group Individual Individual 230 V 50 Hz Central cable connection to further control units 230 V 50 Hz 230 V 50 Hz Electronics 230 V 50 Hz Control unit 11 en ...

Страница 12: ...Declaration of conformity 12 en ...

Страница 13: ...13 ...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ......

Отзывы: