7.3.2. “bEEP” menu
This menu contains options connected with acoustic signal :
"
AL
”
-
if this parameter is set to “
on
”, any critical situation causes by acoustic signal
"
r1
”
-
if this parameter is set to “
on
”, activation of relay
R1
causes by acoustic signal
"
r2
"
-
if this parameter is set to “
on
”, activation of LED
R2
causes by acoustic signal
"
r3
"
-
if this parameter is set to “
on
”, activation of LED
R3
causes by acoustic signal
"
r4
"
-
if this parameter is set to “
on
”, activation of LED
R4
causes by acoustic signal
Acoustic signal (turned on by e.g. relay ) can be turned off by pressing of any
button
7.3.3. “inPt” menu (common parameters)
This menu presets the measurement input:
“
tYPE
"
- type of the input / sensor. This parameter can be set to values:
”0-20”
- current input - range 0..20 mA,
”4-20”
- current input - range 4..20 mA,
”0-5”
-
voltage input - range 0..5 V,
”1-5”
-
voltage input - range 1..5 V,
”0-10”
-
voltage input - range 0..10 V,
”2-10”
-
voltage input - range 2..10 V,
”60”
-
voltage input - range 0..60 mV,
”75”
-
voltage input - range 0..75 mV,
”100”
-
voltage input - range 0..100 mV,
”150”
-
voltage input - range 0..150 mV,
”Pt 1”
-
Pt 100 input,
”Pt 5”
-
Pt 500 input,
”Pt10”
-
Pt 1000 input,
”tc k”
-
thermocouple input, type K,
”tc S”
-
thermocouple input, type S,
”tc J”
-
thermocouple input, type J,
”tc t”
-
thermocouple input, type T,
”tc n”
-
thermocouple input, type N,
”tc r”
-
thermocouple input, type R,
”tc b”
-
thermocouple input, type B,
”tc E”
-
thermocouple input, type E.
For current and voltage inputs displayed values are defined by parameters
“Lo C”
,
”Hi
C”
(or by user defined characteristic points) and parameter
”Pnt”
.
”FiLt”
- option allows to change the filtration time constant. Expressed in seconds. Acceptable
values range from 0 (no filtration ) to 255.