background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

Ebony Super

Baxi Heating Ltd.

page 2

Installation Instructions – Page 2

INTRODUCTION

The Baxi Ebony Super is a hearth or wall mounted gas fired room
heater with a flame and coal effect. Input at maximum setting is
5.42kW (18,500 Btu/h) corresponding to a net output of 3.47kW
(11,840 Btu/h) approx. The fire is available for use with Gas Type
G20 (Natural Gas) at 20mbar. The fire is controlled by a control
knob positioned on the right hand side of the case. Ignition is by a
piezo spark to the burner.
The control knob has six positions giving a choice of four output
rates:

have a flat vertical area and an opening size to the dimension
shown (Fig. 2). A shelf may be fitted above the fire provided that it
does not exceed 150mm (6in deep) and is at least 100mm (4in)
above the top of the fire. A clearance of 75mm (3in) is required at
each side of the fire for access during servicing.

(

b)

Fireplace opening: At the height of the flue outlet the fireplace
should have a minimum dimension of 100mm (4in) from the
front face of the opening to the fireplace back brick (Fig. 3).
There must be a minimum height of 250mm (10in) from the

NATURAL GAS

PROPANE

bottom of the catchment space to the base of the the flue

Position 

-

OFF

Position 2

-

Medium

spigot.

Position 

-

Pilot.

Position 3

-

Medium High.

Position 1

-

Low.

Position 4

-

High

(c)

Hearth:

 If the fire is to be hearth mounted the hearth must be

The outer case has two concealed lamps to illuminate the artificial
coal bed. This light effect is operated by a switch below the control
knob. It may be used with or without the gas fire.

NOTICE

Discolouration of Wall Surfaces

Most heating appliances generate warm air convection
currents and transfer heat to any wall surface against which
they are situated.

Some soft furnishings (such as blown vinyl wallpapers) may
not be suitable for use where they are subjected to
temperatures above normal room levels and the manufacturers
advice should be sought before using this type of wall
covering adjacent to any heating appliance.

The likelihood of wall staining from convected air currents will
be increased in environments where high levels of cigarette
smoke or other contaminants exist.

GENERAL

The installation must be carried out by a CORGI Registered
Installer or other competent person and be in accordance with the
relevant requirements of the GAS SAFETY (Installation and Use)
REGULATIONS (as amended), the BUILDING REGULATIONS
(Scotland) (Consolidation), the LOCAL BUILDING REGULATIONS
and the CURRENT I.E.E. WIRING REGULATIONS. It should also
be in accordance with the relevant BRITISH
STANDARD CODES OF PRACTICE.

IMPORTANT INFORMATION

This product contains Refractory Ceramic Fibres (R.C.F.) which are
man-made vitreous silicate fibres. Excessive exposure to these
materials may cause temporary irritation to eyes, skin and
respiratory tract. Care must be taken when handling these articles
to ensure the release of dust or fibres is kept to a minimum.
To ensure that the release of fibres from these articles is kept to a
minimum, during installation and servicing it is recommended that a
H.E.P.A. filtered vacuum is used to remove any dust, soot or other
debris accumulated in and around the appliance. This should be
performed before and after working on the installation. It is
recommended that any replaced item(s) are not broken up but
sealed within heavy duty polythene bags and clearly labelled
“R.C.F. waste”. This is not classified as ‘hazardous waste” and may
be disposed of at a tipping site licensed for the disposal of industrial
waste.
Protective clothing is not required when handling these articles but it
is recommended that gloves are worn and the normal hygiene rules
of not smoking, eating or drinking in the work area are followed and
always wash hands before eating or drinking.

SITE REQUIREMENTS

(a)

Fireplace or surround:

 The fireplace or

surround must be of non-combustible material and

of non-combustible materials, at least 13mm (½ in) thick and
measuring at least 326mm (12 13/I6 in) deep and 750mm (29
9/16in) wide (with the fireplace opening central). The top
surface of the hearth should preferably be 50mm (2in) above
the floor level. The floor behind the fire opening in the area of
the closure plate rectangular cutout must be no higher than
the finished hearth level. The fire must not be fitted directly on
to a combustible floor or carpet.

(d)

Wall Fixing:

 The fire may be fitted on to a suitable non-

combustible wall so that the bottom of the rear legs is not less
than 100mm (4in) above the finished floor level (Fig. 4).

FLUE 

(BS 5440: Part 1)

(a)

Existing chimneys:

 A chimney which has previously been

used to burn solid fuel MUST be swept before beginning the
installation and any restrictions such as dampers or register
plates. must be removed. The chimney must be at least
310cm (10ft) in height and also meet the following
requirements:

(i)

It must NOT be cracked.

(ii)

It must serve only one room.

