Tab.31
Appliance
Power supply type
Cable cross section
(mm
2
)
Circuit breaker curve
C (A)
Maximum amperage
(A)
Indoor module
Single phase
Cable provided (3 x
1.5)
10
-
Electrical back-up
Single phase
3 x 2.5
16
-
-
2 x 0.75
-
-
AWHP 4.5 MR
Single phase
3 x 2.5
16
12
AWHP 6 MR-3
Single phase
3 x 2.5
16
13
AWHP 8 MR-2
Single phase
3 x 4
25
17
(1) Connection cable linking the outdoor unit to the indoor module
5.10.3 Accessing the PCBs
1. Unscrew the two screws on the protective cover for the PCBs but do
not remove them.
2. Slide the cover upwards and remove it.
3. Lift the control panel flap slightly.
4. Tilt the control panel flap forwards.
For more information, see
Removing the appliance's front panel, page 35
Fig.60
MW
-3
0
0
0
6
6
2
-0
1
1
2
Fig.61
MW
-3
0
0
0
6
6
3
-0
1
4
3