INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1. Two holes for the supply and return air openings

must be cut through the wall as shown in Figure 1.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight
of the installed unit.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. The unit itself is suitable for 0 inch clearance, but

the supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1/4 inch
clearance to combustible material.  If a combustible
wall use a minimum of 30½" x 10½" dimensions for
sizing.  However, it is generally recommended that a
1-inch clearance is used for ease of installation and
maintaining the required clearance to combustible
material.  The supply air opening would then be
32" x 12".  See Figures 2 and 3 for details.

        WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing damage, injury or death.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.  See Figure 2.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped secured to the right side of
the back.

6. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 2.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

9. On side-by-side installations, maintain a minimum

of 20 inches clearance on left side to allow access to
control panel and heat strips, and to allow proper
airflow to the outdoor coil.  Additional clearance
may be required to meet local or national codes.

       WARNING

Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is not
maintained.  See Figure 2.

Содержание WL7013B

Страница 1: ...NTED PACKAGE AIR CONDITIONERS Model WL7013B WL7023A INSTALLATION INSTRUCTIONS Manual 2100 428A Supersedes 2100 428 File Volume III Tab 16 Date 07 25 06 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned ...

Страница 2: ...CFM and Rated ESP 17 Table 9 Maximum ESP of Operation Electric Heat Only 17 Table 10 Pressure Table 18 Getting Other Information and Publications 3 Wall Mount General Information Air Conditioning Wall Mount Model Nomenclature 4 Shipping Damage 6 General 6 Duct Work 6 7 Condensate Drain 7 Installation Instructions Wall Mounting Information 8 Mounting the Unit 8 Wiring Main Power 13 Wiring Low Volta...

Страница 3: ...nter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 T...

Страница 4: ...H U T B 0 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 70 6 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VENTILATION OPTIONS B Blank off Plate FILTER OPTIONS N No Filter COLOR OPTIONS X Beige Standard 1 White 2 Mesa Tan 4 Buckeye Gray COIL OPTIONS X Standard 1 Phenolic Coated Evaporator 2 Phenolic Coated Condenser 3 Phe...

Страница 5: ...Manual 2100 428A Page 5 of 18 FIGURE 1 UNIT DIMENSIONS ...

Страница 6: ...on to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway TABLE 2 ELECTRICALSPECIFICATIONS l e d o M T I U C R I C E L G N I S d e t a R s t l o V e s a h P o N d l e i F r e w o P s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E r o e s u F t k C r e k a e r B 2 d l e i F r e w o P e r i W e z i S 2 d ...

Страница 7: ... air duct A metallic return air grille is required with installations not requiring a return air duct The spacing between louvers on the grille shall not be larger than 5 8 inch NOTE If no return air duct is used applicable installation codes may limit this cabinet to installation only in a single story structure Any grille that meets with 5 8 inch louver criteria may be used It is recommended tha...

Страница 8: ...ply air opening would then be 32 x 12 See Figures 2 and 3 for details WARNING Failure to provide the 1 4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage injury or death 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 2 4 Mount bottom mounting bracket 5 Hook top rain flashing under b...

Страница 9: ...Manual 2100 428A Page 9 of 18 FIGURE 2 MOUNTING INSTRUCTIONS ...

Страница 10: ...s This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 INCH CLEARANCE TO COMBUSTIBLE SURFACES ...

Страница 11: ...Manual 2100 428A Page 11 of 18 SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS ...

Страница 12: ...Manual 2100 428A Page 12 of 18 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS ...

Страница 13: ...pening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on three phase scroll compressor start ups WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All equipment leaves the f...

Страница 14: ...Manual 2100 428A Page 14 of 18 FIGURE 7 UNIT 24V TERMINAL BOARD ...

Страница 15: ... or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two line connections to the unit SERVICE HINTS 1 Caution homeowner to maintain clean air filters at all times Also not to needlessly close off supply and return air registers This reduces airflow th...

Страница 16: ...ut features both soft and manual are a function of the Compressor Control Module ADJUSTMENTS Adjustable Delay on Make and Delay on Break Timer The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes Delay on Make DOM timing on power up and after power interruptions is equal to 2 minutes plus 10 of Delay on Break DOB setting 0 5 minute 30 seconds DOB 123 second DOM 1 0 ...

Страница 17: ...L W 5 2 1 TABLE 6 INDOOR BLOWER PERFORMANCE CFM 230V P S E H n I 2 O 0 7 L W d e e p S h g i H l i o C y r D l i o C t e W 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 TABLE 8 RATED CFM AND ESP l e d o M d e t a R M F C d e t a R P S E d e d n e m m o c e R e g n a R w o l f r i A 0 7 L W 5 2 4 1 0 2 0 5 2 4 1 5 7 7 1 1 TABLE 9 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY Values shown are ...

Страница 18: ...2 1 7 2 7 2 2 7 9 8 2 3 7 5 0 3 4 7 4 2 3 5 7 3 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 3 7 0 2 2 3 7 4 3 2 4 7 8 4 2 5 7 3 6 2 6 7 9 7 2 7 7 6 9 2 8 7 3 1 3 9 7 2 3 3 0 8 2 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 6 7 8 2 2 6 7 2 4 2 7 7 7 5 2 8 7 2 7 2 9 7 9 8 2 0 8 6 0 3 1 8 4 2 3 2 8 4 4 3 3 8 4 6 3 B 3 1 0 7 L W B D g e d 5 7 B W g e d 2 6 e d i S w ...

Отзывы: