Installation and operation
18 / 28
1043613
EN
Information about nozzles, as per gas category, may be found in table 2, section
'Technical Data'.
The nozzles are part of the supplied set.
5. Re-tighten the main burner's nozzle (a).
6. Set the air controller (f) within the distance provided in Table 2.
7. Re-tighten the screw (g).
8. When the nozzle is exchanged, check the appliance's operation, as set forth in
section
'Functional Control'
.
9. Change the previous data on the rating plate, by putting the sticker with rating
data of the new gas type.
Functional Control
• Before test-running, install the appliance in a well ventilated room and remove
any flammable materials from the vicinity of the appliance.
• Before starting, perform the tightness test using soapsuds. Cover connections
and pipe fittings with soapsuds. Leakages are revealed when bubbles are
produced on couplings and pipe connections. Other method involves
observation of gas meter. No reaction of gas meter indicates that there are no
gas leakages.
CAUTION!
Do not use open flame for checking tightness of gas installation!
• Restart the appliance, observing indications in section
'Appliance Start-up'
.
• Check the appliance for gas tightness (see DVGW data sheets, TRGI/TRF).
• Verify burner's ignition.
– Verify flame shape.