background image

3

ARNING

W

 

Never randomly press the push button on 

the app without having a line of sight to the 

sun shading system.

Fig. 2 

 Smartphone  app

The manual override operation, a push button on the 

device, has the highest priority and overrides all KNX com-

mands (even the safety objects).
The operating behaviour corresponds to the "KNX behav-

iour":
Brief push of the button = Stop
Long push of the button = Move

WARNING

Never randomly press the buttons on the 

keypad without having a line of sight to 

the sun shading system.

Programming

You can perform programming either in the app or directly 

on the device. 
There is a Prog button for programming and a display LED 

both in the app and on the keypad (see Fig. 3).

The procedure here is basically the same:

 

 

Press the programming button in the app or on the 

device (Fig. 3) to put the device into programming 

mode. The red LED lights up when programming mode 

is active. Programming is performed using the ETS on 

the PC. This software ends the programming mode 

automatically. The red LED goes out.

 

 

If the programming mode is to be ended earlier, press 

the programming button again. The red LED goes out.

Fig. 3 

 Cover  plate

LED flash patterns

Communication 

LED green

Error 

LED 

red

Statement

Flashes 

irregu-

larly

X

SMI communication, 

no fault

Flashes 

irregu-

larly

X

SMI communication, 

faults occur (the LED 

is deactivated during 

the motor search & 

initialisation)

Lights 

up con-

stantly

X

X

Unparameterised - SMI 

bus not yet commis-

sioned or no motors in 

the internal motor list

Maintenance

There are no parts inside the device that require mainte-

nance. 

Cleaning

Clean the housing with a soft, dry cloth. Do not use deter-

gents, cleaning agents, solvents, abrasive substances or 

steam cleaners!

Liability

Failure to comply with the product information in these in-

structions and any use of the device other than its intend-

ed use may result in the manufacturer refusing to honour 

warranty claims for product damage. In this case, liability 

for secondary harm to persons or damage to property will 

also be excluded. Observe the information in the operating 

instructions for your sun shading system. The automatic 

or manual operation of the sun shading system while iced 

over and the use of the sun shading system during severe 

weather may cause damage and must be prevented by 

the operator through suitable precautions.

Obligations for the disposal of electrical devices

 

A marking with this symbol indicates the following 

obligations under the scope of legal regulations: 

 

 

The owner of this electrical device must dispose of it 

separately from unsorted municipal waste for further 

recycling.

 

 

Used batteries and accumulators that are not enclosed 

in the old device, as well as lamps/bulbs that can be 

removed from the old device without breaking, must be 

disposed of separately.

 

 

Distributors of electrical devices and disposal compa-

nies are obliged to take back the equipment free of 

charge.

 

 

The owner must take it upon themselves to delete any 

personal data contained in the electrical device prior to 

disposal.

Содержание KNX/SMI Actuator REG-3TE 16K BT

Страница 1: ... Actuator Important information for fitters certified electricians operators Please forward accordingly These instructions must be kept by the operator 4002 630 009 0 01 03 2022 Becker Antriebe GmbH Friedrich Ebert Straße 2 4 35764 Sinn Germany www becker antriebe com ...

Страница 2: ...002 630 011 0 You can download the software manual and the product database for the actuator from www becker antriebe com downloads or from the ETS online catalogue Installation The device is intended for installation in a distribution cabinet The device is installed by clipping it onto a DIN rail TH 35 DIN 60715 Electrical connection An on site overload current protection device fuse and a discon...

Страница 3: ...arameterised SMI bus not yet commis sioned or no motors in the internal motor list Maintenance There are no parts inside the device that require mainte nance Cleaning Clean the housing with a soft dry cloth Do not use deter gents cleaning agents solvents abrasive substances or steam cleaners Liability Failure to comply with the product information in these in structions and any use of the device o...

Страница 4: ...C Conformity Available at www becker antriebe com ce This device meets the EMC directives for use in residen tial and commercial areas Ambient conditions Operating temperature 0 50 C Storage temperature 25 70 C Humidity not condensing 10 40 85 Hrel Degree of soiling 2 Connections Supply 230 V AC Screw terminals SMI interface Spring terminals KNX bus system Spring terminals Connection terminals Sup...

Страница 5: ... BN BK GY GNYE M SMI I PE L N I Motor 1 Motor 2 Motor 15 Motor 16 5 1 5 mm2 All motor lines H05RR F 5 G 0 75 BK Example Connection of SMI motors Maximum of 16 motors Total power maximum 3600 VA for the power saving relay of the SMI drives Connection when using motor lines H05RR F 5 G 0 75 with two black wires I Black 1 between BL and GNYE I Black 2 between BN and GNYE X6 Auxiliary voltage connecti...

Страница 6: ......

Отзывы: