Ex p control unit
Motor purge controller
Operation
Rev. 0
01-37A2-7D0003_Operating instructions_MPC_20210923_0_en.docx
Page 47 of 96
7
Operation
The following chapters describe the operation of the Ex p control unit for the end
user. The configuration and setting description is given in a separate operating
manual.
The complete solution is self-starting after connection of purge gas supply and
supply voltage. System states can be queried via the WEB interface.
7.1
Web interface
The Ex p control unit is supplied with a fixed IP address as standard.
Standard IP address (delivery status): 192.168.11.101
The following options are available for establishing a connection between laptop
and PC.
Laptop (192.168.11.99 // 255.255.0.0)
Direct
Indirect
USB / LAN Interface converter
Ex p control unit (192.168.11.101)
Setting the LAN connection
The settings of the LAN interface on the PC (or converter / managed switch) must
be parameterised so that it can communicate with the Ex p control unit.
Settings:
Configuration LAN interface:
Extended / speed: 100 Mbps full duplex
Properties of the Internet Protocol Ver. 4 (TCP/IPv4):
Activation of fixed IP address
IP address: 192.168.11.99
Subnet mask: 255.255.0.0