background image

Page 4 

    

nuts (2 - off) and fully tighten.

Stub pipe. Braze to downdrop pipe. 

Using the approved jointing technique as detailed in the 

contract specification, braze stub pipe to downdrop pipe. 

With HTM 2022, HTM02-01 installations the copper stub 

pipe is joined using the fluxless brazing technique with 

Oxygen-free nitrogen purge. 

 

 

Care should be taken when working in confined spaces, 

precautions should be taken to avoid excessive build up of 

nitrogen.

Note...

If the stub pipe has been reduced in length by any more than 

100mm the plastic backplate must be protected against 

contact with the brazing flame to avoid damage occurring. 

Proprietary reusable heat shield compounds are available for 

this purpose.  

Terminal unit.  Blank. 

Fit blanking kit assembly Part No. 1825190 to terminal unit.

Note...

This will completely seal off the assembly ready for pipeline 

carcass pressure testing.

Plaster box. Fit. 

Locate plaster box over backplate and press into position.

Terminal unit. Pressure check. 

When all first fix terminal units on a specific distribution 

system have been installed, carry out pipeline carcass 

pressure testing in accordance with the commissioning 

procedure.

Plaster shield. Fit. 

Locate plaster shield into plaster box and press into position.

Installation procedure - Bed head installation

Bed head trunking must provide suitable mounting studs to 

enable the terminal unit backplate to be firmly secured. The 

procedure to install a BEACONMEDÆS AGS terminal unit first 

fix assembly within bed head trunking is as follows: -

Distribution system. Purge. 

Using Medical quality air, purge associated distribution 

system to remove all particulate matter prior to fitting 

terminal unit.

Terminal unit. Locate pipe run. 

Temporarily locate terminal unit backplate over securing 

studs and align pipework. Establish necessary pipe run 

layout and mark copper stub pipe for length required. Re-

move terminal unit assembly.

Copper stub pipe. Cut to length. 

Using a wheel cutter, cut copper stub pipe to required 

length. Ensure that ends are square, free from burrs and 

re-round as necessary. Ensure that component is clean and 

blow through as necessary to remove any particles.

Terminal unit. Fit. 

Using any necessary copper pipe fittings, align copper stub 

pipe with distribution system layout. Locate terminal unit 

backplate over securing studs. Fit nuts (2 - off) and tighten.

Stub pipe. Braze to distribution system. 

Using the approved jointing technique as detailed as 

detailed in the contract specification, braze stub pipe to 

distribution system and any fittings used. Care must be 

taken to prevent heat damage to the terminal unit, bed head 

trunking and any associated structure, electrical wiring etc. 

Proprietary reusable heat shield compounds are available for 

this purpose. With HTM 2022, HTM02-01 installations the 

copper stub pipe is joined using the fluxless brazing 

technique with Oxygen-free Nitrogen purge.  

 

Care should be taken when working in confined spaces, 

precautions should be taken to avoid excessive build up of 

nitrogen.

Terminal unit.  Blank. 

Fit blanking kit assembly Part No. 1825190 to terminal unit.

Note...

This will completely seal off the assembly ready for pipeline 

carcass pressure testing.

Terminal unit.  Pressure check.  

When all first fix terminal units on a specific distribution 

system have been installed, carry out pipeline carcass 

pressure testing in accordance with the commissioning 

procedure.

Installation of Pendant Units

General requirements.

Pendant/Boom mounted AGS terminal units are installed in 

the location and the quantity detailed in the contract 

specification, however the following requirements should be 

met unless otherwise stated: -

Terminal units should be securely fastened to a mounting 

plate contained within the pendant.

The construction of the pendant should provide for 

segregation of gases and electric’s, and provided with 

Отзывы: