background image

Manual 2100-461
Page

14

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to HPC
or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions, the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure tables can be found later in the
manual covering all models.  It is imperative to match
the correct pressure table to the unit by model number.

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the
models covered by this manual.  The compressor control
is an anti-short cycle/lockout timer with high and low
pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit  the 

delay on make

 period begins which will be

2 minutes plus 10% of the 

delay on break

 setting.  When

the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.   If the high pressure switch
opens again in this same operating cycle the unit will go
into 

manual lockout

 condition and the alarm relay circuit

will energize.   Recycling the wall thermostat resets the
manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Содержание YA302

Страница 1: ... Copyright 2005 Manual No 2100 461 Supersedes Date 06 20 05 INSTALLATION INSTRUCTIONS Models YA302 YA372 WALL MOUNTED PACKAGED AIR CONDITIONER MIS 383 ...

Страница 2: ...Voltage Wiring 12 Figure 9 Fan Blade Setting 15 Tables Table 1 Electrical Specifications 2 Table 2 Dimensions of Basic Unit 3 Table 3 Electric Heat Table 4 Table 4 Operating Voltage Range 7 Table 5 Thermostat Wire Size 7 Table 6 Wall Thermostat and Subbase Combinations 7 Table 7 Fan Blade Dimensions 15 Table 8 Suction Line Temperatures 15 Table 9 Indoor Blower Performance 15 Table 10 CFM and ESP 1...

Страница 3: ... Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone 212 642 4900 Fax 212 302 1286 ASHRAE American Society ...

Страница 4: ... y t i c a p m A 1 m u m i x a M l a n r e t x E r o e s u F t k C r e k a e r B 2 d l e i F r e w o P e r i W e z i S 2 d n u o r G e r i W e z i S 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E e s u F t k C r o r e k a e r B 2 r e w o P d l e i F e z i S e r i W 2 d n u o r G e z i S e r i W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A 2 0...

Страница 5: ...W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 0 3 A Y 2 7 3 A Y 0 2 8 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 0 4 0 5 8 1 5 7 5 2 3 9 7 1 5 7 6 2 5 7 8 2 5 2 9 2 0 0 7 2 5 7 2 9 1 9 3 5 7 2 2 4 1 9 9 1 4 0 0 2 1 0 0 5 FRONT VIEW BACK VIEW SIDE VIEW ...

Страница 6: ...mmended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 1 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installe...

Страница 7: ...y and return must be properly sized for the design air flow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 11 for maximum static pressure available fo...

Страница 8: ...igure 6 WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or HACR Type circuit breaker size Each outdoor unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current Depending on the installed KW of electric heat there may be two field power circuits required If this is the case the un...

Страница 9: ...d 7 c i n o r t c e l E 3 4 0 3 0 4 8 0 0 2 M C l o o c e g a t s 1 t a e h e g a t s 1 n o o t u a n a F l o o c f f o t a e h m e t s y S WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable operating voltage range for the 240 and 208V...

Страница 10: ...nual 2100 461 Page 8 FIGURE 3 MOUNTINGINSTRUCTIONS NOTE It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation ...

Страница 11: ...61 Page 9 FIGURE 4 WALL MOUNTINGINSTRUCTIONS FIGURE 5 WALL MOUNTINGINSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT DIMENSIONS MIS 549 ...

Страница 12: ...Manual 2100 461 Page 10 MIS 550 FIGURE 6 COMMONWALL MOUNTINGINSTALLATIONS ...

Страница 13: ...NCE MIS 277 WARNING WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in fire ...

Страница 14: ...Manual 2100 461 Page 12 FIGURE 8 LOW VOLTAGE WIRING ...

Страница 15: ...essure drops and discharge pressure rises when the compressor is energized Reverse rotation also results in an elevated sound level over that with correct rotations as well as substantially reduced current draw compared to tabulated values START UP PHASE MONITOR All units with three phase compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal The ph...

Страница 16: ...TROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring and alarm relay output Adjustable Delay On Make And Break Timer On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes plus 10 of the dela...

Страница 17: ... o C y r D l i o C t e W l i o C y r D l i o C t e W 0 5 9 3 1 5 1 3 1 0 5 9 5 3 9 1 0 4 3 1 0 7 2 1 0 3 9 5 1 9 2 5 8 2 1 0 9 1 1 0 1 9 5 8 8 3 5 0 2 1 0 0 1 1 5 5 8 0 3 8 4 0 1 1 1 0 0 0 1 0 0 8 5 5 7 5 5 0 0 1 0 7 8 TABLE 11 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY l e d o M t e l t u O t n o r F t e l t u O p o T d e e p S w o L d e e p S h g i H d e e p S w o L d e e p S h g i H d e e p S ...

Страница 18: ... 8 7 4 4 2 9 7 8 5 2 0 8 5 7 2 1 8 2 9 2 3 8 8 0 3 4 8 7 2 3 5 8 5 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 0 8 0 2 2 1 8 5 3 2 3 8 0 5 2 5 8 5 6 2 6 8 2 8 2 7 8 9 9 2 9 8 6 1 3 0 9 5 3 3 1 9 4 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 8 2 2 4 8 3 4 2 6 8 9 5 2 8 8 4 7 2 9 8 2 9 2 0 9 9 0 3 2 9 7 2 3 3 9 7 4 3 4 9 6 6 3 2 7 3 A Y B D g e d 5 7 B W g e d...

Страница 19: ... n o C t n e i b m A w o L X X X A 6 1 A M C l o r t n o C e r u s s e r P w o L X X X X A 8 1 A M C C P L C A L X X X 5 1 C M C t i K t r a t S X 5 0 A 3 0 A W H E e g a k c a P r e t a e H 1 X 8 0 A 3 0 A W H E e g a k c a P r e t a e H 1 X 0 1 A 3 0 A W H E e g a k c a P r e t a e H 1 X 5 1 A 3 0 A W H E e g a k c a P r e t a e H 1 X 6 0 B 3 0 A W H E e g a k c a P r e t a e H 1 X X 9 0 B 3 0 A...

Отзывы: