C-4) Electrical Connections:

C-4.1) Power Cable:

The cord assembly mounted to the pump must not be modified 

in any way except for shortening to a specific application. 

Any splice between the pump and the control panel must be 

made in accordance with all applicable electric codes. It is 

recommended that a junction box, if used, be mounted outside 

the sump or be of at least NEMA 4 (EEMAC-4) construction if 

located within the wet well. Do not use the power cable to lift 

pump. 

NOTE: THE WHITE WIRE IS NOT A NEUTRAL OR 

GROUND LEAD, BUT A POWER CARRYING CONDUCTOR.

C-4.2)  Control Cable:

The cord assembly mounted to the pump must not be modified 

in any way except for shortening to a specific application. 

Any splice between the pump and the control panel must be 

made in accordance with all applicable electric codes. It is 

recommended that a junction box, if used, be mounted outside 

the sump or be of at least NEMA 4 (EEMAC-4) construction if 

located within the wet well. Do not use the control cable to lift 

pump. 

NOTE: THE WHITE WIRE IS NOT A NEUTRAL OR 

GROUND LEAD, BUT A POWER CARRYING CONDUCTOR.

C-4.3) Overload Protection:

C-4.3-1) Three Phase (Optional)

 - The normally closed 

(N/C) thermal sensor is embedded in the motor windings and 

will detect excessive heat in the event an overload condition 

occurs. The thermal sensor will trip when the windings become 

too hot and will automatically reset itself when the pump 

motor cools to a safe temperature. It is recommended that the 

thermal sensor be connected in series to an alarm device to 

alert the operator of an overload condition, and/or the motor 

starter coil to stop the pump. In the event of an overload, the 

source of this condition should be determined and rectified 

immediately. 

DO NOT LET THE PUMP CYCLE OR RUN IF 

AN OVERLOAD CONDITION OCCURS !

C-4.3-2) Single Phase

 - The type of in-winding overload 

protector used is referred to as an inherent overheating 

protector and operates on the combined effect of temperature 

and current. This means that the overload protector will trip out 

and shut the pump off if the windings become too hot, or the 

load current passing through them becomes too high. It will 

then automatically reset and start the pump up after the motor 

cools to a safe temperature. In the event of an overload, the 

source of this condition should be determined and rectified 

immediately. 

DO NOT LET THE PUMP CYCLE OR RUN IF 

AN OVERLOAD CONDITION OCCURS !

If current through the temperature sensor exceeds the values 

listed, an intermediate control circuit relay must be used to 

reduce the current or the sensor will not work properly.

TEMPERATURE SENSOR ELECTRICAL RATINGS

Volts

Continuous 

Amperes

Inrush 

Amperes

220-240

1.50

15.0

440-480

0.75

7.5

575-600

0.60

6.0

C-4.4) Wire Size:

Consult a qualified electrician for proper wire size if additional 

power cable length is required. See table for electrical 

information.

SECTION: D START-UP OPERATION

D-1) Check Voltage and Phase:

Before operating pump, compare the voltage and phase 

information stamped on the pump identification plate to the 

available power.

D-2) Check Pump Rotation:

Before putting pump into service for the first time, the motor 

rotation must be checked. Improper motor rotation can result 

in poor pump performance and can damage the motor and/

or pump. To check the rotation, suspend the pump freely, 

momentarily apply power and observe the “kickback”. 

“Kickback” should always be in a counter-clockwise direction 

as viewed from the top of the pump motor housing.

D-2.1) Incorrect Rotation for Three-Phase Pumps:

In the event that the rotation is incorrect for a three-phase 

installation, interchange any two power cable leads at the 

control box. DO NOT change leads in the cable housing in the 

motor. Recheck the “kickback” rotation again by momentarily 

applying power.

D-2.2) Incorrect Rotation for Single-Phase Pumps:

In the unlikely event that the rotation is incorrect for a single 

phase pump, contact a Barnes Service Center.

D-3) Identification Plate:

Record the numbers from the pump identification plate for 

future reference.

D-3.1) Insulation Test:

Before the pump is put into service, an insulation (megger) 

test should be performed on the motor. The resistance values 

(ohms) as well as the voltage (volts) and current (amps) should 

be recorded.

D-3.2) Pump-Down Test:

After the pump has been properly wired and lowered into the 

basin, sump or lift station, it is advisable to check the system 

by filling with liquid and allowing the pump to operate through 

its pumping cycle. The time needed to empty the system, or 

pump-down time along with the volume of water, should be 

recorded.

SECTION E: PREVENTATIVE MAINTENANCE

As the motor is oil filled, no lubrication or other maintenance 

is required, and generally Barnes Pumps will give very 

reliable service and can be expected to operate for years on 

normal sewage pumping without failing. However as with any 

mechanical piece of equipment a preventive maintenance 

program is recommended and suggested to include the 

following checks:

WARNING ! - Pressure builds up due to heat.

Содержание 3SEH-L

Страница 1: ...ram product changes may occur As such Crane Pumps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Brampton Piqua Ohio 45356 Ontario Canad...

Страница 2: ...re 11a 11b 15 16 EXPLODED VIEW Figure 12 17 PARTS LIST 18 19 WARRANTY 21 WARRANTY REGISTRATION 22 RETURNED GOODS POLICY 22 SPECIAL TOOLS AND EQUIPMENT INSULATION TESTER MEGGER DIELECTRIC TESTER SEAL T...

Страница 3: ...rt fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety dev...

Страница 4: ...200 230 460 60Hz is Tri voltage motor 575V Requires overload protection to be included in control panel OPTIONAL EQUIPMENT Seal Material Impeller Trims Additional Cord Normally Closed Temperature Sen...

Страница 5: ...t station or basin shall be vented in accordance with local plumbing codes This pump is designed to pump sewage effluent or other nonexplosive or noncorrosive wastewater and shall NOT be installed in...

Страница 6: ...If current through the temperature sensor exceeds the values listed an intermediate control circuit relay must be used to reduce the current or the sensor will not work properly TEMPERATURE SENSOR EL...

Страница 7: ...10 08 12 36 3SE2052L 2 0 575 3 60 3450 C B 4 0 14 4 14 4 SOOW SOW 57 14 5 15 75 14 95 HORIZONTAL Series 3SEH1522L 1 5 230 1 60 3450 A F 12 0 31 0 12 3 SOOW SOW 61 15 5 1 14 4 53 3SEH1592L 1 5 200 230...

Страница 8: ...essure is still holding constant and no bubbles are observed slowly bleed the pressure and remove the gauge assembly Replace oil as described in section F 1 4 If the pressure does not hold then the le...

Страница 9: ...ny control cables 32 if equipped Remove socket head cap screws 9 Vertically lift the motor housing 5 from seal plate 1 by lifting handle 17 Inspect square ring 8 for damage or cuts Remove the motor bo...

Страница 10: ...aragraph F 3 3 Insert female end of cable plug into housing bore aligning timing mark with hole in terminal block 23 38 optional see Figure 6 Compress cable plug with compression flange 30a 32a by tig...

Страница 11: ...e 9 It is extremely important to keep seal faces clean during assembly Dirt particles lodged between these faces will cause the seal to leak Place spring 31c over shaft and in place on rotating member...

Страница 12: ...esign configuration This number is used for ordering and obtaining information G 3 MODEL NUMBER This designation consists of numbers and letters which represent the discharge size series horsepower mo...

Страница 13: ...13 FIGURE 10...

Страница 14: ...eller for freedom of operation security and condition Clean impeller and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so...

Страница 15: ...15 34 30 5 22 1 6 3 8 24A 10 2 7 32 21 20 OPTIONAL TEMPERATURE SENSOR CABLE ASSEMBLY 29 FIGURE 11a CROSS SECTION VERTICAL DISCHARGE...

Страница 16: ...16 34 30 5 22 1 6 3 8 24B 10 2 7 32 21 20 OPTIONAL TEMPERATURE SENSOR CABLE ASSEMBLY 29 FIGURE 11b CROSS SECTION HORIZONTAL DISCHARGE...

Страница 17: ...17 2 6 8 1 9 9 31 29 10 3 24A 20 25 34 22 21 7 5 11 12 19 41 23 40 30 11 16 38 40 41 32 11 16 a b c d 7 35 WITH OPTIONAL TEMP SENSOR CABLE ASSY 24B FIGURE 12 EXPLODED VIEW...

Страница 18: ...es 230V 3 Phase 19 1 014270 Pipe Plug 375 NPT 20 1 084386MA 3SE1522L 2022L 067572MB 3SE1592L 1542L 092858 3SE1552L 2052L 067572MB 3SE2092L 2042L 21 1 036391 Capacitor 1 phase 370V 45MFD 22 1 039858 Ca...

Страница 19: ...TEMP SENSOR 100 FT TEMP SENSOR TERMINAL BLOCK TEMP SENSOR 3SE1522L None None None None 3SE1592L 103741XC 103741XF 103741XL 103584 3SE1542L 113288XC 113288XF 113288XL 113272 3SE1552L 113288XC 113288XF...

Страница 20: ...20 Notes...

Страница 21: ...ION Your product is covered by a warranty www cranepumps com downloadables CATALOGS_OIPMs Warranty 24MonthWarranty pdf If you have a claim under the provisions of the warranty contact your local Crane...

Отзывы: