background image

Manual 2100-466
Page

6

WALL MOUNTING INFORMATION

1. Two holes, for the supply and return air openings,

must be cut through the wall as shown in Figure 3.

2. On wood-frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.

        

WARNING

Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is
not maintained.  See Figure 3.

3. Concrete block walls must be thoroughly inspected to

insure that they are capable of carrying the weight of
the installing unit.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. The unit itself is suitable for “0” inch clearance, but

the supply air duct flange and the first 3 feet of supply
air duct require a minimum of 1/4 inch clearance to
combustible material.  If a combustible wall, use a
minimum of 28½" x 8½" dimensions for sizing.
However, it is generally recommended that a 1-inch
clearance is used for ease of installation and
maintaining the required clearance to combustible
material.  The supply air opening would then be 30" x
10".  See Figures 3 and 7 for details.

     

    WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet can result in fire.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.  See Figure 3.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped secured to the right side of the
back.

6. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 3.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

9. On side by side installations, maintain a minimum of

20 inches clearance on left side to allow access to
heat strips and control panel and to allow proper
airflow to the outdoor coil.  Additional clearance may
be required to meet local or national codes.

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker size.
Each outdoor unit is marked with a “Minimum Circuit
Ampacity”.  This means that the field wiring used must
be sized to carry that amount of current.  Depending on
the installed KW of electric heat, there may be two field
power circuits required.  If this is the case, the unit serial
plate will so indicate.  All models are suitable only for
connection with copper wire.  Each unit and/or wiring
diagram will be marked “Use Copper Conductors Only”.
These instructions 

must be

 adhered to.  Refer to the

National Electrical Code (NEC) for complete current
carrying capacity data on the various insulation grades
of wiring material.  All wiring must conform to NEC
and all local codes.

The electrical data lists fuse and wire sizes (75ºC
copper) for all models, including the most commonly
used heater sizes.  Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit may be locked to
prevent unauthorized access to the disconnect.  To
convert for the locking capability, bend the tab located
in the bottom left hand corner of the disconnect opening
under the disconnect access panel straight out.  This tab
will now line up with the slot in the door.  When shut, a
padlock may be placed through the hole in the tab
preventing entry.

Содержание YL302

Страница 1: ...Copyright 2005 Manual No 2100 466 Supersedes Date 07 18 05 Model YL302 YL372 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS MIS 861...

Страница 2: ...15 Table 11 Maximum ESP of Operation Electric Heat Only 15 Table 12 Cooling Pressure 16 Table 13 Optional Accessories 16 Getting Other Information and Publications For more information contact these...

Страница 3: ...Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington D...

Страница 4: ...N A N A N 0 6 A N A N A N 0 3 A N A N A N 4 A N A N A N 0 1 A N A N A N 8 A N A N A N 0 1 Z 0 B 2 0 3 L Y 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1 7 1 2 3 0 5 0 2 5 3 0 5 2 1 8 8 2 1 0 1 0 1 A N A N A N A N A...

Страница 5: ...d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 0 3 L Y 2 7 3 L Y 0 2 8 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 0 4 0 5 8 1 5 7 5 2 3...

Страница 6: ...onal Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning Syst...

Страница 7: ...gures 3 and 7 for further details Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Any grille that meets the 5 8 inch louver...

Страница 8: ...drilled and screwed or welded to the structural wall itself depending upon wall construction Be sure to observe required clearance if combustible wall 9 On side by side installations maintain a minim...

Страница 9: ...c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u a g 8 1 e g u a g 6 1 e g u a g 4 1 e g u a g 2 1 5 4 0 6 0 0 1 0 6 1 0 5 2 TABLE 5 THERMOSTAT WIRE SIZE TABLE 6 WALL THERMOSTAT AND SUBBASE COMBI...

Страница 10: ...ting flanges and under the top flashing at the time of installation MIS 859 TOP SEAL WITH BEAD OF CHALKING ALONG ENTIRE LENGTH OF TOP RAIN FLASHING SUPPLIED FOAM AIR SEAL SUPPLY AIR DUCT 1 4 CLEARANCE...

Страница 11: ...100 466 Page 9 MIS 948 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS MIS 1051 SEE FIGURE 3 MOUNTING INSTRUCTIONS FOR OPENIN...

Страница 12: ...Manual 2100 466 Page 10 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 1050...

Страница 13: ...rfaces MIS 277 WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insu...

Страница 14: ...Manual 2100 466 Page 12 FIGURE 8 LOW VOLTAGE WIRING...

Страница 15: ...urrent draw compared to tabulated values The direction of rotation of the compressor may be changed by reversing any two line connections to the unit START UP PHASE MONITOR All units with three phase...

Страница 16: ...ROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring and a...

Страница 17: ...compressor as shown in the following table A AIRFLOW TABLE 8 SUCTION LINE TEMPERATURES s l e d o M d e t a R w o l f r i A F 5 9 p m e T D O F 2 8 p m e T D O 2 0 3 L Y 0 0 0 1 9 5 6 5 6 6 4 6 2 7 3...

Страница 18: ...D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 8 2 2 4 8 3 4 2 6 8 9 5 2 8 8 4 7 2 9 8 2 9 2 0 9 9 0 3 2 9 7 2 3 3 9 7 4 3 4 9 6 6 3 2 7 3 L Y B D g e d 5 7 B W g e d 2 6 e d i S w o L e...

Отзывы: