Ex p Control unit
APEX
px
Operation
Rev. 0
01-37A2-7D0001_px_Manual_Exp-Control-Unit_20210923_0_en.docx
Page 53 of 96
7
Operation
Operation of the Ex p control unit for end users is described in the following
chapters. A description of the configuration and settings is provided in separate
operating instructions.
The complete solution starts automatically after connecting the purge gas
supply and the supply voltage. System statuses can be queried via the WEB
interface.
WEB interface
The Ex p control station is supplied with a fixed IP address as standard.
Standard IP address (factory default): 192.168.11.101
The following options are available to establish a connection between laptop and
PC.
Laptop (192.168.11.99 // 255.255.0.0)
Direct
Indirect
USB / LAN interface converter
Ex p Control Unit (192.168.11.101)
Adjusting the LAN connection
Settings for the LAN interface on the PC (or converter / managed switch) must be
programmed so that it can communicate with the Ex p control unit.
Settings:
Configuration of the LAN interface:
Extended / speed: 100 Mbps full duplex
Properties of internet protocol Ver. 4 (TCP/IPv4):
Activation of fixed IP address
IP address: 192.168.11.99
Subnet mask: 255.255.0.0