6 Settings
6 Settings
6.1
Access to USER parameters
To display/modify the list of USER parameters, proceed as follows:
Important
The factory settings for certain settings may differ based on the
market the product is destined for.
6.2
List of USER parameters
Tab.9 Table of parameters
Name
Description
Factory
value
Mini
mum
Maxi
mum
Level
AP016
CH operation
0: Off
1: On
1
–
–
User
AP017
Domestic hot water (DHW)
0: Off
1: On
1
–
–
User
AP073
Average external temperature [°C] when switching from summer/
winter mode (with outside sensor)
22
10
30
User
AP074
Force summer mode (with outside sensor)
0: Auto according to AP073
1: Summer
0
–
–
User
DP004
Anti-legionella function
0: Disabled
1: Weekly
2: Daily (only available with Room Unit)
0
–
–
User
DP070
Domestic hot water temperature setpoint.
In the case of operation with a calorifier tank and programming via
room unit corresponding to the comfort setpoint [°C]
60
35
60
User
DP200
DHW mode:
0: Domestic hot water programming (only available with Room Unit)
1: Manual (boiler with calorifier tank) – Preheating active (instanta
neous boiler)
2: Antifreeze (boiler with calorifier tank) – No preheating (instantane
ous boiler)
2
–
–
User
Fig.7 Accessing the user parameters
on the menu
turn the
turn the
knob until the
knob;
to confirm;
modify the value of the parameter using
the Press the
key to confirm;
Press the
key to exit.
appears. Press the
key to confirm;
knob until you reach the required setting. Press the
key
press the + keys simultaneously, the symbol
bar starts to flash;
16
400 Combi 2