background image

Manual 2100-347F
Page

6 of 24

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be
checked for external signs of shipping damage.  If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting  inspection by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment, required to make up the entire
air conditioning system should be carefully read before
beginning the installation.  Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.

3

Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
Based on 75° C copper wire.  All wiring must conform to NEC and all local codes.
These “minimum Circuit Ampacity” values are to be used for sizing the field power conductors.  Refer to
the National Electric Code (latest revision), article 310 for power conductor sizing.   

CAUTION:  When

more than one field power conductor circuit is run through one conduit, the conductors must be
derated.  Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when
more than 3 conductors are in a raceway.

1

2

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 3 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

Any heat pump is more critical of proper operating
charge and an adequate duct system than a straight air
conditioning unit.  All duct work, supply and return,
must be properly sized for the design air flow
requirement of the equipment.  Air Conditioning
Contractors of America (ACCA) is an excellent guide to
proper sizing.  All duct work or portions thereof not in
the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage.

TABLE  2

ELECTRICAL SPECIFICATIONS

T

I

U

C

R

I

C

E

L

G

N

I

S

T

I

U

C

R

I

C

L

A

U

D

l

e

d

o

M

d

e

t

a

R

&

s

t

l

o

V

e

s

a

h

P

.

o

N

d

l

e

i

F

r

e

w

o

P

s

t

i

u

r

i

C

3

m

u

m

i

n

i

M

t

i

u

c

r

i

C

y

t

i

c

a

p

m

A

1

m

u

m

i

x

a

M

l

a

n

r

e

t

x

E

r

o

e

s

u

F

t

i

u

c

r

i

C

r

e

k

a

e

r

B

2

d

l

e

i

F

r

e

w

o

P

e

r

i

W

e

z

i

S

2

d

n

u

o

r

G

e

r

i

W

e

z

i

S

3

m

u

m

i

n

i

M

t

i

u

c

r

i

C

y

t

i

c

a

p

m

A

1

m

u

m

i

x

a

M

l

a

n

r

e

t

x

E

r

o

e

s

u

F

t

i

u

c

r

i

C

r

e

k

a

e

r

B

2

d

l

e

i

F

r

e

w

o

P

e

z

i

S

e

r

i

W

2

d

n

u

o

r

G

e

z

i

S

e

r

i

W

.

t

k

C

A

.

t

k

C

B

.

t

k

C

A

.

t

k

C

B

.

t

k

C

A

.

t

k

C

B

.

t

k

C

A

.

t

k

C

B

Z

0

A

,

0

0

A

-

1

1

6

H

W

5

0

A

8

0

A

0

1

A

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1

2

r

o

1

2

r

o

1

2

r

o

1

2

5

4

7

8

8

8

9

0

6

0

0

1

0

1

1

0

2

1

6
4
3
3

0

1

8
6
6

-

-

-

2

5

2

5

2

5

-

-

-

6

2

2

4

2

5

-

-

-

0

6

0

6

0

6

-

-

-

0

3

0

5

0

6

-

-

-

6
6
6

-

-

-

0

1

8
6

-

-

-

0

1

0

1

0

1

-

-

-

0

1

0

1

0

1

Z

0

B

,

0

0

B

-

1

1

6

H

W

9

0

B

1

-

8

0

2

/

0

3

2

1

-

8

0

2

/

0

3

2

1
1

6

3

0

6

0

5

0

7

8
6

0

1

0

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Z

0

C

,

0

0

C

-

1

1

6

H

W

9

0

C

3

-

0

6

4

3

-

0

6

4

1
1

8

1

2

3

5

2

5

3

0

1

8

0

1

0

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Содержание WH611

Страница 1: ...ATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Model WH611 Manual 2100 347F Supersedes 2100 347E File Volume III Tab 17 Date 03 27 06 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving...

Страница 2: ...3 Table 10 Maximum ESP of Operation 23 Table 11 Pressure Table Cooling 24 Table 12 Pressure Table Heating 24 Getting Other Information and Publications For More Information 3 Wall Mount General Heat P...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...43 3 Ton 49 4 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate C Commercial Ventilator Motorized w o...

Страница 5: ...n U h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B 1 1 6 H W 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 5 1 8 7 9 2 8 7 3 4 9 1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4...

Страница 6: ...rmation on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct...

Страница 7: ...Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be...

Страница 8: ...or vented type system to assure proper drainage FIGURE 3 CONDENSATE DRAINS MIS 1278 CONDENSER CONDENSATE DRAIN EVAPORATOR CONDENSATE DRAIN CONDENSATE DRAIN CONDENSER A hole is provided in the unit bas...

Страница 9: ...h clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 4 and 5 for details WARNING Failure...

Страница 10: ...Manual 2100 347F Page 10 of 24 FIGURE 4 MOUNTING INSTRUCTIONS MIS 796...

Страница 11: ...RNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 i...

Страница 12: ...G WALL STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FIN...

Страница 13: ...Manual 2100 347F Page 13 of 24 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS 550...

Страница 14: ...the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capabilit...

Страница 15: ...eat loss calculation of the building are useful in determining the correct set points OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 10 and 11 Heat pump compressor operation at outdoor temperatures...

Страница 16: ...mostat This is done to maximize efficiency by utilizing the heat pump to bring the conditioned space temperature up rather than cycling on the electric heat due a second stage call for heat from the t...

Страница 17: ...d light to activate This is a signal to the operator of the equipment to place system in the emergency heat position TH5220D1151 8403 058 Thermostat Thermostat will display on the screen Em Heat when...

Страница 18: ...ing See the Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is changed or rewired If improper rotation is corrected at this time there wil...

Страница 19: ...ow in operation The second option has no Auto changeover position but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in Heat position the B t...

Страница 20: ...ng for the outdoor ambient to fall into the defrost region FIGURE 15 DEFROST CONTROL BOARD MIS 1174 By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost senso...

Страница 21: ...a l p e R t o n g n i s a h p r e w o P t c e r r o c e s a h p n o D E L d e r r o f k c e h C y l n o s t i n u e s a h p 3 r o t i n o m t i n u e h t o t s d a e l r e w o p o w t h c t i w S r o...

Страница 22: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Страница 23: ...r u t a r e p m e T D O 2 8 e r u t a r e p m e T 1 1 6 H W 0 5 3 1 1 5 8 4 3 5 0 5 TABLE 10 MAXIMUM ESP OF OPERATION d e e p S h g i H d e e p S m u i d e M 5 0 A 8 0 A 0 1 A 3 3 3 3 3 3 9 0 B 3 3 9...

Страница 24: ...i S h g i H 9 6 1 8 1 0 7 7 0 2 2 7 9 2 2 3 7 7 4 2 5 7 1 6 2 6 7 2 7 2 6 7 8 7 2 7 7 1 8 2 8 7 0 8 2 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 7 7 8 1 2 7 4 1 2 5 7 7 3 2 6 7 6 5 2...

Отзывы: