Barnes 4SHV Скачать руководство пользователя страница 11

11

B-4.3) Overload Protection:

 

Current sensing overloads must be provided in the pump 

control panel and should be properly sized for the full load 

current of the pump. Three normally closed (N/C) thermal 

sensors wired in series (one per phase) are embedded in 

the motor windings and will detect excessive heat in the 

event an overload condition occurs which will then trip and 

stop the pump when wired in series with the pump contactor 

control circuit. The thermal sensor leads marked P1 and 

P2 MUST be connected in series with the stop button of 

the pilot circuit of the magnetic motor controller located in 

the control panel so that the thermostat will open the circuit 

before dangerous temperatures are reached. A manual 

momentary start switch is required to prevent the automatic 

restarting of the motor when the thermostat resets. For a 

typical wiring diagram, refer to Figure 4.  

 

In the event of an over temperature condition, the source 

of this condition should be determined and rectified before 

the pump is put back into normal operation. 

DO NOT LET 

THE PUMP CYCLE OR RUN IF AN OVER TEMPERATURE 

CONDITION OCCURS! 

 

If current through the temperature sensor exceeds the values 

listed, an intermediate control circuit relay must be used to 

reduce the current or the sensor will not work properly.

TEMPERATURE SENSOR ELECTRICAL RATINGS

Volts

Continuous 

Amperes

Inrush 

Amperes

110-120

3.00

30.0

220-240

1.50

15.0

440-480

0.75

7.5

B-4.4) Moisture Sensors:

 

A normally open (N/O) detector is installed in the pump seal 

chamber, which will detect any moisture present, and a 

continuity test resistor built into the motor. The test resistor 

is rated 1 watt at 330K ohms. The moisture sensors 

MUST

 

be connected to moisture detector control in the control 

panel which includes a continuity test circuit, see Figure 

4 for typical wiring diagram. The normally closed (N/C) 

contact of the moisture detector 

MUST

 be connected in 

series with the stop button of the pilot circuit of the magnetic 

motor controller. Wiring must be provided from the moisture 

detector sensor probe leads of the motor designated W1 

and W2 to terminals 9 and 10 of the 2800-XXX control. 

Terminal pair 1-2 must be continuously energized from an 

A-C supply line of electrical characteristics shown on the 

data table. In the event of moisture detection, the pump 

should be pulled and the source of the failure located and 

repaired. 

IF MOISTURE DETECTION HAS OCCURRED, 

SCHEDULE MAINTENANCE AS SOON AS POSSIBLE !

B-4.5) Control Panel and Electrical System:

 

The control panel and the electrical system 

MUST

 be 

properly designed and wired to include at least, but not 

limited to the following;

 

a. Proper grounding per NEC. 

 

b. A temperature sensing circuit (See Fig. 4) 

 

c. A moisture detection circuit with continuity test

 

    circuit  (See Fig. 5) 

 

d. A level control system. 

 

e. A main power manual disconnect and lock out. 

 

f.  A motor starter and overload system.

TYPICAL THERMAL PROTECTION

WIRING DIAGRAM

FIGURE 4

Содержание 4SHV

Страница 1: ...20 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 125508 50 Rev P 4SHV Vo...

Страница 2: ...BLE SHOOTING 16 SH CROSS SECTIONS Fig 9 10 EXPLODED VIEWS Fig 11 17 18 PARTS LISTS 19 22 WARRANTY 25 WARRANTY REGISTRATION 26 RETURNED GOODS POLICY 26 START UP REPORT 27 28 Other brand and product nam...

Страница 3: ...sert fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety d...

Страница 4: ...h a dirt bottom the legs will sink into the dirt and the suction will become plugged B 1 1 Submergence It is recommended that the pump be operated in the Continuous Duty Submergence condition and the...

Страница 5: ...ews into the clamping plate Slowly tighten the two screws alternating back and forth until the clamping plate is drawn down flush to the top of the cord boss on the pump The two screws should be torqu...

Страница 6: ...Pump rated for operation at 10 voltage at motor Cord Suffix XF 50 Feet XJ 75 Feet or XL 100 Feet MODEL NO PART NO KW VOLT PH Hz RPM Nom NEMA START CODE FULL LOAD AMPS 1 2 SERVICE FACTOR AMPS LOCKED RO...

Страница 7: ...D 28 5 33 5 91 7 21 125499 8 4 18 4 SOLD SEPARATELY 4SHDI150Z4 130982 50 15 0 400 3 50 1450 G 33 5 38 9 170 4 21 125499 8 4 18 4 SOLD SEPARATELY 4SHDI185Z4 130597 50 18 5 400 3 50 1450 E 40 4 48 5 170...

Страница 8: ...om NEMA START CODE FULL LOAD AMPS 1 2 SERVICE FACTOR AMPS LOCKED ROTOR AMPS DRIVER FRAME CORD P N CORD SIZE CORD NOTES SHMN Pump 6SHMN55Z4 133128 50 5 5 400 3 50 1450 K 20 0 21 0 91 7 21 125497 12 4 1...

Страница 9: ...RATELY 6SHDK300Z4 132231 50 30 0 400 3 50 1450 D 58 0 72 0 233 9 28 130907 6 4 18 4 INCLUDED WITH PUMP 6SHDK370Z4 132233 50 37 0 400 3 50 1450 E 77 1 92 1 338 0 28 130908 2 4 18 4 INCLUDED WITH PUMP 6...

Страница 10: ...ether T6 T9 Together MOISTURE AND TEMPERATURE SENSORS MOISTURE AND TEMPERATURE SENSORS Control Cable Control Cable Lead ID Lead ID Green Ground Green Brown P1 Temperature Sensor Yellow P2 Temperature...

Страница 11: ...peres 110 120 3 00 30 0 220 240 1 50 15 0 440 480 0 75 7 5 B 4 4 Moisture Sensors A normally open N O detector is installed in the pump seal chamber which will detect any moisture present and a contin...

Страница 12: ...e Sensor Control With a moisture detection control a normally closed push button and neon indicating lamp is typically provided as a means of checking the moisture sensing components When the push but...

Страница 13: ...eakdown refill the seal chamber as per section F 1 2 4 If oil is found to be dirty or contaminated or measures below 15 KV breakdown the pump must be carefully inspected for leaks at the shaft seal 4...

Страница 14: ...cing seal remove stationary 4A from mounting plate by prying out with flat screw driver E 3 2 Reassembly Lightly oil DO NOT use grease outer surface of stationary member 4A Press stationary member 4A...

Страница 15: ...3 MODEL NUMBER This designation consists of numbers and letters which represent the discharge size series horsepower motor phase and voltage speed and pump design This number is used for ordering and...

Страница 16: ...ller for freedom of operation security and condition Clean impeller and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so t...

Страница 17: ...17 FIGURE 9 SH Pump Series Cross Sections FIGURE 10 SH Vortex SH Enclosed...

Страница 18: ...18 FIGURE 11 SH Pump Series Exploded Views APPLY GREEN LOCTITE RC603 TORQUE TO 45 1 4FT LBS APPLY GREEN LOCTITE RC603 TORQUE TO 45 1 4FT LBS...

Страница 19: ...ze 11 125453 Volute Vortex Cast Iron 129994 Volute Enclosed Cast Iron 129995 Volute Enclosed Cast Iron 127254 Volute Enclosed Cast Iron 130830 Volute Enclosed Cast Iron 130831 Volute Enclosed Cast Iro...

Страница 20: ...29863 Ring Snap Tru Arc 5100 175 PH 15 7 Mo Stainless Steel 41 1 127270 Plug Cap 3 37 Tapered PE 42 2 125856 Sensor Moisture 18NPT AMP PP SS 43 1 125450A Bracket Bearing 21 Frame Class 30 CI 44 1 1306...

Страница 21: ...n 127262TM 235mm 9 25in 127262TN 230mm 9 06in 127262TP 225mm 8 86in A Hydraulics Impeller Part No Trim Dia mm in 125454B 205mm 8 07in 125454BTA 200mm 7 87in 125454 205mm 8 07in 125454TA 200mm 7 87in 1...

Страница 22: ...A 365mm 14 37in 130827TB 360mm 14 17in 130827TC 355mm 13 98in 130827TD 350mm 13 78in 130827TE 345mm 13 58in 130827TF 340mm 13 45in 130827TH 330mm 12 99in 130827TJ 325mm 12 80in 130827TK 320mm 12 60in...

Страница 23: ...Notes...

Страница 24: ...Notes...

Страница 25: ...RETURNED GOODS AUTHORIZATION CONTACT YOUR LOCAL CRANE PUMPS SYSTEMS INC DISTRIBUTOR Products Returned Must Be Cleaned Sanitized Or Decontaminated As Necessary Prior To Shipment To Insure That Employe...

Отзывы: