![Baumuller b maXX 1000 Скачать руководство пользователя страница 116](http://html.mh-extra.com/html/baumuller/b-maxx-1000/b-maxx-1000_parameter-manual_2711401116.webp)
Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
116
4.3
P1184
Only external terminal JOG (MI3 to MI5 or MI7 to MI12)
can be used.
= 5 (jog mode) and the jog command is „ON“, the b
maXX
®
1000 will accelerate from minimum output frequency
to jog frequency
. When the jog command is „OFF“, the b maXX
®
1000 will decelerate from jog
frequency to zero. The used accel/decel time is set by the jog ramp-up/ramp-down time
(
Before using the JOG command, the drive must be stopped first and operation mode
must be set to 5. During Jog operation, other operation commands are not ac-
cepted, except commands via the FORWARD, REVERSE and STOP keys on the digital
keypad.
Figure 51:
Jog ramp-up/ramp-down time
P1184
HLG Tippbetrieb Frequenz
0.10 to 600.00 Hz
EE
RFG jog frequency
6.00 Hz
ON
BM_u_RFGJogFrequency
100:1 s