13
Length of refrigerant connections
Note: All the requirements below should be met at the same time:
RZT50
RZT70
RZT100
RZT120
RZT140
RZT160
Maximum distance of
connections (m)
L
20
30
30
30
50
50
Maximum height
difference (m)
H
15
15
15
15
30
30
Max. distance with
precharge (m)
P
8
8
8
8
8
8
Additional charge
(g/m)
C
20
50
50
50
50
50
Refrigerant adjustment: lf total pipe length exceeds 8m
,
additional refrigerant
(R410A) change is required. (The outdoor unit is charged with refrigerant for total
pipe length up to 8m).