background image

Notes for Guidance – page 8

PIPE SIZING

a)

The sizes of flow and return pipes from the boiler
should be determined by normal methods according to
the requirements of the system.  Normally the pump
should be set to give a 11ºC (52ºF) drop across the
system with the gas rate of the boiler adjusted to the
output required.

b)

The open vent pipe must be a minimum of 22mm and
must rise continuously to above the feed tank. The flow
pipe from the boiler may form part of the open vent. No
part of the open vent should contain a valve.

c)

The 15mm cold feed pipe should not include a valve
unless required by the local water authority.

DOMESTIC HOT WATER

An indirect cylinder must be used. If a self priming indirect
type is employed it must be of adequate size and applied
strictly in accordance with the cylinder manufacturers’
instructions.

FUEL ECONOMY

Better fuel economy is achieved by exercising control of the
boiler by means of a room thermostat and or a cylinder
thermostat as appropriate.

ALLOWING THE BOILER TO CYCLE ON THE BOILER
THERMOSTAT DOES NOT PRODUCE THE BEST
RESULTS. SIMILARLY FOR ECONOMY AND BOILER
PERFORMANCE THE SYSTEM SHOULD BE DESIGNED
SO THAT GRAVITY CIRCULATION IN THE HEATING
CIRCUIT DOES NOT TAKE PLACE WHEN THE PUMP IS
NOT RUNNING.

IMPORTANT:  Gravity Flow and Return connections
must be taken from the same side of the boiler.

In both cases the cold feed pipe which is the neutral
point of the system is shown directly behind the pump
to avoid sub atmospheric pressure (air entrainment) in
the system.

Содержание Boston 2 40 RS

Страница 1: ...Baxi Boston 2 RS Floor Standing Room Sealed Gas Fired Central Heating Boilers Comp No 235322 Iss 5 6 00 Please leave these instructions with the User Installation and Servicing Instructions ...

Страница 2: ...the unit to be fitted under a work top The pump cannot be fitted in the case in this type of application See PUMP All appliances are designed for use on Gas Type G20 Natural Gas only at supply pressure 20 mb Each appliance consists essentially of three components namely 1 COMBUSTION CHAMBER with heat exchanger burner controls and inlet of air duct 2 OUTER CASE 3 BALANCED FLUE TERMINAL Benchmark Lo...

Страница 3: ...nts nationwide When ordering a terminal guard quote the appliance model number The guard manufacturers listed below can be contacted for terminal sizes and guard model numbers VENTILATION Detailed recommendations for air supply are given in BS 5440 2 The room in which the boiler is installed does not require a purpose provided air vent When the boiler is installed in a purpose made cupboard air ve...

Страница 4: ...se copper pipe for the boiler Flow and Return The copper must extend at least 1 metre from the boiler and include any branches The copper pipe must not be insulated GAS SUPPLY The gas connection is located at the bottom left hand side of the appliance and is Rc in B S P T internal Ensure that the pipework from the meter to the appliance is of adequate size Do not use pipes of a smaller size than t...

Страница 5: ...d Pipe sizes are suitable for the system design PUMP Fig 5 A suitable pump e g Grundfos UPS 15 50 15 60 or equivalent Myson or Wilo with ball type isolating valves and 22mm compression fittings may be fitted inside the outer case The pump should be connected to the in flow connection on the front of the heat exchanger using the following standard fittings A 1 off Elbow BSP male x BSP female B 1 of...

Страница 6: ...Fitting the Appliance page 6 ...

Страница 7: ...arrying conductors become taut before the earthing conductor if the cable should slip out of the cable grip 1 With the outer case assembled as in Outer Case 1 4 remove the 2 screws securing the thermostat cover to the facia panel 2 Fit the input cable to the terminal strip and clamp using the cable grip provided and clamp the incoming cable into the cable clips provided on the outer case side pane...

Страница 8: ...inder must be used If a self priming indirect type is employed it must be of adequate size and applied strictly in accordance with the cylinder manufacturers instructions FUEL ECONOMY Better fuel economy is achieved by exercising control of the boiler by means of a room thermostat and or a cylinder thermostat as appropriate ALLOWING THE BOILER TO CYCLE ON THE BOILER THERMOSTAT DOES NOT PRODUCE THE...

Страница 9: ...ght the pilot as previously described Operate the burner and allow the system to reach normal operating temperature Make further checks for leaks and check the burner setting pressure adjusting if necessary This is done by adjusting the throttle screw red plastic surround in either direction as required Fig 7 Remove the pressure gauge and tighten the pressure test point sealing screw The boiler an...

Страница 10: ... c Remove the injector from the feed pipe clean and replace 15 Clean the pilot as follows Unscrew the pilot tubing nuts at both ends and remove the pilot tube Remove and clean the pilot injector and clean the pilot shroud Fig 15 16 Re assemble the pilot components and then the burner in reverse order of dismantling 17 Refit the burner and controls assembly checking that the door seal is undamaged ...

Страница 11: ...Servicing the Unit page 11 ...

Страница 12: ...uple nuts at the valve and at the pilot bracket 3 Disconnect the pilot feed pipe at the valve and at the pilot bracket ensuring that the pilot injector is not misplaced 4 Disconnect the electrode lead and remove the piezo unit 5 Remove the screw securing the electrical terminal cover to the gas valve Disconnect the electrical connections 6 Remove the valve complete with the heat shield and inlet p...

Страница 13: ...Changing Components page 13 ...

Страница 14: ...Short Parts List page 14 Click here for Helplines ...

Отзывы: