B-3) Liquid Level Controls: 

It is recommended to use a liquid level control system 

that allows the on and off point to be separated by at least 

twelve inches. An additional set point (lag point) should 

be incorporated with an alternator switching system for 

a duplex (two pump) station. A high level alarm may be 

required to alert maintenance personnel that there is a 

high water situation in the wet well should the output of the 

pump station drop below the inflow rate. A low level cut off 

may be installed to provide system shutdown if the main 

level control system malfunctions. The off point should be 

positioned so that the liquid level never drops below the 

minimum continuous duty point for the pump shown in 

figure 1.

B-4.1) Electrical Connections:

WARNING! - All model pumps and 

control panels must be properly 

grounded per the NATIONAL 

ELECTRIC CODE or CANADIAN 

ELECTRIC CODE, State, Province 

and local codes. Improper 

grounding voids warranty.

B-4) Power/Control Cord:

 

The power/control cord used with pump has a patent 

pending “quick disconnect” feature that allows the cord 

to be easily attached and disconnected at the pump. The 

maximum amperage rating for the cord is cast in the top of 

the cast stainless mounting plate. The voltage connection 

for the motor is determined by the cord assembly used. 

Low voltage cords (208 & 230 Volt) utilize a molded quick 

connect plug that is colored black. High voltage cords 

(460 & 575 Volt) utilize a molded quick connect cord 

that is colored orange. 

It is important to verify that the 

cord being used is rated for the nameplate voltage 

and amperage rating shown on the pump nameplate.

 

Refer to Chart on page 7.

 No internal wiring adjustments 

are necessary for dual and tri-voltage pumps. All jumper 

connections to set the proper voltage are made by the cord 

plug itself.

A flat alignment mark is molded into the plug and mating 

socket on the pump. These should be used as a visual 

indication as to the correct orientation of the plug. Insert the 

plug into the pump and install the two 12 mm socket head 

cap screws into the clamping plate. Slowly tighten the two 

screws alternating back and forth until the clamping plate is 

drawn down flush to the top of the cord boss on the pump. 

The two screws should be torqued until the plate is down to 

a point where 

metal to metal

 contact is made between the 

stainless steel plate and pump housing. (See Fig. 2)

The cord assembly mounted to the pump must not be 

modified in any way except for shortening to a specific 

application. Any splice between the pump and the control 

panel must be made in accordance with all applicable 

electric codes. It is recommended that a junction box (if 

used) be mounted outside the sump or be of at least Nema 

6 or 6P construction with NEMA 6 or 6P watertight cord 

grips if located within the wet well. A water and vapor tight 

seal fitting 

MUST

 be used in conduit leaving the wet well 

to prevent moisture and gasses from reaching the control 

panel. Prior to installation, the pump power cable should be 

inspected for nicks or damage. If damaged, the cord should 

be replaced before installation. 

CORD CLAMPING PLATE SHOULD BE DRAWN METAL 

TO METAL (50 FT/LBS BOLT TORQUE). IF A GAP 

EXISTS CONTINUE TO TIGHTEN BOLTS. DO NOT USE 

ANY TYPE OF SEALANT OR GREASE ON THE CORD 

ENTRY.

 

DO NOT USE THE POWER CORD TO LIFT PUMP.

B-4.1) Electrical Connections:

When the electrical connections are made, the lead wires 

from the power cable should be stripped so that the ground 

wire is at least two inches longer than the power leads. 

This will ensure that if the cable is inadvertently pulled out 

of the connection point, the ground wire will be the last lead 

to break the circuit.

B-4.2) Wire Size:

 

If additional cable is required consult a qualified electrician 

for proper wire size. Voltage drop due to wire resistance 

between the pump and power connection point should be 

limited to 3% when additional cable is added.

WARRANTY NOTE: 

Both the temperature sensor and moisture 

detection system must be connected to the 

motor circuitry such that the motor will be de-

energized or sound alarm if excessive motor 

temperatures are reached and/or if water is 

detected in the seal chamber and/or motor 

chamber. Failure to have the above mentioned 

systems installed and operative, nullifies 

warranty.

FIGURE 2b

FIGURE 2a

Содержание 4SHV

Страница 1: ...20 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 125508 50 Rev P 4SHV Vo...

Страница 2: ...BLE SHOOTING 16 SH CROSS SECTIONS Fig 9 10 EXPLODED VIEWS Fig 11 17 18 PARTS LISTS 19 22 WARRANTY 25 WARRANTY REGISTRATION 26 RETURNED GOODS POLICY 26 START UP REPORT 27 28 Other brand and product nam...

Страница 3: ...sert fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety d...

Страница 4: ...h a dirt bottom the legs will sink into the dirt and the suction will become plugged B 1 1 Submergence It is recommended that the pump be operated in the Continuous Duty Submergence condition and the...

Страница 5: ...ews into the clamping plate Slowly tighten the two screws alternating back and forth until the clamping plate is drawn down flush to the top of the cord boss on the pump The two screws should be torqu...

Страница 6: ...Pump rated for operation at 10 voltage at motor Cord Suffix XF 50 Feet XJ 75 Feet or XL 100 Feet MODEL NO PART NO KW VOLT PH Hz RPM Nom NEMA START CODE FULL LOAD AMPS 1 2 SERVICE FACTOR AMPS LOCKED RO...

Страница 7: ...D 28 5 33 5 91 7 21 125499 8 4 18 4 SOLD SEPARATELY 4SHDI150Z4 130982 50 15 0 400 3 50 1450 G 33 5 38 9 170 4 21 125499 8 4 18 4 SOLD SEPARATELY 4SHDI185Z4 130597 50 18 5 400 3 50 1450 E 40 4 48 5 170...

Страница 8: ...om NEMA START CODE FULL LOAD AMPS 1 2 SERVICE FACTOR AMPS LOCKED ROTOR AMPS DRIVER FRAME CORD P N CORD SIZE CORD NOTES SHMN Pump 6SHMN55Z4 133128 50 5 5 400 3 50 1450 K 20 0 21 0 91 7 21 125497 12 4 1...

Страница 9: ...RATELY 6SHDK300Z4 132231 50 30 0 400 3 50 1450 D 58 0 72 0 233 9 28 130907 6 4 18 4 INCLUDED WITH PUMP 6SHDK370Z4 132233 50 37 0 400 3 50 1450 E 77 1 92 1 338 0 28 130908 2 4 18 4 INCLUDED WITH PUMP 6...

Страница 10: ...ether T6 T9 Together MOISTURE AND TEMPERATURE SENSORS MOISTURE AND TEMPERATURE SENSORS Control Cable Control Cable Lead ID Lead ID Green Ground Green Brown P1 Temperature Sensor Yellow P2 Temperature...

Страница 11: ...peres 110 120 3 00 30 0 220 240 1 50 15 0 440 480 0 75 7 5 B 4 4 Moisture Sensors A normally open N O detector is installed in the pump seal chamber which will detect any moisture present and a contin...

Страница 12: ...e Sensor Control With a moisture detection control a normally closed push button and neon indicating lamp is typically provided as a means of checking the moisture sensing components When the push but...

Страница 13: ...eakdown refill the seal chamber as per section F 1 2 4 If oil is found to be dirty or contaminated or measures below 15 KV breakdown the pump must be carefully inspected for leaks at the shaft seal 4...

Страница 14: ...cing seal remove stationary 4A from mounting plate by prying out with flat screw driver E 3 2 Reassembly Lightly oil DO NOT use grease outer surface of stationary member 4A Press stationary member 4A...

Страница 15: ...3 MODEL NUMBER This designation consists of numbers and letters which represent the discharge size series horsepower motor phase and voltage speed and pump design This number is used for ordering and...

Страница 16: ...ller for freedom of operation security and condition Clean impeller and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so t...

Страница 17: ...17 FIGURE 9 SH Pump Series Cross Sections FIGURE 10 SH Vortex SH Enclosed...

Страница 18: ...18 FIGURE 11 SH Pump Series Exploded Views APPLY GREEN LOCTITE RC603 TORQUE TO 45 1 4FT LBS APPLY GREEN LOCTITE RC603 TORQUE TO 45 1 4FT LBS...

Страница 19: ...ze 11 125453 Volute Vortex Cast Iron 129994 Volute Enclosed Cast Iron 129995 Volute Enclosed Cast Iron 127254 Volute Enclosed Cast Iron 130830 Volute Enclosed Cast Iron 130831 Volute Enclosed Cast Iro...

Страница 20: ...29863 Ring Snap Tru Arc 5100 175 PH 15 7 Mo Stainless Steel 41 1 127270 Plug Cap 3 37 Tapered PE 42 2 125856 Sensor Moisture 18NPT AMP PP SS 43 1 125450A Bracket Bearing 21 Frame Class 30 CI 44 1 1306...

Страница 21: ...n 127262TM 235mm 9 25in 127262TN 230mm 9 06in 127262TP 225mm 8 86in A Hydraulics Impeller Part No Trim Dia mm in 125454B 205mm 8 07in 125454BTA 200mm 7 87in 125454 205mm 8 07in 125454TA 200mm 7 87in 1...

Страница 22: ...A 365mm 14 37in 130827TB 360mm 14 17in 130827TC 355mm 13 98in 130827TD 350mm 13 78in 130827TE 345mm 13 58in 130827TF 340mm 13 45in 130827TH 330mm 12 99in 130827TJ 325mm 12 80in 130827TK 320mm 12 60in...

Страница 23: ...Notes...

Страница 24: ...Notes...

Страница 25: ...RETURNED GOODS AUTHORIZATION CONTACT YOUR LOCAL CRANE PUMPS SYSTEMS INC DISTRIBUTOR Products Returned Must Be Cleaned Sanitized Or Decontaminated As Necessary Prior To Shipment To Insure That Employe...

Отзывы: