Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
110
4.3
P1165
This parameter sets the function of the AO1 output 0 to +10 V
DC
(ACM is signal ground),
see also
P1166
This parameter sets the voltage range of the analog output signal AO1.
When
is set to 0, the analog output voltage is directly proportional to the output
frequency of the b maXX
®
1000. With
set to 100 %, the maximum output fre-
quency
of the b maXX
®
1000 corresponds to +10 V
DC
on the AO1 output.
Similarly, if
is set to 1, the analog output voltage is directly proportional to the
output current of the b maXX
®
1000. With
set to 100%, then 2.5 times the rated
current corresponds to +10 V
DC
on the AO1 output.
For Example: When using the meter with full scale of 5 volts, adjust
to 50 %. If
is set to 0, then 5 V
DC
will correspond to maximum output frequency.
P1167
This parameter selects the mode of the analog voltage output or analog current output.
For further information see
P1165
Analoges Ausgangssignal AO1
0 to 1
EE
Analog output signal AO1
0
STOP
BM_u_AnalogOutputSignal1
1:1
Value
Meaning
0
Analog frequency meter (0 to maximum output frequency)
1
Analog current meter (0 to 250 % of rated current)
P1166
Analoges Ausgangssignal Verstärkung AO1
0 to 200 %
EE
Analog output gain AO1
100 %
STOP
BM_u_AnalogOutputGain AO1
1:1
NOTE
Any type of voltmeter can be used. If the meter reads full scale at a voltage less than 10 V,
should be set using the following formula:
= ((meter full scale voltage)/10) x 100%
P1167
AO2 Auswahl Ausgang Mode
0 to 2
EE
AO2 terminal mode selection
0
STOP
BM_u_TerminalModeSelectionAO2
1:1
Value
Meaning
0
AVO2 (analog voltage output)
1
ACO2 by 0 to 20 mA (analog current output)
2
ACO2 by 4 to 20 mA (analog current output)
Содержание b maXX 1000
Страница 1: ...E 5 07004 03 b maXX 1000 Parameter manual ...
Страница 65: ...Parameter Parameter manual b maXX 1000 Document no 5 07004 03 65 of 208 4 Figure 18 Base block speed search ...
Страница 164: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 164 of 208 A ...
Страница 208: ...Parameter manual b maXX 1000 Document no 5 07004 03 Baumüller Nürnberg GmbH 208 of 208 Notes ...
Страница 209: ......