9252000892 Rev A
BE1-50/51B-229 General Information
1-1
SECTION 1
•
GENERAL INFORMATION
INTRODUCTION
BE1-50/51B-229 Overcurrent Relays are self-powered, microprocessor-based, non-directional phase or
ground relays that monitor single-phase ac current and provide accurate instantaneous and time-over-
current protection for 50 or 60 Hz power systems.
BE1-50/51B-229 relays are direct replacements for General Electric Type SFC relays. BE1-50/51B relays
offer true plug and play convenience; they can be installed in an existing SFC relay case with no wiring
changes required. Table 1-1 lists the SFC relays that can be replaced by the BE1-50/51B-229.
Table 1-1. Type SFC Relays Suitable for Direct Replacement
SFC Model
Time Curve Type
Output Contact Circuits
SFC151
∗∗
A
Inverse
1
SFC153
∗∗
A
Very Inverse
1
SFC177
∗∗
A
Extremely Inverse
1
∗
Represents any allowed character per GE publication GEK-36807.
An existing SFC relay is replaced with a BE1-50/51B-229 relay by performing the following simple steps.
1. Configure your new BE1-50/51-229 relay with the desired settings.
2. Remove the existing SFC relay.
3. Attach the cover adapter plate to the existing case.
4. Insert the BE1-50/51B-229 relay into the case.
5. Install the existing SFC connection plug.
6. Install the new Basler Electric relay cover.
FEATURES
BE1-50/51B-229 Overcurrent Relays have the following standard features.
•
Independent time and instantaneous elements
•
Secure breaker tripping from the relay front panel
•
Direct-reading front panel controls
•
Minimum pickup setting for safety during installation
•
Time characteristics extend to a pickup multiple of 40
•
Rugged draw-out construction
•
Gravity latching targets retain indication without power
•
Built-in accuracy eliminates internal adjustments
•
Minimum transient overreach
•
Field-selectable characteristic curves similar to either GE IAC or ABB type curves
•
Field-selectable instantaneous or integrating reset function
•
Field-selectable 50 or 60 Hz operation
•
Field-selectable 0.0 or 0.1 second fixed, instantaneous time delay
Advantages
BE1-50/51B-229 Overcurrent Relays have many advantages over other overcurrent relays. The primary
advantages are listed below.
•
Time characteristics are defined by equations and graphs
•
Field-selectable time characteristics
•
Very low burden extends the linear range of the system CTs
•
Self-powered from the sensed current
•
Continuous
automatic
calibration
Содержание BE1-50/51B-229
Страница 1: ...INSTRUCTION MANUAL FOR OVERCURRENT RELAY BE1 50 51B 229 Publication 9252000892 Revision A 03 08 ...
Страница 2: ......
Страница 6: ...iv BE1 50 51B 229 Introduction 9252000892 Rev A This page intentionally left blank ...
Страница 8: ...vi BE1 50 51B 229 Introduction 9252000892 Rev A This page intentionally left blank ...
Страница 10: ...ii BE1 50 51B 229 General Information 9252000892 Rev A This page intentionally left blank ...
Страница 20: ...ii BE1 50 51B 229 Controls and Indicators 9252000892 Rev A This page intentionally left blank ...
Страница 24: ...2 4 BE1 50 51B 229 Controls and Indicators 9252000892 Rev A This page intentionally left blank ...
Страница 26: ...ii BE1 50 51B 229 Functional Description 9252000892 Rev A This page intentionally left blank ...
Страница 30: ...ii BE1 50 51B 229 Installation 9252000892 Rev A This page intentionally left blank ...
Страница 34: ...4 4 BE1 50 51B 229 Installation 9252000892 Rev A This page intentionally left blank ...
Страница 36: ...ii BE1 50 51B 229 Testing 9252000892 Rev A This page intentionally left blank ...
Страница 42: ...ii BE1 50 51B 229 Time Characteristic Curves 9252000892 Rev A This page intentionally left blank ...
Страница 45: ...9252000892 Rev A BE1 50 51B 229 Time Characteristic Curves A 3 Figure A 3 D Definite Time Similar to ABB CO 6 ...
Страница 50: ...A 8 BE1 50 51B 229 Time Characteristic Curves 9252000892 Rev A Figure A 8 BS142 B Very Inverse ...
Страница 51: ...9252000892 Rev A BE1 50 51B 229 Time Characteristic Curves A 9 Figure A 9 BS142 C Extremely Inverse ...