background image

                                  BDCOM S6508 Switch Hardware Installation Guide 

2.5.2    Record local log 

 

After check all,please labeled on the transport box,and take the relevant record. 

Each equipment must have a local log record, including these information: produce 
date, debug record, software and hardware version number, product series number. 

- 31 - 

Содержание S6508

Страница 1: ...BDCOM S6508 Switch Hardware Installation Guide...

Страница 2: ...r installation 22 2 1 Safety notice 22 2 1 1 Ensure safety as the following principals 22 2 1 2 Safety principal of Moving 22 2 1 3 Safety principal of operation with electricity 23 2 1 4 Preventing E...

Страница 3: ...1 Installing steps 39 3 11 Connecting external interface cable 39 3 11 1 Notice proceeding 39 3 11 2 Connecting Steps 39 3 12 Packing cable 39 3 12 1 Notice proceeding 39 3 12 2 Packing Steps 40 3 13...

Страница 4: ...flow of checking installation trouble 57 6 2 trouble shooting of losting switch password 58 6 3 deal with hardware installation trouble 58 6 3 1 trouble shooting about power supply module 58 6 3 2 tr...

Страница 5: ...s so commonly used So ShangHai Baud Data Communication Co Ltd Provide a business ethernet scheme to support this application for business ISP BDCOM S6508 is a switch that can be managned for buseniss...

Страница 6: ...itch View S6508 Switch is a 10 slot vertical chassis Figure 1 1 shows the S6508 Switch chassis Figure 1 1 BDCOM S6508 Switch View 1 Airflow exhaust the system module air exhaust 2 Fan Assembly the sys...

Страница 7: ...2 2m metal Rack H W D 2200mm 600mm 600mm 2 0m metal Rack H W D 2000mm 600mm 600mm 1 8m metal Rack H W D 1800mm 600mm 600mm 1 6m metal Rack H W D 1600mm 600mm 600mm 1 4 2 Chassis The S6508 Chassis is 1...

Страница 8: ...MSU slot there are 2 MSU slots only support LS6508 MSU 3 LPU slot there are 8 LPU slots the LPU module such as LS65 32FE TX LS65 4GE TX SFP and LS65 16FE SFP can be pluged in the Slots 4 Fan Assembly...

Страница 9: ...508 Switch Hardware Installation Guide Figure 1 3 S6508 side view 1 Airflow intake the system module air inlet 2 Chassis handle can be used to move the S6508 3 Airflow exhaust the system module air ex...

Страница 10: ...have 10 system module Slots the space between the two near Slots is 40mm The slots is vertical The Slots number is ordinal from left to right is Slot 1 to Slot 9 The Slot 5 and the Slot 6 are MSU Slot...

Страница 11: ...ut or DC Power Input There are 2 type Power supply module AC Power supply module and DC Power supply module are supported in S6508 1 DC Power Supply When you want to use DC Supply input you can use LS...

Страница 12: ...AC Power Chassis the chassis s Slot PowerA and Slot PowerB only Support LS65 PWR AC 800 module Double DC Power Chassis the chassis s Slot PowerA and Slot PowerB only Support LS65 PWR DC 800 module AC...

Страница 13: ...rovides cooling air for the MSU modules and the LPU modules Sensors on the MSU modules monitor the internal air temperatures If the air temperature exceeds a preset threshold the TEMPALM LED turns red...

Страница 14: ...four are LPU modules System Management and Switching Unit module LS6508 MSU is the MSU module LS6508 MSU is the center of Ethernet Switching Manage and Control the S6508 system 4 Port Gigabit TX SFP...

Страница 15: ...dule provides 16 switched 100 Mbps ports Support 100BASE SFP module 1 6 1 System Management and Switching Unit module LS6508 MSU Figure1 11 is System Management and Switching Unit module LS6508 MSU fr...

Страница 16: ...1 11 LS6508 MSU front view 1 Port LS6508 MSU module provides three Port Console port AUX port 10 100Base T Ethernet port 2 LED There are 7 LEDs on the LS6508 MSU front panel Table1 2 decribes the LEDs...

Страница 17: ...t the fan assembly Off means that the system Fan is OK TEMPALM Red means that air temperature exceeds a preset threshold Off means that air temperature is OK 3 Button Table 1 3 LS6508 MSU module butto...

Страница 18: ...le connector RJ45 Connector Support Category 5 UTP cable SFP module Connector support any Gigabit SFP module include 1000BASE SX LX LH and ZX SFPs or copper SFPs The RJ45 Connector and the SFP module...

Страница 19: ...WR Green means that the Module is Power On Off means that the Module is Power Off SYS Green means that the Module is active Off means that the Module is No active On the top of Panel SWAP Green means...

Страница 20: ...Gigabit SFP Module LS65 4GE SFP Panel View 1 Port LS65 4GE SFP module provides 4 switched full duplex Gigabit Ethernet Ports The ports have SFP module connectors for 1000BASE SX LX LH and ZX SFPs or...

Страница 21: ...n Off means that the Module is Power Off SYS Green means that the Module is active Off means that the Module is No active On the top of Panel SWAP Green means that the module can be hot pluged out Off...

Страница 22: ...gure 1 14 LS65 16FE SFP module front view 1 Port LS65 16FE SFP module provides 16 switched 100 Mbps full duplex ports The 16 ports have SFP module connectors for 100BASE SFP modules 2 LED Description...

Страница 23: ...r Off SYS Green means that the Module is active Off means that the Module is No active On the top of LINK ACT LEDs SWAP Green means that the module can be hot pluged out Off means that the module can...

Страница 24: ...t Switching Module LS65 32FE TX 1 Port LS65 32FE TX module provides 32 switched 10 100 Mbps autosensing full or half duplex ports The 32 ports have RJ45 connectors for Category 3 Category 5 Category 5...

Страница 25: ...eceiving data Off means that the Port is No link PWR Green means that the Module is Power On Off means that the Module is Power Off SYS Green means that the Module is active Off means that the Module...

Страница 26: ...ould cause damage to your eyes wear protection glasses Do not wear loose clothing that could get caught in the chassis Fasten your tie or scarf and roll up your sleeves Before working on a chassis or...

Страница 27: ...e room s Power switch Do not maintenance the S6508 with power on by one person alone Do not place the chassis in the wet room also do not allow the liquid inpour the chassis When using DC Power to sup...

Страница 28: ...General site requirements S6508 chassis should operate in the house For that the equipment operate well and prolong longevity of the system the chassis installed site has the following requirements 2...

Страница 29: ...humidity conditions can cause moisture migration and penetration into the system This moisture can cause corrosion of internal components and degradation of properties such as electrical resistance t...

Страница 30: ...un 15 days 3 The extreme scurviness working environment usually indicate that the environment temperature and humidity which can get right range among 5 hours when there is trouble in the room air con...

Страница 31: ...s one of the most important parts of equipment installation When you properly ground systems during installation you reduce or prevent shock hazards equipment damage due to transients and data corrupt...

Страница 32: ...ack of the chassis one is signal ground the other is protecting ground The view like Figure 2 3 Figure 2 3 S6508 ground connector view In order to ensure the equipment to run normally users must read...

Страница 33: ...ting for power supply system 2 The switch working place should not share with the grounding fitting of electrical equipment and preventing thunder equipment It is better that their distance is farness...

Страница 34: ...iment 2 Wrappage of faceplate The backup faceplate of equipment in the box It is the usual instance something maybe different everything according to the compact Please check the equipment carefully a...

Страница 35: ...cord local log After check all please labeled on the transport box and take the relevant record Each equipment must have a local log record including these information produce date debug record softwa...

Страница 36: ...2 has be readed Please confirm that the principals are all reached 3 1 Installing flow Prepartion before install S6508 Install rack Install s6508 on rack Grounding switch Connect AC power Connect DC...

Страница 37: ...e hole in the chassis base and the expand bolt The Rack must be stably after installing The Rack must be apeak after installing The Rack must be a beeline with other Rack in the room the error must be...

Страница 38: ...nding at each side of the chassis grasp the chassis handle with one hand and use the other hand near the back of the chassis for balance Slowly lift the chassis in unison Avoid sudden twists or moves...

Страница 39: ...unding Steps 1 Loosen the nut of the ground connector which local on the rear of the chassis 2 Connect the right grounding cable to the ground connector 3 Tight the the nut of the ground connector 4 C...

Страница 40: ...n Must use the right color power wire to Connect the Power Make sure that there is solid metal to metal contact 3 6 2 Connecting steps 1 Conect the power wires to the right conncetor tight the screw 2...

Страница 41: ...g steps 1 Plug the power cord into the power connection 2 Connect the other end of power cord to an AC input power source 3 8 Connect the cable to the LS6508 MSU module 3 8 1 Connecting steps 1 Plug o...

Страница 42: ...ive screws on the module 3 Place your thumbs on the ejector levers and simultaneously rotate the levers outward to unseat the module from the backplane connector 1 Before remove the module confirm tha...

Страница 43: ...printed circuit boards or connectors When Installing or removing the module Please use ejector levers 3 11 Connecting external interface cable 3 11 1 Notice proceeding Distinguish correctly between si...

Страница 44: ...stallation 3 13 1 Checking the Rack Confirm that Power supply are matched to the Power switchboard of the rack After the chassis being unstalled in the rack comfirm that the front door and the back do...

Страница 45: ...st Install software Config parameter Run self test Debug over Set up cofiguration envirament yes no Finish Installation 4 2 set up configurable environment 4 2 1 set up configurable environment by con...

Страница 46: ...iroment by console 2 Run hyperTerminal program like Terminal in Windows 3 1 system or hyperTermial if you want to run it please selet program accessary hyperTerminal as shown in figure 4 2 Figure 4 2...

Страница 47: ...al type is set to VT100 Figure 4 4 COM parameter configration After POWER on system will run self checking after self checking switch will prompt user to input ENTER until command prompt string is dis...

Страница 48: ...multimeter 5 If 220V AC power supply input is ok turn on the switch of the power supply module all module s PWR indicator lights are lighted The fans of fan board in the chassis are turned on and if t...

Страница 49: ...upgrade S6508 IOS Installation and upgradation of system IOS can be run in BOOTROM moniter enviroment or run time enviroment you can also upgrad BIOS in BOOTROM moniter enviroment 4 5 1 Installation a...

Страница 50: ...r ip address 192 168 1 1 255 255 255 0 4 Test network by ping command monitor ping ip_address ip_address target ip address 5 To install or upgrade system software by tftp protocal input following comm...

Страница 51: ...2 168 20 1 prompt Destination file name main bin switch bin please wait TFTP successfully receive 3377 blocks 1728902 bytes monitor 2 download system software by zmodem protocal 1 Run s6508 system sof...

Страница 52: ...the filename which is saved in flash users must input the filename 5 Enter port baudrate prompt speed 9600 For example Terminal program can use Hyper Terminal or termial simulation program monitor do...

Страница 53: ...9600bps 4 5 2 update configuratation Switch s config is stored in file file name is startup config user can upgrade configuration file same as upgrade system sotrware use tftp protocal monitor copy tf...

Страница 54: ...to MSU 1 Power on system when prompt selt test information press ctrl p and enter system moniter mode Carry out the following command monitor copy tftp rom ip_addr This command is used to download fi...

Страница 55: ...em software itself and Bootrom software The method is similar with that on monitor mode 1 Use TFTP protocol 1 Run system software enter privilege mode switch 2 Enter into config mode config a ip addre...

Страница 56: ...un system software enter privilege mode switch 2 Type command download co and type enter switch download c0 3 select baudrate you can select 110 134 150 200 300 600 1200 1800 2400 4800 9600 19200 3840...

Страница 57: ...o the incept configuration of S6508 please use write command to save the current configuration into incept configuration files of flash And users can look over the incept configuration files by show s...

Страница 58: ...ase refer to S6508 s manual S6508 switch configuration manual and s6508 switch command manual 5 2 run diagnose function in s6508 S6508 support a lots of debug function when system has problem Users ca...

Страница 59: ...y module after loosening two captive screws on the panel of power supply module Then after eligible power supply is replaced give a good screw and connect power cable 5 4 remote maintenance S6508 supp...

Страница 60: ...BDCOM S6508 Switch Hardware Installation Guide Chapter 6 Hardware Troubleshooting 56...

Страница 61: ...BDCOM S6508 Switch Hardware Installation Guide 6 1 The universal flow of checking installation trouble 57...

Страница 62: ...ower supply module rouble 1 AC power supply module can t work trouble description The moudle s PWR indicator lights are not lighted Green light on the panel of power supply module is not lighted Fans...

Страница 63: ...ain and confirm that the system module is installed tightly and then give a good screw If still not work check if the corresponding slots of the backplane is loose If so install the system module to o...

Страница 64: ...that hyperTerminal program specify Configuration parameter of COM port is identify with 4 2 said If not please change COM configuration parameter in accordance to 4 2 If still no effect please contac...

Страница 65: ...any Name ShangHai BDCOM Produce Area Made in China Leave factory series number 7 1 3 Produce Area ShangHai China 7 1 4 Product Type Network Equipment 7 1 5 Wrapper The inner wrappwer is plastic bag Th...

Страница 66: ...ship plane truck Used canopy avoid rainwater in trasport Gently move it 7 1 7 Stockpile Stockpile location Repository Stockpile condition Temperature 25 0 C 55 0 C Humidity 40 90 Without caustic gas i...

Страница 67: ...Hardware Installation Guide Certificate Product produce date checker s sign or seal can replaced by checker s number Product free maintain card Product maintain card include these contents 1 Condition...

Отзывы: