Program Levels 

5

 

 

 

Programming order 

 

Unlock the keyboard. 

 

Adjust the configuration parameters. 

 

If needed, restrict the access again  
by adjusting the 

Lock Keyboard

 parameter. 

Access control (Hidden level) 

 

Hold 

 

depressed while turning  

the power supply on and until  

Loc"

 appears. 

 

Set keyboard locking mode  
according to Table 1.

 

Basic level 

At power-on, BPT50-A enters Basic level.  
At this level, the device indicates  
the measured pressure with a resolution, 
according to the 

Point Position

 parameter. 

 

If the measured value is greater than 

Display High

 

+ 10, the display shows 

blinking error message 

{++}

 

When the measured value is less than 

Display Low

 - 10, 

L__V

 is displayed. 

 

Either error message may appear 
on the display also as a result  
of a damaged sensor. 

Configuration level 

 

Enter from Basic level by pressing  

and holding 

 until 

conF

 appears 

on the display.  

 

Choose a parameter using 

 or 

 

.  

 

To enter parameter value  

adjustment mode, press 

 

 

If no key has been pressed for a while, 
the device automatically returns  
to Basic level, storing all confirmed 
changes. 

 

For quick exiting and saving,  

use key combination 

 

+

 

 or 

select 

rtn

 and press 

 

Содержание BPT50-A

Страница 1: ...OLLSJ SWEDEN tel 46 0 40 88009 fax 46 0 40 929877 e mail info basi se BPT50 A OPERATION MANUAL Please read this Operation Manual before mounting and operating Save the Manual for future references PRE...

Страница 2: ...Screw the BPT50 A transmitter to its exact place using a preinstalled bush with a female thread matching the transmitter s one etc To ensure hermetical mounting use a proper gasket e g DIN16258 The r...

Страница 3: ...roes appears on the display and the rightmost digit blinks To select another digit press The 4 rightmost digits can accept values from 0 to 9 and the leftmost digit can accept the value or none To inc...

Страница 4: ...99 9999 0 255 0 3000 no YES 9999 9999 L_ _V d EY ESP E EY Description Display decimal point position Display value at low limit of the input range Display value at high limit of the input range Consta...

Страница 5: ...g to the Point Position parameter If the measured value is greater than Display High 10 the display shows blinking error message When the measured value is less than Display Low 10 L__V is displayed E...

Страница 6: ...g Input Filtration Low pass filter This first order filter acts ONLY within a certain band around filter output value This has been designed to cut periodic noises outside the communication signal spe...

Страница 7: ...gether with household waste material If disposed of within European Union this product should be treated and recycled in accordance with the laws of your jurisdiction implementing the WEEE Directive 2...

Страница 8: ...Warranty and Support serial number manufacturing date QC check mark passed stamp BASI Instrument AB p o box 53 SE 275 06 VOLLSJ SWEDEN tel 46 0 40 88009 fax 46 0 40 929877 e mail sales basi se QD 8 2...

Отзывы: