Rear Flue Fitting
Provide a minimum vertical height of 600mm of
flue, with a single bend only, from the height of the
rear flue outlet.
See figure 6a.
Fit and seal a "T" section (with soot box) directly
into the flue spigot. The maximum horizontal
section allowed is 150mm.
Top Flue Fitting
Provide a minimum vertical height of 600mm of
flue measured from the top of the appliance. See
figure 6c.
Move the fire, with flue spigot in place, into
position under the flue and seal the spigot/flue
connection with fire cement. (Ref fig 5c).
It is recommended that a smoke test is performed
inside the fire to ensure that adequate flue draw is
evident.
Fig 6a
Fig 6b
Fig 6c
Baxi Gas Stoves
11
INSTALLATION
non- combustible closure plate,
incorporating access for cleaning debris.
non- combustible closure plate,
incorporating access for cleaning debris.