Ceiling Mounting

1. Attach the sign to canopy (7) by inserting the canopy 

    into sign then slide to the side to lock.
2. Feed transformer leads through top hole of housing (4), 

    making sure to secure the wires into wire guides found 

    at the edge of the sign.
3. Make electrical connections: see 

Electrical Connection

 

    section. 
4. Attach mounting plate (8) to junction box (10). 
5. Feed the excess wires into junction box. Align holes in 

    canopy with those in mounting plate. Use supplied 

    screws to secure canopy to the mounting plate, 

    tightening until canopy is pulled tightly to the ceiling.
6. For units without battery door: connect the battery 

    terminals first before securing the faceplate to the 

    housing.
7. Remove the diffuser (3) from inside of faceplate (1) 

    in order to remove snap-in chevrons (2) as required. 

    Store the unused chevron covers in a safe place. 

    Then snap the faceplate (1) to housing (4).

8. For double-faced signs, replace the backplate with the 

    extra EXIT faceplate.
9. For units with a battery door: after securing the faceplate 

    to the housing open battery door and connect the battery 

    terminals. Close door and push the test button to 

    confirm. Allow to charge for 24 hours before the 90 

    minute test. Then follow 

Self-test/Self-diagnostics 

    testing

 section.

End Mounting

1. Attach sign to canopy (7) by inserting canopy into sign 

    then slide to the top to lock.
2. Feed transformer leads through the side hole of the  

    housing (4), making sure to secure the wires into wire 

    guides found at the edges of the sign.
3. Make electrical connections: see 

Electrical Connection

 section. 

4. Attach mounting plate (8) to junction box (10). 
5. Feed excess wire into the junction box.
6. For units without a battery door: connect the battery terminals before securing the faceplate to the housing.
7. Align holes in canopy with those in the mounting plate. Use supplied screws to secure the canopy to the mounting 

    plate, tightening until canopy is pulled tightly to the ceiling.

Faceplate
Chevron Cover
Red/Green Diffuser

Enclosure
Backplate
Canopy Plug

Canopy
Mounting Plate
Wire Nuts

Junction Box

(Building Supply)

INSTALLATION INSTRUCTIONS

800.533.3948 • www.barronltg.com 

2

Junction Box

(Building Supply)

Faceplate

Chevron Cover
Red/Green

Diffuser

Enclosure
Backplate
Canopy Plug

Canopy
Mounting Plate
Wire Nuts

10070040 Rev 6 - 11/18

VEX SERIES

Содержание EXITRONIX VEX Series

Страница 1: ... housing open the battery door and connect the battery terminals Close door and push the test button to confirm Allow to charge for 24 hours before the 90 minute test Then follow Self test Self diagnostics testing section 1 IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS When using electrical equipment basic safety precautions should always be followed including the following DISCONNE...

Страница 2: ...or and connect the battery terminals Close door and push the test button to confirm Allow to charge for 24 hours before the 90 minute test Then follow Self test Self diagnostics testing section End Mounting 1 Attach sign to canopy 7 by inserting canopy into sign then slide to the top to lock 2 Feed transformer leads through the side hole of the housing 4 making sure to secure the wires into wire g...

Страница 3: ...ions see Electrical Connection section 4 All electrical connections should be made inside the VEPA junction box 5 Fasten VEPA to canopy using 8 32 x machine screws Electrical Connections All electrical connections should be made inside junction box Make electrical connections as follows 120V AC 277V AC White Common White Common Black 120V Orange 277V Green Ground Green Ground Note Cap unused leads...

Страница 4: ...de requirements after AC power has been supplied for a minimum of 24 hours c Self testing with a 30 minute discharge once every 180 days after AC power has been supplied for a minimum of 24 hours d Self testing with a 90 minute discharge once every 365 days conforming to NFPA code requirements after AC power has been supplied for a minimum of 24 hours 3 Fault Indication 3 Battery Recharge Failure ...

Страница 5: ...at the unit is in testing mode GREEN RED FLASHING indicates that the battery is charging RED STEADY and BLINKING would indicate a fault or a service alert The LED indicator would be off when the unit is in emergency mode Refer to Fault Indication section for more details 2 Self Diagnostic Service The self diagnostic function is factory preset without any field adjustment The automatic self diagnos...

Страница 6: ... the table below 5 Operation During an electrical power failure the unit will transfer into emergency mode and stay illuminated for a minimum of 90 minutes To test the unit the battery needs to be charged initially for 24 hours before depressing the test button to do manual test On pressing the test button the unit will transfer into a simulated emergency mode with the LED indicator flashing or bl...

Отзывы: