FILTERS

A 1-inch throw away filter is suppled with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the service door.  A 1-inch washable filter and a 2-inch
pleated filter are also available as optional accessories.
The internal filter brackets are adjustable to
accommodate the 2-inch filter by bending the metal tabs
holding the 1-inch filter down.  There are two tabs on
each side of the filter.

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in
the service panel.

If the unit is equipped with the fresh air damper
assembly, the assembly is shipped already attached to
the unit.  The damper blade is locked in the closed
position.  To allow the damper to operate, the maximum
and minimum blade position stops must be installed.
See Figure 2.

All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets is based upon the fresh air
blank-off plate in place and is recommended for
maximum energy efficiency.

The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base.  There are
openings in the unit base for the drain hose to pass
through.  In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.

DUCT WORK

All duct work, supply and return, must be properly sized
for the design air flow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.  All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.

Refer to Table 11 for maximum static pressure available
for duct design.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of 1-inch of insulation.  Use
insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.
A 1/4 inch clearance to combustible material for the first
3 feet of duct attached to the outlet air frame is required.
See Wall Mounting Instructions and Figures 3 and 4 for
further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Any grille that meets the 5/8 inch louver criteria may be
used.  It is recommended that Bard Return Air Grille Kit
RG-2 through RG-5 or RFG-2 through RFG-5 be
installed when no return duct is used.  Contact
distributor or factory for ordering information.  If using
a return air filter grille, filters must be of sufficient size
to allow a maximum velocity of 400 fpm.

        CAUTION

Some installations may not require any return
air duct.  A metallic return air grille is required
with installations not requiring a return air
duct.  The spacing between louvers on the
grille shall not be larger than 5/8 inches.

FIGURE 2

FRESH AIR DAMPER ASSEMBLY

MIS-938

Содержание YA302

Страница 1: ... Copyright 2005 Manual No 2100 461 Supersedes Date 06 20 05 INSTALLATION INSTRUCTIONS Models YA302 YA372 WALL MOUNTED PACKAGED AIR CONDITIONER MIS 383 ...

Страница 2: ...Voltage Wiring 12 Figure 9 Fan Blade Setting 15 Tables Table 1 Electrical Specifications 2 Table 2 Dimensions of Basic Unit 3 Table 3 Electric Heat Table 4 Table 4 Operating Voltage Range 7 Table 5 Thermostat Wire Size 7 Table 6 Wall Thermostat and Subbase Combinations 7 Table 7 Fan Blade Dimensions 15 Table 8 Suction Line Temperatures 15 Table 9 Indoor Blower Performance 15 Table 10 CFM and ESP 1...

Страница 3: ... Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone 212 642 4900 Fax 212 302 1286 ASHRAE American Society ...

Страница 4: ... y t i c a p m A 1 m u m i x a M l a n r e t x E r o e s u F t k C r e k a e r B 2 d l e i F r e w o P e r i W e z i S 2 d n u o r G e r i W e z i S 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E e s u F t k C r o r e k a e r B 2 r e w o P d l e i F e z i S e r i W 2 d n u o r G e z i S e r i W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A 2 0...

Страница 5: ...W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 0 3 A Y 2 7 3 A Y 0 2 8 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 0 4 0 5 8 1 5 7 5 2 3 9 7 1 5 7 6 2 5 7 8 2 5 2 9 2 0 0 7 2 5 7 2 9 1 9 3 5 7 2 2 4 1 9 9 1 4 0 0 2 1 0 0 5 FRONT VIEW BACK VIEW SIDE VIEW ...

Страница 6: ...mmended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 1 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installe...

Страница 7: ...y and return must be properly sized for the design air flow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 11 for maximum static pressure available fo...

Страница 8: ...igure 6 WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or HACR Type circuit breaker size Each outdoor unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current Depending on the installed KW of electric heat there may be two field power circuits required If this is the case the un...

Страница 9: ...d 7 c i n o r t c e l E 3 4 0 3 0 4 8 0 0 2 M C l o o c e g a t s 1 t a e h e g a t s 1 n o o t u a n a F l o o c f f o t a e h m e t s y S WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable operating voltage range for the 240 and 208V...

Страница 10: ...nual 2100 461 Page 8 FIGURE 3 MOUNTINGINSTRUCTIONS NOTE It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation ...

Страница 11: ...61 Page 9 FIGURE 4 WALL MOUNTINGINSTRUCTIONS FIGURE 5 WALL MOUNTINGINSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT DIMENSIONS MIS 549 ...

Страница 12: ...Manual 2100 461 Page 10 MIS 550 FIGURE 6 COMMONWALL MOUNTINGINSTALLATIONS ...

Страница 13: ...NCE MIS 277 WARNING WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in fire ...

Страница 14: ...Manual 2100 461 Page 12 FIGURE 8 LOW VOLTAGE WIRING ...

Страница 15: ...essure drops and discharge pressure rises when the compressor is energized Reverse rotation also results in an elevated sound level over that with correct rotations as well as substantially reduced current draw compared to tabulated values START UP PHASE MONITOR All units with three phase compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal The ph...

Страница 16: ...TROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring and alarm relay output Adjustable Delay On Make And Break Timer On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes plus 10 of the dela...

Страница 17: ... o C y r D l i o C t e W l i o C y r D l i o C t e W 0 5 9 3 1 5 1 3 1 0 5 9 5 3 9 1 0 4 3 1 0 7 2 1 0 3 9 5 1 9 2 5 8 2 1 0 9 1 1 0 1 9 5 8 8 3 5 0 2 1 0 0 1 1 5 5 8 0 3 8 4 0 1 1 1 0 0 0 1 0 0 8 5 5 7 5 5 0 0 1 0 7 8 TABLE 11 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY l e d o M t e l t u O t n o r F t e l t u O p o T d e e p S w o L d e e p S h g i H d e e p S w o L d e e p S h g i H d e e p S ...

Страница 18: ... 8 7 4 4 2 9 7 8 5 2 0 8 5 7 2 1 8 2 9 2 3 8 8 0 3 4 8 7 2 3 5 8 5 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 0 8 0 2 2 1 8 5 3 2 3 8 0 5 2 5 8 5 6 2 6 8 2 8 2 7 8 9 9 2 9 8 6 1 3 0 9 5 3 3 1 9 4 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 8 2 2 4 8 3 4 2 6 8 9 5 2 8 8 4 7 2 9 8 2 9 2 0 9 9 0 3 2 9 7 2 3 3 9 7 4 3 4 9 6 6 3 2 7 3 A Y B D g e d 5 7 B W g e d...

Страница 19: ... n o C t n e i b m A w o L X X X A 6 1 A M C l o r t n o C e r u s s e r P w o L X X X X A 8 1 A M C C P L C A L X X X 5 1 C M C t i K t r a t S X 5 0 A 3 0 A W H E e g a k c a P r e t a e H 1 X 8 0 A 3 0 A W H E e g a k c a P r e t a e H 1 X 0 1 A 3 0 A W H E e g a k c a P r e t a e H 1 X 5 1 A 3 0 A W H E e g a k c a P r e t a e H 1 X 6 0 B 3 0 A W H E e g a k c a P r e t a e H 1 X X 9 0 B 3 0 A...

Отзывы: