3.11
Derating characteristic of asynchronous machines without forced ventilation
Standard asynchronous machines without forced ventilation normally require a derating
of the maximum continuous current at speeds lower than the rated speed.
Figure 192:
Typical derating of standard asynchronous machines (without forced ventilation)
Two derating factors are provided which proportionally to the rated speed lower the max-
imum continuous current at the standstill point and at half the rated speed. Based on this
a current limit curve is interpolated from the available current values again and is used for
the calculation of the l
2
t actual value (see
). The maximum continuous current
is fixed to the rated current if it is above the rated speed.
Figure 193:
Speed-dependent l
2
t overload monitoring of asynchronous machines without forced ventilation
25
50
75
100 125 150
20
40
80
100
60
6.46[1]
6.46[0]
5000_0361_rev01.cdr
Df
%
Motor speed / Nominal speed, %
(Self ventilated)
N
D
N
D
N
1
N
6.46[0]
6.46[1]
6.46[0], 6.46[1]
18.22
5000_0362_rev01.cdr
Ref
I
107.9
Df
Motor I t derating factors
2
Speed actual value
Nominal current
I´act
I values
2
Содержание b maXX BM5800
Страница 10: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 10 of 814 Contents ...
Страница 724: ...Monitoring Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 724 of 814 3 11 ...
Страница 756: ...Error descriptions Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 756 of 814 4 5 ...
Страница 800: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 800 of 814 ...
Страница 808: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 808 of 814 ...
Страница 814: ...Parameter manual b maXX BM5800 Document No 5 16029 03 Baumüller Nürnberg GmbH 814 of 814 Notes ...
Страница 815: ......