BE1-32R, -32 O/U INSTALLATION 4-15
NOTE
Be sure the relay case is hard-wired to earth ground with no smaller than 12 AWG copper
wire attached to the ground terminal on the rear of the relay case. When the relay is
configured in a system with other protective devices, it is recommended to use a
separate lead to the ground bus from each relay.
CONNECTIONS
Incorrect wiring may result in damage to the relay. Be sure to check model and style number before
connecting and energizing the particular relay.
Except as noted above, connections should be made with minimum wire size of 14 AWG. The following
illustrations provide information on relay connections.
Control circuit connections are shown in Figure 4-17.
Internal connections are shown in Figures 4-18 through 4-21.
Typical external connections are shown in Figures 4-22 and 4-23.
Sensing input connections are shown in Figures 4-24 through 4-29.
NOTES:
1.
Overpower, underpower, and power supply status output contacts are optionally normally open or normally closed.
2.
Auxiliary output contacts are optionally normally open, normally closed, or SPDT. if SPDT, power supply status is not
available.
Figure 4-17. Control Circuit Diagram