33
INST
ALLER Section
(en)
7114043.01 (1-06/13)
This procedure can also be used to adjust the quantity of
CO
2
to the
ignition power
and to the
minimum power
by pressing
after point 5 of the procedure described above.
• After saving the new value (point 5 of the procedure), press
to take the boiler to its
ignition power
. Wait for the value of
CO
2
to stabilise and then adjust as described in point 4 of the procedure (the power value is a number <> 100 and <> 0) then
save (point 5).
• press
again to take the boiler to
minimum power
. Wait for the value of
CO
2
to stabilise and then adjust as described in
point 4 of the procedure (power value = 00);
• to exit the function, press the buttons for at least 6 seconds as described in point 1.
13. GAS VALVE
This appliance does not require any mechanical adjustment on the valve. The system ensures electronic auto-adaptation.
Gas valve key
Pi
Gas supply pressure tap
13.1 GAS CONVERSION METHODS
Only an Authorised Technical Assistance Service can convert boiler operation from
NATURAL GAS
to
LPG
or vice-versa. To
perform calibration, set parameter
P02
as described in the PARAMETER SETTINGS section. Lastly, check the combustion pa-
rameters as described in the SPECIAL FUNCTIONS - CHECKING COMBUSTION PARAMETERS section.
When the gas change is complited the boiler data plate must be amended to indicate the new gas data.
14. PARAMETERS SETTING
To programme the parameters of the boiler electronic board, proceed as follows:
• Press
and
together and hold them down for 6 seconds until programme row “
P01
” appears on the display alternated
with the set value;
• Press
to scroll the list of parameters;
• Press
the value of the selected begins flashing, press
to change the value;
• Press
to confirm the value or press
to exit without saving.
Further information concerning the parameters listed in the following table are supplied together with the required acces-
sories.
DESCRIPTION OF PARAMETERS
FACTORY PARAMETERS
16
24
P01
-------
00
P02
Gas used
00
= METHANE -
01
= LPG
00
P03
Hydraulic system
06
P04
Programmable relay 1 settings (See SERVICE instructions)
00
= no associated function
01
= relay contact closed with Room Thermostat demand (230V)
02
= relay contact closed with Remote Control demand (low voltage)
03
= system fill contact
04
= boiler faulty signal contact
05
= fan contact (kitchen fan)
06-07
= not used
08
= timed contact for enabling external DHW pump
09
= timed contact for enabling external DHW circulation pump via DHW
programming from remote control
10
= relay contact closed with DWH demand active
11 - 12 - 13
= not used
02
P05
Programmable relay 2 settings (See SERVICE instructions)
Same configurations as relay 1 - P04
04
Содержание NUVOLA DUO-TEC GA 16
Страница 21: ...21 7114043 01 1 06 13 ...
Страница 41: ...41 I N S T A L L E R S e c t i o n e n 7114043 01 1 06 13 ...
Страница 61: ...61 7114043 01 1 06 13 ...
Страница 102: ...7114043 01 1 06 13 102 S E C T I O N A ...
Страница 104: ...7114043 01 1 06 13 104 S E C T I O N B ...
Страница 106: ...7114043 01 1 06 13 106 S E C T I O N C ...
Страница 107: ...107 S E C T I O N D 7114043 01 1 06 13 25 mm ...
Страница 109: ...109 S E C T I O N E 7114043 01 1 06 13 ...
Страница 110: ...7114043 01 1 06 13 110 S E C T I O N F ...