Operation
Ex p Control unit
APEX
px
Page 64 of 96
01-37A2-7D0001_px_Manual_Exp-Control-Unit_20210923_0_en.docx
Rev. 0
Functions
Switching value
Function
Open valve 1
Cooling using purging air
Open valve 2
Cooling using valve 2, e.g. vortex
Deactivating of Ex p (K1)
The enable is withdrawn on exceeding the
temperature
Warning in plain text
A plain text warning is issued in the
messages area on exceeding the
temperature
Plain text alarm message
A plain text alarm is issued in the
messages area on exceeding the
temperature
Setting “Temperature sensors“
Procedure
Connect the computer to the Ex p control unit / control station
Activate the programming switch
Log into the WEB interface at the user level
Select the Extended / sensors menu
Activate the corresponding button for the required temperature sensor,
e.g. temperature sensor 1, by clicking PT100 or 1000
Manual button changes to
Confirm the pop-up window with changed value
Select the display unit in °C or °F by clicking and activating the button.
Display changes to
Confirm the pop-up window with changed value
Select the T-sensors / temperature sensor 1 menu
The signal for the active sensor is displayed by the green detector
Save switching value 1
e.g. 25 °C
Confirm the pop-up window with changed value
Save switching value 2
e.g. 35 °C
Confirm the pop-up window with changed value
Save switching value 3
e.g. 60 °C
Confirm the pop-up window with changed value
Save switching hysteresis
e.g. 5 K
functions will be activated and deactivated at a hysteresis
of 5K