7. INITIAL COMMISSIONING
Preheating:
No
Electric
Water
Reheating:
No
Electric
Water
Change over
Direct vaporizer
MENU 08 - AQS SENSOR
S
elect air quality
sensor
Switching be-
tween air quality
sensors
MENU 09 - TEMPERATURE SENSOR
Select the main
temperature sensor
Supply duct:
Supply air
temperature sensor
Extract duct:
Extract
air temperature sensor
Room:
Temperature sensor installed in the room (optional)
MENU 10 - SUPPLY DUCT LIMITS
Maximum
temperature in
the
duct
Maximum tem-
perature in the
duct
Enable/disable reduc-
tion of ventilation rate
when the minimum
temperature drops in
the inlet
duct
(enabled by default =
when the temperature
drops below the min-
imum set, the ventila-
tion rate is reduced)
We recommend enabling flow reduction if the minimum set
temperature isn’t reached due to the possible condensation of
water on the surface of the ventilation system.
If “supply duct”
temperature sensor
is set,
max.
temperature will not be controllable
Probe DCV
DCV limit
Without
Temperature probe
Blowing
Suction
Blowing limits
for setpoint