INSTALLATION INSTRUCTIONS

800.533.3948 • www.barronltg.com 

4

Self-test/Self-diagnostics testing for numeric indicator

1. 

Introduction

    

Once the unit is properly installed according to the installation instruction and AC power is supplied, the EXIT sign

will illuminate. The numeric Indicator will display the status of the unit. 

2. 

Self-test/Self-diagnostics 

(G2-NI option)

The self-test/self-diagnostics function is a factory preset without any field adjustment. The automatic self-test/

self-diagnostics feature serves the following test.
a. Online real-time monitoring of battery and LED(s): identifies battery charging, disconnection and failure along with 

    LED failures.
b. Self-testing with a 60 second discharge once every 30 days (conforming to NFPA code requirements), after AC 

    power has been supplied for a minimum of 24 hours. 
c. Self-testing with a 30 minute discharge once every 180 days, after AC power has been supplied for a minimum of 24 

    hours.
d. Self-testing with a 90 minute discharge once every 365 days (conforming to NFPA code requirements), after AC 

    power has been supplied for a minimum of 24 hours.

3. 

Fault Indication

 

      3                               Battery Recharge Failure*

      4                               Battery Disconnection

      5                               LED Failure

      6                               Battery Failure**

 * A battery recharge failure will display if the battery is NOT able to recharge within the 24 hour charge time.

** A battery failure will display if the battery is NOT able to operate the unit for the period of the discharge test.

0  Normal service 

1  Battery charging

 

2  Emergency mode 

3  Battery recharge failure 

4  Battery disconnected

 

5  LED failure 

6  Battery Failure

 

7  Manual testing 

8  Yearly/monthly self-check testing mode 

Numeric Indicator  Fault Descrip

on 

10070040 Rev 6 - 11/18

VEX SERIES

Содержание EXITRONIX VEX Series

Страница 1: ... housing open the battery door and connect the battery terminals Close door and push the test button to confirm Allow to charge for 24 hours before the 90 minute test Then follow Self test Self diagnostics testing section 1 IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS When using electrical equipment basic safety precautions should always be followed including the following DISCONNE...

Страница 2: ...or and connect the battery terminals Close door and push the test button to confirm Allow to charge for 24 hours before the 90 minute test Then follow Self test Self diagnostics testing section End Mounting 1 Attach sign to canopy 7 by inserting canopy into sign then slide to the top to lock 2 Feed transformer leads through the side hole of the housing 4 making sure to secure the wires into wire g...

Страница 3: ...ions see Electrical Connection section 4 All electrical connections should be made inside the VEPA junction box 5 Fasten VEPA to canopy using 8 32 x machine screws Electrical Connections All electrical connections should be made inside junction box Make electrical connections as follows 120V AC 277V AC White Common White Common Black 120V Orange 277V Green Ground Green Ground Note Cap unused leads...

Страница 4: ...de requirements after AC power has been supplied for a minimum of 24 hours c Self testing with a 30 minute discharge once every 180 days after AC power has been supplied for a minimum of 24 hours d Self testing with a 90 minute discharge once every 365 days conforming to NFPA code requirements after AC power has been supplied for a minimum of 24 hours 3 Fault Indication 3 Battery Recharge Failure ...

Страница 5: ...at the unit is in testing mode GREEN RED FLASHING indicates that the battery is charging RED STEADY and BLINKING would indicate a fault or a service alert The LED indicator would be off when the unit is in emergency mode Refer to Fault Indication section for more details 2 Self Diagnostic Service The self diagnostic function is factory preset without any field adjustment The automatic self diagnos...

Страница 6: ... the table below 5 Operation During an electrical power failure the unit will transfer into emergency mode and stay illuminated for a minimum of 90 minutes To test the unit the battery needs to be charged initially for 24 hours before depressing the test button to do manual test On pressing the test button the unit will transfer into a simulated emergency mode with the LED indicator flashing or bl...

Отзывы: