check its operation:
i.
Switch the fan on.
ii.
Go outside the building and place a
hand over the rectangular exhaust
outlet of the terminal. The fan should
be heard to increase to “boost” speed
within approximately two seconds.
iii.
Remove the hand. The fan should
revert to normal speed after
approximately three seconds.
!
The unit includes a blocked flue
sensor system. To check its operation:
i.
Switch the fan on.
ii.
Block off the rectangular exhaust outlet of the terminal. The system should shut down
within ten seconds.
iii.
After checking turn off the electrical supply to the appliance. If the above tests are
not satisfactory, refer to the servicing section of this manual.
8.8 Terminal guarding.
Position the terminal guard to wall, align and ensure equal clearances around fan box.
Mark off the four fixing positions on wall. Remove the terminal guard and drill at the
marked positions, four holes using a no. 10 drill. Insert wall plugs, reposition the
terminal guard and secure to wall using four screws supplied.
9. GAS SUPPLY INSTALLATION
9.1 Gas supply connection.
1.
Connect the supply line to the appliance.
2.
Unless the supply pipe connection is from the left
front side, the supply pipe will have to be formed to
avoid various components below the burner. If a
visible connection is to be made, it will be necessary
to cut a small notch in the side of the fret to allow
the gas pipe to pass.
3.
If gas supply is to the rear of the appliance, then
entry is via the large grommet, at the lower left hand
side of the back face. Pierce the grommet to allow
pipe entry (See figure 29).
4.
Check the installation pipework for gas soundness
in accordance with the current edition of BS6891.
Do not use leak detection sprays on this appliance.
Page 27
INSTALLER GUIDE
Figure 28.
Figure 29.