![Baumuller b maXX 1000 Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/baumuller/b-maxx-1000/b-maxx-1000_parameter-manual_2711401026.webp)
Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
26
4.3
P0041
The upper lower limits are to prevent operation errors and machine damage. If the output
frequency upper limit is 50 Hz and the maximum output frequency is 60 Hz, the output
frequency will be limited to 50 Hz. If the output frequency lower limit is 10 Hz, and the min-
imum output frequency
is set to 1.0 Hz, then any command frequency between
1.0 to 10 Hz will generate a 10 Hz output from the drive.
The maximum output frequency
is regarded to 100 %.
This parameter must be equal to or less than the output frequency upper limit
.
Output frequency lower limit value = (
⋅
) / 100
Figure 8:
V/f curve
P0041
Ausgangsfrequenz: untere Grenze
0.0 to 100.0 %
EE
Output frequency: lower limit
0.0 %
STOP
BM_u_OutFreqlowerLimit
10:1
-