SETTING THE CLIMATE CURVE Kt
To set the climate curve
Kt,
access
menu 2
as described in section 14.2.1 and proceed as follows:
.
•
B
720
(Heating curve slope)
B
to confirm
•
B
(
from 0.10 to 4
)
B
to confirm.
Select the climate curve from among those available, see the curve chart in annex
“SECTION” E
at the end of this manual (the
preset curve is 1.5).
KEY TO CURVE CHART Kt - “SECTION” E
Flow temperature
Outside temperature
14.5.2 CONNECTING AN EXTERNAL STORAGE BOILER
(for models 1.12 - 1.18 - 1.24 - 1.32)
The heating-only boilers, models 1.12 - 1.18 - 1.24 and 1.32 can be connected to an external storage boiler as they are factory-
fitted with a powered three-way valve. Connect the storage boiler to the water supply. Connect the DHW priority NTC sensor,
supplied as an accessory, to terminals 9-10 of the M2 terminal block. The sensitive element of the NTC probe must be inserted in
the holder provided on the storage boiler. To adjust the temperature of the DHW see section 3.
KEY TO STORAGE BOILER CONNECTIONS (see diagram C in annex
“SECTION” G
at the end of this manual).
A
Heating Unit
E
Heating water / Storage boiler return
B
Powered 3-way valve
F
Storage boiler unit
C
Heating water flow
G
DHW priority probe
D
Storage boiler water flow
The anti-legionellosis function is
NOT
ENABLED. To enable it, set parameter
1640
as described below.
To activate the ANTILEGIONELLOSIS
function, proceed as follows:
•
Access MENU 2 as described in section 14.2.1.
•
B
Temps / mode hot water
B
B
programme row
1640
then
B
to confirm.
•
B
Periodically
or
Fixed weekday
then choose one of the two items and
B
to confirm.
Choose
Periodically
to enable the function once a week on the set day and at the set time. To set the day and time, use the same
procedure described above: set parameter
1641
to establish which days (from 1 to 7) the function must activate and parameter
1644
to set the starting time of the function.
Choose
Fixed weekday
to enable the function once a week on the set day and at the set time. Set parameter
1642
to establish
the day of the week (from Monday to Sunday) on which the function must activate and parameter
1644
to set the start time of the
function.
15. SPECIAL FUNCTIONS
Available functions are:
•
Manual control
(
301
) - Options: 25 - 90 (°C) In this mode the boiler operates at the set temperature value.
•
Chimney sweeper
(programme row
303
) - Options: Full load (maximum thermal power of the boiler), Part load (reduced
thermal power), Full heating load (maximum thermal power in the heating mode).
•
Controller stop function
(
304
) - Options: from 100% (maximum thermal power) to 0% (reduced thermal power). This function
facilitates gas valve calibration operations.
•
Deaeration function
(
312
) - Options: On (function enabled) - Off (function disabled). See section 15.1 “System gas extraction
function”.
The procedure used to enable these functions is the following:
•
From the main menu
A
and
C
(hold down for
approx. 6 seconds)
names of the FUNCTIONS (see
figure to side: 301 - 303 - 304 - 312)
•
B
to choose the FUNCTION
B
to ENABLE the
chosen function then
B
FUNCTION menu
B
to edit (see example below).
E.g.:
turn knob
B
to enable the CALIBRATION function
(programme row
304
), press knob B, the function is now active
and preset to 100% (the boiler is at its maximum thermal
power). Press the knob and turn it to select the required power
percentage (0% corresponds to the reduced thermal power
level).
To manually interrupt the function, repeat the procedure described above. When the function is disabled, “
off
” is shown on
the display.
Содержание LUNA PLATINUM
Страница 25: ...25 7110317 02 3 10 14...
Страница 49: ...49 7110317 02 3 10 14...
Страница 73: ...73 7110317 02 3 10 14...
Страница 99: ...99 7110317 02 3 10 14...
Страница 125: ...125 7110317 02 3 10 14...
Страница 126: ...7110317 02 3 10 14 126 S E C T I O N A LUNA PLATINUM GA 24 33 LUNA PLATINUM GA 1 12 1 18 1 24...
Страница 132: ...7110317 02 3 10 14 132 S E C T I O N C...
Страница 133: ...133 S E C T I O N C 7110317 02 3 10 14 C33 C13 C43 C53 C83 C13 C33 CG_1638 CG_2168 5 2 7 6 4 3 1...
Страница 134: ...7110317 02 3 10 14 134 S E C T I O N C 25 mm S E C T I O N D...
Страница 136: ...7110317 02 3 10 14 136 S E C T I O N E...
Страница 137: ...137 S E C T I O N F 7110317 02 3 10 14...
Страница 138: ...7110317 02 3 10 14 138 S E C T I O N G...