(iii)

It must not communicate with any void, space or any room
other than that in which the fire is situated.

(iv)

It must NOT be blocked by paper, rubble etc.

(v)

It must have a positive updraught.

(vi)

The cross sectional area of the flue must not be less than
120cm

2

 (19in

2

).

If there is no positive updraught DO NOT FIT THE FIRE and seek
expert advice. Positive updraught can be detected by the use of a
lighted match or smoke match (see relevant paragraph under
INSTALLATION). Any underdraught vent or additional air supply
openings that enter the fireplace must be completely sealed off.

(b)

Pre-cast flue

: The fire is suitable for fitting into properly

designed and constructed pre-cast flues complying with the
requirements of BS 1289 of at least 310cm (10ft) in height and
having a flue way of at least 197mm x 67mm (7 ¾ in x 2 5/8in)
or equivalent cross sectional area.

NOTE:  It must be ensured that any mortar between the blocks
is not extruded into the flueway and that if raking blocks are
used they must be fitted according to the manufacturers
instructions.

Содержание EBONY SUPER

Страница 1: ...heating spares co Tel 0161 620 6677 Page 1 Please leave these Instructions with the User Baxi Ebony Super Gas Fire Comp No 236202 Issue 4 10 99 Installation and Servicing Instructions Baxi Ebony Super G C No 32 077 37 ...

Страница 2: ...ndling these articles to ensure the release of dust or fibres is kept to a minimum To ensure that the release of fibres from these articles is kept to a minimum during installation and servicing it is recommended that a H E P A filtered vacuum is used to remove any dust soot or other debris accumulated in and around the appliance This should be performed before and after working on the installatio...

Страница 3: ...CAL CONNECTION THIS APPLIANCE MUST BE EARTHED ALL EXTERNAL WIRING BETWEEN THE APPLIANCE AND THE ELECTRICAL SUPPLY SHALL COMPLY WITH CURRENT I E E REGULATIONS The mains lead has the following specifications 16 0 2mm 3 core PVC covered PVC insulated wire to BS 6500 IMPORTANT Mains lead wires Green and yellow Earth Blue Neutral Brown Live FOR THE MAINS PLUG USE A 3AMP FUSE The appliance is supplied w...

Страница 4: ...attention DO NOT FIT THE FIRE SEEK EXPERT ADVICE HEARTH FIXING Fireplace or Surround a Fit the fire backing plate to the fire using the M5 x 8mm thread forming screws provided The backing plate may be screwed to the wall for extra support if necessary Fig 6 b Position the fire minus the outer case against the closure plate and determine the position of the gas connection c Adjust the feet to level...

Страница 5: ... position and wait for 3 minutes before attempting to light the pilot again d Push in the control knob and turn fully anti clockwise Check that the ignition is satisfactory e Check the fire pressure with the control knob turned fully anti clockwise The pressure should be 14 1mbar 1 0mbar 5 6 in wg 0 4 in wg No adjustment is provided on the fire Turn the control knob to the OFF position Remove the ...

Страница 6: ...ve the outer case for access to all controls a Pull off the control knob b Remove the cover panel under the front of the fire by grasping it firmly by its side edges and pulling forwards c Remove the two case securing screws Fig 7 d Lift the case away from the heat exchanger 2 Remove the glass front panel Fig 10 a Ensure that the glass front panel is cold b Slide the glass front panel retaining cl...

Страница 7: ...Supplied By www heating spares co Tel 0161 620 6677 Ebony Super Baxi Heating Ltd page 7 Fit the Outer Case Page 7 ...

Страница 8: ...fting it carefully away from the locating pins CAUTION The coal bed is extremely fragile and must be handled accordingly Gloves should be worn and any inhalation of the dust should be avoided Keep the coals away from children at all times Please read the Important Information Section on page 2 On re assembly ensure that the coal bed is correctly located over the locating pins BURNER Figs 10 11 and...

Страница 9: ... Glass Frame Assembly 155 758 040955 C Knob Gas Tap Control 156 431 234551 D Flame Failure Device Gas Tap E05 653 242512 E Piezo Unit Vernitron 66111 393 734 042941 F Electro Magnet Unit E01 617 239413 G Injector F11 Cat 18 230 381 879 092133 H Burner Aeromatic Baxi Special 155 949 043210 I Oxy pilot Assembly 350mm SIT OP 9402 378 914 236204 J Lead Electrode 378 915 236199 K Coal Bed 156 429 23514...

Страница 10: ...Supplied By www heating spares co Tel 0161 620 6677 Ebony Super Baxi Heating Ltd Page 10 Fault Finding Chart Page 10 11 BAXI EBONY SUPER Gas Type G20 Natural Gas Click here for Helplines ...

Отзывы: