There is a cycle speed up jumper on the control.  This
can be used to reduce the time between defrost cycle
operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or
another ¼ inch QC, to short between the 

SPEEDUP

terminals to accelerate the HPC timer and initiate
defrost.

Be careful not to touch any other terminals with the
instrument used to short the 

SPEEDUP

 terminals.  It

may take up to 10 seconds with the 

SPEEDUP

terminals shorted for the speedup to be completed and
the defrost cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminals.

Otherwise the timing will remain accelerated and run
through the 1-minute minimum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.

There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a 0° coil temperature.

FIGURE  13

DEFROST CONTROL BOARD

This can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.

By placing a jumper across the 

SEN JMP

 terminals (a

¼ inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out and will
activate the timing circuit.  This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.

In order to terminate the defrost test the 

SEN JMP

jumper must be removed.  If left in place too long, the
compressor could stop due to the high pressure control
opening because of  high pressure condition created by
operating in the cooling mode with outdoor fan off.
Pressure will rise fairly fast as there is likely no actual
frost on the outdoor coil in this artificial test condition.

There is also a 5-minute compressor time delay function
built into the HPC.  This is to protect the compressor from
short cycling conditions.  In some instances, it is helpful to
the service technician to override or speed up this timing
period, and shorting out the 

SPEEDUP

 terminals for a few

seconds can do this.

Содержание WH423

Страница 1: ...MOUNTED PACKAGE HEAT PUMPS Models WH423 WH483 WH604 INSTALLATION INSTRUCTIONS Manual 2100 487 Supersedes NEW File Volume III Tab 17 Date 01 04 08 Bard Manufacturing Company Inc Bryan Ohio 43506 Since...

Страница 2: ...21 Removal of Fan Shroud 21 Refrigerant Charge 21 Pressure Chart 22 23 Optional Accessories 23 Figures Figure 1 Unit Dimensions 5 Figure 2 Blower Damper Assembly 8 Figure 3 Mounting Instructions 10 Fi...

Страница 3: ...Summer Air Manual N Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Co...

Страница 4: ...6 0 0 2 1 5 1 4 5 0 0 4 8 3 2 6 3 0 0 2 1 5 2 1 3 0 0 4 8 3 0 8 1 0 0 2 1 5 8 1 3 3 4 0 0 4 1 6 5 7 3 0 5 0 6 4 0 2 2 3 8 0 5 2 8 6 1 2 7 0 0 2 1 5 VENTILATION OPTIONS X Barometric Fresh Air Damper St...

Страница 5: ...Manual 2100 487 Page 5 of 23 FIGURE 1 UNIT DIMENSIONS...

Страница 6: ...1 0 1 Z 0 B 0 0 B 3 8 4 H W 6 0 B 3 9 0 B 5 1 B 8 1 B 3 8 0 2 0 3 2 1 1 1 1 1 5 2 3 4 2 5 2 5 0 6 5 3 0 5 0 6 0 6 0 6 8 8 6 6 6 0 1 0 1 0 1 0 1 0 1 A N A N A N A N A N A N A N A N A N A N A N A N A N...

Страница 7: ...rs of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent conde...

Страница 8: ...cost of operation information as required for Department of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency The bl...

Страница 9: ...pening would then be 32 x 12 See Figures 3 3A and 5 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom mounting bracket 5 Hook top rain f...

Страница 10: ...Air Opening Wall Circuit breaker access door Heater access panel Note It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under top flashing at time of i...

Страница 11: ...00 487 Page 11 of 23 FIGURE 5 WALL MOUNTINGINSTRUCTIONS FIGURE 4 WALL MOUNTINGINSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT D...

Страница 12: ...Manual 2100 487 Page 12 of 23 FIGURE 6 COMMONWALL MOUNTINGINSTALLATIONS...

Страница 13: ...pacity This means that the field wiring used must be sized to carry that amount of current Depending on the installed KW of electric heat there may be two field power circuits required If this is the...

Страница 14: ...ent heater operation during low temperature cooling operation FIGURE 8 COMPRESSOR CUTOFF THERMOSTAT WIRING 4 10KW 1PH 6 9KW 3 PH FIGURE 9 COMPRESSOR CUTOFF THERMOSTAT WIRING 15 20KW 1 PH 3 PH Temperat...

Страница 15: ...a u n a M r o o t u A ELECTRIC HEAT HOLD OFF SEE FIGURES 10 AND 11 In other applications it is desirable to disable the operation of the electric heat until outdoor temperatures have reached a certai...

Страница 16: ...e the Phase Monitor later in this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no negativ...

Страница 17: ...utdoor motor R G also make starting indoor blower motor Heat pump heating cycle now in operation The second option has no Auto changeover position but instead energizes the reversing valve solenoid co...

Страница 18: ...temperature FIGURE 13 DEFROST CONTROL BOARD This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region By placing a jumper across...

Страница 19: ...i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c y...

Страница 20: ...4 0 7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4...

Страница 21: ...0 0 5 1 0 0 8 1 5 6 6 1 0 4 5 1 0 0 4 1 0 0 6 1 5 2 5 1 0 5 4 1 5 7 3 1 0 0 2 2 0 0 1 2 0 0 0 2 5 7 8 1 0 0 0 2 0 0 9 1 0 0 8 1 0 0 7 1 4 5 0 0 3 1 5 7 1 1 0 7 3 1 0 5 2 1 5 8 2 1 0 5 1 1 5 7 7 1 0 5...

Страница 22: ...1 1 3 2 4 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 2 7 1 1 2 3 7 6 2 2 5 7 1 4 2 6 7 6 5 2 8 7 2 7 2 9 7 8 8 2 0 8 4 0 3 2 8 1 2 3 4 8 7 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w...

Страница 23: ...g a k c a P r e t a e H s e g a k c a P r e t a e H s e g a k c a P r e t a e H s e g a k c a P r e t a e H X X X X 0 2 A 4 0 H W H E 9 0 B 4 0 H W H E 5 1 B 4 0 H W H E s e g a k c a P r e t a e H s...

Отзывы: