PRODUCT MANUAL - BARIX R6 - V01.03 - 07/20/2005
Detailed “register” map – again – please note that the protocol
address in Modbus/RTU is the register number -1 !!
Register
Function
1
Live I/O (Byte, Relay state in bit 0..5)
2..256
Reserved, not accessible
257
Device type (hex 0xB1)
258
Firmware version
259
Serial number 1
st
part
260
Serial number 2
nd
part
261..264
reserved
265..272
One-time writable for installer
273
Default relay setting for startup
274
Serial interface mode
275
Modbus address
276..289
reserved
290..512
Memory for installer/software use
513....
65536
not accessible
Detailed “coils” map – please note that in the protocol, address in
Mobus/RTU is the coil number -1 !!
Coil
Function
1..6
Relay 1..6
7..65536
Reserved, do not access
Modbus Register Map • 14
Complete
Register Map
Complete Coils
Map