Heaters should be connected only to circulating 

hot water systems

 where at 

least 1 gpm water fl ow is expected.  They are essentially small unit heaters, and will work on one or two pipe 
systems, or in a series loop where pressure and temperature drop can be tolerated (see capacity charts and 
piping diagrams). These units are not designed for use with steam systems. See bottom paragraph on page 7. 
These units are not recommended to be used with a gravity fl ow system. Series loop systems do not require 
scoop or venturi tees.

4.

Piping Charts

System Considerations

Maintenance & Service

     Properly installed, the Beacon Morris TWIN-FLO 

III 

heater should require very little attention. Since the 

heating element is carefully constructed and tested, and of non-ferrous materials, it should never require 
service. The cross-fl ow blower has been thoroughly engineered, with ball bearings for 10,000 hrs. bearing life 
expectancy. 

As with any electrical rotating device, a yearly inspection and cleaning is recommended.

  

Wherever there is air movement, there will be some accumulation of dust and lint. In this case it will collect on 
the rotor blades and air passage of the unit. Regular cleaning with a vacuum cleaner tool is advised, with fre-
quency determined by prevailing conditions. 

Always make sure that the air grille is not blocked by foreign 

objects or materials.

 

 

NOTE: In an up feed system, unit is located above hot water supply line. In a down feed  

 

 

system, unit is located below hot water supply line.

For One Pipe System Down Feed, two directional fl ow tees should be used. They should be spaced 12 
to 18 inches apart. To better understand directional fl ow tee installation, refer to page 5.

If directional fl ow tee's are not available, an adjustable screw operated fl ow control or circuit setter 
can be placed between the two standard tee's in a one pipe system. 

For consistent response of the reverse acting thermostat, and effective outlet air temperature, 
the average water temperature should not be below 120° F (49° C). Blower motor shuts off at 
105° F (41° C) and will not operate until water temperature reaches 120° F (49° C).

If utilizing water temperature below 120° F (49° C), the blower will not operate with the self contained
aquastat. An optional low temperature aquastat, 110° to 95° F (43° to 35° C) is available.

Installation should be done with as few fi ttings as possible. Multiple fi ttings may cause too much resistance.

Содержание twin-floIII

Страница 1: ...loor level and check piping and wiring locations The air outlet should be facing but not extending beyond the toe space riser at the opening The air outlet should also be located at the bottom portion...

Страница 2: ...TWIN FLO III TYPE K42 FIGURE A 2 TWIN FLO III TYPE K84 FIGURE B TWIN FLO III TYPE K120 FIGURE C Dimensions shown in English and metric...

Страница 3: ...mply connect it to the 115 V line The blower then starts after a short warm up and stops a few minutes after the circulator shuts off see diagram 1 Adding a line voltage type room thermostat will perm...

Страница 4: ...his case it will collect on the rotor blades and air passage of the unit Regular cleaning with a vacuum cleaner tool is advised with fre quency determined by prevailing conditions Always make sure tha...

Страница 5: ...em and create a pressure drop towards the supply tee forcing water up into the unit The arrow on the tee should point in the direction of water flow Figure 2 Figure 1 cutaway Figure 2 cutaway A ventur...

Страница 6: ...ble solutions a Water is not hot enough Check system water temp If radiant system low temperature aquastat may be needed b Water not circulating fast enough Kickspace heaters must have at least 1GPM f...

Страница 7: ...valve Do not return to bottom drain tapping Operation from steam boiler water is entirely possible as long as supply and return connection is installed be low level of water line on a steam boiler Thi...

Страница 8: ...any workmanship of any installer of the Product This limited warranty is conditional upon a shipment to the Manufacturer of that part of the Product thought to be defective Goods can only be returned...

Отзывы: