background image

17

16

EN

Split Air Conditioner | Aire acondicionado Split | Ar condicionado Split

2. Reserve a certain length of drain hose and power cord for installation when 

binding them. When binding, separate the indoor power to a certain degree, and 

then separate the drain hose.

3. Bind them evenly.

4. The liquid pipe and gas pipe should be bound separately at the end.

Note:

•  The power cord and control wire cannot be crossed or wound.
•  The drain hose should be bound at the bottom.

Step 9: hang the indoor unit
1. Put the bound pipes in the wall pipe and then make them pass through the wall 

hole.

2. Hang the indoor unit on the wall-mounting frame.

3. Stuff the gap between pipes and wall hole with sealing compound.

4. Attach the wall pipe.

5. Check if the indoor unit is installed firmly and tight to the wall.

 

Note:

•  Do not bend the drain hose excessively in order to prevent blockage.

Check after installation

•  Check according to the following requirement after finishing installation.

Items to be checked

Possible malfunction

Has the unit been installed firmly?

The unit may drop, shake or emit noise.

Have you done the refrigerant leakage test?

It may cause insufficient cooling (heating) 

capacity.

Is thermal insulation of pipeline sufficient?

It may cause condensation and water dripping.

Does the water drain well?

It may cause condensation and water dripping.

connection pipe

drain hose

band

indoor power cord

outdoor

indoor

upper hock

lower hock of 

wall-mounting frame

wall pipe

sealing

compound

Is the power supply voltage in accordance with 

the voltage marked on the nameplate?

It may cause a malfunction or damage the 

components.

Is the electric wiring and pipeline installed 

correctly?

It may cause a malfunction or damage the 

components.

Is the unit grounded securely?

It may cause electrical leakage.

Does the power supply cord comply with the 

specification?

It may cause a malfunction or damage the 

components

Is there any obstruction in the air inlet or outlet? It may cause insufficient cooling (heating) 

capacity.

Were the dust and debris caused during 

installation removed?

It may cause a malfunction or damage the 

components.

Are the gas valve and liquid valve of the 

connection pipe completely open?

It may cause insufficient cooling (heating) 

capacity.

Have the inlet and outlet of pipe hole been 

covered?

It may cause insufficient cooling (heating) 

capacity or waste electricity.

Test operation
1. Preparation of test operation

•  The client approves the air conditioner.
•  Specify the important notes regarding the air conditioner for the client.

2. Test operation method

•  Connect the power and press the ON/OFF button on the remote controller to 

start operation.

•  Press the MODE button to select AUTO, COOL, DRY, FAN and HEAT to check 

whether or not it is operating normally.

•  If the ambient temperature is lower than 16°C, the air conditioner can’t start 

cooling.

Configuration of connection pipe
1. Standard length of connection pipe

5m, 7.5m, 8m

2. Min. length of connection pipe is 3m.

3. Max. length of connection pipe and max. height difference.

Cooling capacity

Max length of connection 

pipe

Max height difference

5000Btu/h (1465W)

15

5

7000Btu/h (2051W)

15

5

9000Btu/h (2637W)

15

5

12000Btu/h (3516W)

20

10

18000Btu/h (5274W)

25

10

24000Btu/h (7032W)

25

10

28000Btu/h (8204W)

30

10

36000Btu/h (10548W)

30

20

42000Btu/h (12306W)

30

20

48000Btu/h (14064W)

30

20

G306MA_AF1_AC18_indoor_170216.indd   16-17

17.02.16   18:33

Содержание 18BTUs

Страница 1: ...Conditioner 18BTUs Aire acondicionado Split 18BTUs Ar condicionado Split 18BTUs Indoor BAC2326 Instruction Manual Manual de Instrucciones Manual de Instru es G306MA_AF1_AC18_indoor_170216 indd 1 17 02...

Страница 2: ...ons and safety measures described in this manual carefully We wish our clients great satisfaction in using their new appliance INDEX 1 SAFETY INSTRUCTIONS 4 1 1 Power Supply 4 1 2 Power Cord and Other...

Страница 3: ...it has a damaged cable or socket or if it is not working properly If the power cord is damaged do not use your appliance Take it to technical assistance for replacement Do not use inadequately rated p...

Страница 4: ...stall suitable power supply cables before using the air conditioner Correctly connect the live wire neutral wire and ground wire of the power socket Be sure to cut off the power supply before proceedi...

Страница 5: ...ndicator temperature indicator temperature indicator temp indicator drying indicator drying indicator display display display display power indicator power indicator receiver window receiver window re...

Страница 6: ...precaution Electric safety regulations must be followed when installing the unit A suitably rated power supply circuit and air switch must be used in compliance with local safety regulations Make sure...

Страница 7: ...es on the wall 2 Drill the screw fixing holes in the wall with impact drill the specification of drill head should be the same as the plastic expansion anchors and then insert the plastic expansion an...

Страница 8: ...g to the color tighten the screw and then fix the power connection wire with a wire clip 4 Replace the wiring cover and then tighten the screw 5 Close the panel Note All wiring in the indoor and outdo...

Страница 9: ...or damage the components Is the electric wiring and pipeline installed correctly It may cause a malfunction or damage the components Is the unit grounded securely It may cause electrical leakage Does...

Страница 10: ...Cooling and heating g m 6 9 52 or 12 15 20 6 or 9 52 16 or 19 15 50 12 19 or 22 2 30 120 16 25 4 or 31 8 60 120 19 250 250 22 2 350 350 Pipe expanding method Note Incorrect pipe expanding is the main...

Страница 11: ...djust Set temperature Press the FAN button to adjust fan speed The cooling only unit can t receive the HEAT mode signal If HEAT mode is set by the remote control press ON OFF button if you can t turn...

Страница 12: ...r off When the child lock function is activated the LOCK indicator on the remote control is ON If you attempt to operate the remote control it won t send a signal Temperature display switchover functi...

Страница 13: ...mitted from indoor unit Indoor unit s air inlet or outlet is blocked Eliminate obstructions If in heating mode has the indoor temperature reached the set temperature After reaching to set temperature...

Страница 14: ...an abnormal sound during operation The air switch trips frequently The air conditioner emits a burning smell The indoor unit is leaking Do not repair or refit the air conditioner yourself If the air c...

Страница 15: ...manual Deseamos que nuestros clientes se sientan plenamente satisfechos con el funcionamiento de su nuevo aparato NDICE NSTRUCCIONES DE SEGURIDAD 30 1 1 Alimentaci n 30 1 2 Cable de alimentaci n y ot...

Страница 16: ...on una tensi n nominal inadecuada 1 3 Humedad y agua No utilice el aparato en lugares h medos No deje que el aparato se moje en ninguna circunstancia pues puede ser peligroso PARA EVITAR EL PELIGRO DE...

Страница 17: ...icionado Una alimentaci n inestable o un cableado incorrecto pueden causar un funcionamiento inadecuado Instale cables de alimentaci n adecuados antes de utilizar el aire acondicionado Conecte correct...

Страница 18: ...talla pantalla pantalla pantalla indicador de encendido indicador de encendido ventana del receptor ventana del receptor ventana del receptor Indicador de color LED de encendido Verde Encendido Rojo A...

Страница 19: ...usar un funcionamiento inadecuado Instale cables de alimentaci n adecuados antes de utilizar el aire acondicionado 4 Conecte correctamente el cable de fase el cable neutro y el cable de tierra de la t...

Страница 20: ...exterior con un gradiente de 5 10 Nota Al abrir el orificio tenga cuidado con el polvo generado y adopte las medidas de seguridad apropiadas Los tacos de expansi n de pl stico no est n incluidos por l...

Страница 21: ...una abrazadera para cables 4 Vuelva a colocar la tapa del cableado y a continuaci n apriete el tornillo 5 Cierre el panel Nota Todos los cables de las unidades interior y exterior deber n ser conecta...

Страница 22: ...ntes La unidad est conectada a tierra de forma segura Podr a causar una fuga el ctrica El cable de corriente cumple con la especificaci n Ya que podr a impedir que funcione correctamente o da ar los c...

Страница 23: ...abla Configuraci n del tubo de conexi n Cantidad de carga de refrigerante adicional para R22 R407C R410A y R134a Di metro del tubo de conexi n Regulador de la unidad exterior Tubo de l quido mm Tubo d...

Страница 24: ...bot n o para ajustar la temperatura definida Pulse el bot n VENTILADOR para ajustar la velocidad del ventilador Cuando se selecciona el modo de deshumificaci n el aire acondicionado funcionar con el...

Страница 25: ...vez aumentar o reducir el tiempo 0 5 horas Mantenga pulsado el bot n o dos segundos cambiar el tiempo m s r pido Suelte el bot n cuando haya alcanzado el tiempo deseado A continuaci n pulse el bot n...

Страница 26: ...lo utiliza Compruebe si el mando a distancia parece estar da ado En caso afirmativo sustit yalo Hay alg n bombillo fluorescente en la estancia Mueva el mando a distancia m s cerca de la unidad interi...

Страница 27: ...alimentaci n est da ado o sobrecalent ndose Hay un ruido anormal durante su funcionamiento El interruptor de aire salta con frecuencia El aire acondicionado emite un olor a quemado La unidad interior...

Страница 28: ...es e medidas de seguran a que se encontram descritas neste manual Desejamos aos nossos clientes uma grande satisfa o na utiliza o do seu novo aparelho NDICE 1 INSTRU ES DE SEGURAN A 56 1 1 Energia de...

Страница 29: ...cabo de alimenta o com uma classifica o incorreta 1 3 Humidade e gua N o utilize o seu aparelho em locais h midos N o permita que o aparelho fique molhado em nenhuma circunst ncia j que tal poder ser...

Страница 30: ...com o seccionador de emerg ncia prima o com um objeto isolante n o met lico N o suba para nem coloque objetos pesados sobre a unidade exterior Poder provocar danos ou ferimentos corporais A instala o...

Страница 31: ...r indicador de funcionamento indicador de funcionamento janela de rece o janela de rece o janela de rece o janela de rece o Indicador LED de alimenta o a cores Verde ligado Vermelho desligado Indicado...

Страница 32: ...ertifique se de que desliga a alimenta o antes de prosseguir com qualquer trabalho relacionado com eletricidade e com seguran a 6 N o ligue a alimenta o at concluir a instala o 7 Se o cabo de alimenta...

Страница 33: ...pl stico nos orif cios 3 Fixe o suporte de parede na parede com parafusos autorroscantes ST4 2X25TA e em seguida verifique se o suporte est instalado firmemente puxando o Se uma bucha de pl stico est...

Страница 34: ...o e o tubo flex vel de escoamento painel parafuso cobertura da cablagem orif cio para interliga o de cabos fio de liga o alimenta o Liga o unidade exterior castanho amarelo verde azul preto Passo 6 i...

Страница 35: ...o ar condicionado Informe o cliente sobre os pontos mais importantes em rela o ao ar 2 M todo do teste de funcionamento Ligue a alimenta o e prima o bot o ON OFF no controlo remoto para colocar em fun...

Страница 36: ...erante necess rios ap s aumentar o tubo de liga o Ap s aumentar o comprimento do tubo de liga o para 10 m deve adicionar 5 ml de leo refrigerante por cada 5 m adicionais tendo em considera o o comprim...

Страница 37: ...opriada do ventilador automaticamente consoante a temperatura ambiente A velocidade do ventilador n o pode ser ajustada no modo de desumidifica o Bot o SWING Oscilar Prima este bot o para ativar a osc...

Страница 38: ...ionado Premir o bot o ou uma vez aumenta ou diminui o tempo em 0 5 h Manter o bot o ou premido durante 2 s altera o tempo mais rapidamente Solte o bot o quando atingir o tempo pretendido Em seguida pr...

Страница 39: ...inicie a fun o emitida uma n voa pela sa da de ar da unidade interior A temperatura e humidade interiores est o altas Isto deve se ao r pido arrefecimento do ar interior Ap s algum tempo a temperatura...

Страница 40: ...a para o intervalo adequado A porta ou a janela est o abertas Feche as portas e as janelas S o emitidos odores Existe uma fonte para o odor como mob lia ou cigarros etc Elimine a fonte do odor Limpe o...

Страница 41: ...bu do por Importado producido y distribuido por Imported produced and distributed by Worten Equipamentos p o Lar S A Rua Jo o Mendon a n 505 4464 503 Senhora da Hora Portugal G306MA_AF1_AC18_indoor_17...

Отзывы: