Electrical Connections
All electrical connections should be made inside the J-box. Make electrical
connections as follows (Fig. 5):
120VAC
277VAC
White - Common
White - Common
Black - 120VAC
Orange - 277VAC
Note:
Cap unused leads to prevent shorting.
Remote Lamp Connection: 3.6V, 2W
1. Remove the ground male connector from the female connector. (Fig. 6)
2. Plug the remote male connector into the female connector. (Fig. 7)
3. Connect extended remote head wires to the remote wires using wire
nuts. Yellow is positive (+) and purple is negative (–).
Maintenance
We recommend that the fixture be tested regularly in accordance with local codes. Replace the batteries as needed if the
discharge time does not achieve 90 minutes.
Operation
Press the test button. The LED heads will turn on and the LED indicator light will turn off. Release the test switch, the LED
indicator will turn on and the LED heads will turn off.
Troubleshooting Guide
If the LED heads or the LED indicator do not illuminate, check the following:
1. Check AC supply; verify that the unit has 24 hours AC supply.
2. Check the battery connections.
3. Discharge the battery and charge the battery for 24 hours, or 48 hours for models with two batteries, and then retest.
4. If above troubleshooting hints do not solve the problem, contact the factory for assistance.
Orange 277VAC
White Neutral
Black 120VAC
Integral
LED Head
Remote
Heads
(Option)
Charge
PCBA
Not remote
capable have 1
battery.
Remote capable
models have 2
batteries.
Fig. 5 - Wiring Diagram
Fig. 7
Fig. 6
Use Flexible Conduit Only.
Ground Male Connector
Female Connector
Remote Wire
Remote Male
Connector
Female Connector
10070204
R
EV 5 - 05/22
3
800-533-3948 www.barronltg.com
LED-51/52 Series
Installation Instructions